Our advantage
Global Logistics
We have a 10-year logistics and express cooperation agreement, so our products can be shipped to any place in the world.
Brand new and original
Our products are imported in bulk from the place of origin. Because of the cooperative relationship, our products are all original and 100% new.
24-hour service
We provide 7*24 hours service to our customers. We will be there whenever you need us.
Price advantage
All our products are priced very favorably because we have our own warehouse and supply.
| Company Information | |||
| [email protected] | |||
| Mobile | +8615980777398 | ||
| +8615980777398 | |||
| 15980777398 |

The Siemens 6AG1305-1BA80-2AA0 Power Supply Module is a SIPLUS version of the SIMATIC S7-300 PS 305 stabilized power supply. It is designed to convert a wide range of DC input voltages into a regulated 24 V DC output for industrial automation equipment.
Unlike conventional AC-input power supplies, the PS 305 accepts DC input. Its rated input voltage options cover 24 V, 48 V, 72 V, 96 V, and 110 V DC, with an overall specified input range of 16.8–138 V DC. The module provides a rated output current of 2 A at 24 V DC, making it suitable for powering compatible control-system loads.
The 6AG1305-1BA80-2AA0 belongs to the Siemens SIPLUS product range. It is based on the standard SIMATIC S7-300 PS 305 design and incorporates conformal coating intended to improve its suitability for demanding environmental conditions. The specified temperature range is −25 to +60 °C, subject to the applicable installation and operating conditions.
In an industrial control cabinet, a stable 24 V DC supply is essential for the operation of many automation components. Sensors, control circuits, interface devices, and other low-voltage equipment may depend on a reliable DC supply. The PS 305 provides a regulated output that can support these loads when their combined current requirements remain within the module’s rating.
The module also includes electronic short-circuit protection and output-voltage indication. These functions help maintenance personnel identify supply conditions and respond to certain electrical faults.
When selecting this module, it is important to distinguish it from the standard 6ES7305-1BA80-0AA0 PS 305. Although the two products are related, the SIPLUS version has additional environmental protection characteristics. The complete order number should be checked when replacing an existing unit.
| Parameter | Specification |
|---|---|
| Brand | Siemens |
| Product Series | SIPLUS SIMATIC S7-300 |
| Model | 6AG1305-1BA80-2AA0 |
| Product Type | PS 305 Stabilized Power Supply Module |
| Power Supply Category | DC Input Power Supply |
| Rated Input Voltage | 24 / 48 / 72 / 96 / 110 V DC |
| Input Voltage Range | 16.8–138 V DC |
| Rated Output Voltage | 24 V DC |
| Rated Output Current | 2 A |
| Output Power | 48 W at 24 V DC and 2 A |
| Output Voltage Tolerance | 24 V ±3% |
| Short-Circuit Protection | Electronic |
| Open-Circuit Protection | Yes |
| Output Voltage Indicator | Green LED |
| Environmental Protection | Conformal coating |
| Operating Temperature Range | −25 to +60 °C |
| Efficiency | Approximately 90% |
| Power Loss | Approximately 27 W |
| Dimensions | 80 × 125 × 120 mm |
| Weight Provided | 0.825 kg |
| Manufacturer Reference Weight | Approximately 0.74 kg |
| Typical Application | SIMATIC S7-300 DC power supply |
Note: The supplied weight is retained for product listing purposes. Siemens documentation specifies approximately 0.74 kg; verify the actual unit and packaging weight before shipment.
The primary function of the PS 305 is to provide a regulated 24 V DC output from a DC input source. It is designed for industrial installations where a suitable DC supply is available and stable low-voltage power is required by automation equipment.
The module accepts several nominal DC input voltages, including 24 V, 48 V, 72 V, 96 V, and 110 V DC. Its specified input voltage range is 16.8–138 V DC.
This broad input range allows the module to be used in installations with different DC distribution arrangements. Before connection, the actual supply voltage must be checked against the permitted input range.
The input circuit processes the incoming DC power and converts it into the regulated output required by connected equipment.
The PS 305 provides a nominal output of 24 V DC with a rated current of 2 A. Its specified output tolerance is 24 V ±3%.
A regulated output is important because industrial control components generally require a stable supply voltage. Excessive voltage variation can cause unstable operation, communication interruptions, or unexpected behavior in connected devices.
The module is designed to maintain the specified output within its rated operating conditions. The total current drawn by connected equipment must remain within the available output capacity.
The module incorporates electronic short-circuit protection. When an output short circuit occurs, the output voltage is interrupted. The power supply can recover automatically after the short-circuit condition has been removed, according to the documented operating behavior.
This function helps protect the power supply and connected circuits from certain abnormal conditions. It does not replace correctly rated upstream protection or proper wiring practices.
A green LED indicates the presence of the 24 V DC output voltage. This visual indication provides a convenient first-level diagnostic reference during installation and maintenance.
If the LED is off, technicians should check the input supply, wiring, protective devices, and output condition. If the indicator flashes, an overload condition may need investigation.
The LED is a basic status indicator rather than a complete diagnostic system. Electrical measurements should be used when troubleshooting supply problems.
The PS 305 provides safety isolation between its input and output circuits. This supports the separation of the incoming DC supply from the 24 V DC load circuit.
Correct grounding and protective-conductor connections remain essential. Installation should follow the manufacturer’s wiring instructions and applicable electrical safety requirements.
A stable 24 V DC supply is a basic requirement in many industrial automation installations. The 6AG1305-1BA80-2AA0 can provide this supply to compatible loads in an S7-300-based control environment.
The PS 305 can be used as a load power supply for suitable control-system equipment. It supports 24 V DC distribution to devices whose voltage and current requirements match the module’s specifications.
When designing a control cabinet, engineers should calculate the total load current rather than selecting a power supply based only on the number of connected devices.
Industrial sensors, proximity switches, and other field devices commonly use 24 V DC. A properly designed distribution circuit can use the PS 305 to supply compatible devices.
The current consumption of each device, cable voltage drop, and any simultaneous operating conditions should be considered when calculating the required capacity.
Interface relays, signal-conditioning devices, and other low-voltage control components may also require 24 V DC. The PS 305 can support these loads when their combined current remains within the rated output.
Separate branch protection and appropriate terminal arrangements should be used where required by the control-system design.
Because the module accepts DC input, it can be considered for installations that distribute power through a DC supply network. This is particularly relevant where the available source is a DC bus or battery-backed DC system.
The input voltage must remain within the module’s permitted range during normal operation and expected supply variations.
The SIPLUS PS 305 is intended for industrial automation installations where regulated 24 V DC power is needed and the available input source is compatible with its DC input range.
The module is associated with the Siemens S7-300 automation environment and can provide 24 V DC power for suitable control-system loads.
It is particularly relevant to maintenance projects involving existing S7-300 installations, where the original power distribution arrangement needs to be retained or restored.
Facilities with DC power distribution may use the PS 305 to convert an available DC supply into a regulated 24 V DC output.
This can simplify the power arrangement for compatible control devices, provided the incoming voltage and available current meet the module’s requirements.
The SIPLUS version is designed with enhanced environmental characteristics and references EN 50155-related requirements. This makes it relevant to selected transportation and railway-related control applications where the complete equipment design and applicable approvals are satisfied.
The module should not be assumed suitable for every railway installation without reviewing the specific environmental, electrical, and certification requirements.
Industrial machines often contain sensors, relays, interface devices, and other control components that operate from 24 V DC.
The PS 305 can support compatible loads in machinery control cabinets. Its suitability depends on the actual load current, input supply, ambient temperature, and installation conditions.
Some automation systems use local DC power conversion near groups of control devices. A PS 305 may be used in such an arrangement when the DC input supply is available and the connected loads are within its rating.
The electrical design should account for cable length, voltage drop, grounding, protective devices, and maintenance access.
Proper installation is necessary to ensure stable output voltage, safe operation, and reliable performance.
Before connecting the module, measure the available DC supply and confirm that it falls within the specified 16.8–138 V DC input range.
The nominal input options are 24 V, 48 V, 72 V, 96 V, and 110 V DC. Confirm the expected operating voltage and supply polarity before wiring.
Incorrect input voltage or polarity can damage the module. Do not connect an AC supply to the DC input terminals.
The module provides 24 V DC at a rated output current of 2 A. The combined current consumption of all connected loads should be calculated before commissioning.
Consider the operating current of sensors, relays, interface equipment, and other devices. Allow suitable capacity for startup conditions and expected load variations.
If the calculated load exceeds the module’s rating, select a power supply with an appropriate capacity rather than operating the PS 305 continuously beyond its specified limits.
The supplied dimensions are 80 × 125 × 120 mm. Confirm the mounting arrangement and available cabinet space before installation.
Provide adequate ventilation and follow the manufacturer’s mounting and clearance instructions. Avoid placing the module near equipment that produces excessive heat or electromagnetic interference.
The conformal coating provides additional protection for electronic assemblies, but it does not make the module waterproof or suitable for unrestricted exposure to corrosive substances.
Connect the input, output, and protective-conductor terminals according to the manufacturer’s wiring diagram.
Use conductors with appropriate cross-sectional areas and insulation ratings. Keep power wiring organized and clearly separated from sensitive signal wiring where required.
Ensure that the protective conductor is connected correctly. A reliable grounding arrangement is important for electrical safety and system performance.
Although the PS 305 includes electronic short-circuit protection, the overall installation still requires suitable upstream protection.
The protective device should be selected according to the input supply, wiring, and manufacturer’s recommendations. Branch protection may also be needed for individual output circuits.
After wiring, verify the input voltage and polarity before energizing the module. Check that the green output indicator illuminates and measure the output voltage.
Connect the intended loads and monitor the output under normal operating conditions. Confirm that the output remains within the specified tolerance and that no abnormal heating or overload indication occurs.
Record the final wiring arrangement and connected load information for future maintenance.
The 6AG1305-1BA80-2AA0 is designed for use in a wider industrial power distribution arrangement. The following components may be used alongside it, depending on the system design.
| Component | Function | Integration Considerations |
|---|---|---|
| SIMATIC S7-300 PLC | Executes automation logic | Verify the power requirements of the CPU and associated modules |
| 24 V DC sensors | Detect machine and process conditions | Confirm voltage and current consumption |
| Interface relays | Switch control signals and loads | Check coil voltage and current |
| Signal-conditioning modules | Adapt field signals for control equipment | Verify the required DC supply |
| DC input source | Supplies the PS 305 input | Must remain within 16.8–138 V DC |
| Circuit breaker | Provides input-side protection | Select according to supply voltage and wiring |
| Terminal blocks | Distribute 24 V DC power | Ensure current ratings and terminal arrangements are suitable |
| Grounding system | Provides protective grounding | Follow electrical safety and installation requirements |
| Control cabinet | Houses automation and power components | Maintain suitable temperature, ventilation, and access |
The listed components are examples of equipment that may form part of an installation. They are not necessarily supplied with the power module.
When replacing the 6AG1305-1BA80-2AA0, the closest technical reference is the standard Siemens PS 305 model on which the SIPLUS version is based. However, the two products should not be treated as identical in environmental protection.
| Related Model or Option | Description | Replacement Considerations |
|---|---|---|
| Siemens 6ES7305-1BA80-0AA0 | Standard SIMATIC S7-300 PS 305 power supply | Similar basic DC input and 24 V DC / 2 A output; compare environmental requirements |
| Siemens 6AG1305-1BA80-2AA0 | SIPLUS S7-300 PS 305 | Original model with conformal coating and enhanced environmental characteristics |
| Siemens 6AG1307 series | SIPLUS S7-300 power supply options | Check output current, input type, and mechanical compatibility |
| Siemens SITOP DC power supplies | Industrial regulated power supply family | May be suitable for a redesigned installation, but not necessarily a direct replacement |
Before selecting an alternative, compare:
A replacement with a different input type or output rating may require wiring and cabinet modifications. For transportation or other demanding environments, verify the applicable environmental and certification requirements before substituting a standard power supply.
The PS 305 accepts nominal DC input voltages from 24 V to 110 V and has a specified operating range of 16.8–138 V DC. This supports installations using different DC distribution levels.
The module provides a stable 24 V DC output with a rated current of 2 A, suitable for compatible industrial control loads.
Its conformal coating and specified −25 to +60 °C operating temperature range make the SIPLUS version relevant to installations with more demanding environmental conditions than typical indoor control cabinets.
The electronic protection function helps manage output short-circuit conditions and supports automatic recovery after the fault is removed, according to the documented operating behavior.
The green LED provides a simple visual indication of output voltage availability, helping technicians perform initial checks during commissioning and maintenance.
The module provides electrical isolation between the input and output circuits, supporting the separation of the incoming DC supply from the 24 V load circuit.
The PS 305 is associated with the SIMATIC S7-300 environment and can be used in compatible industrial control cabinets and maintenance projects.
It is a SIPLUS SIMATIC S7-300 PS 305 stabilized power supply module. It converts DC input power into a regulated 24 V DC output for compatible industrial control equipment.
It supports nominal input voltages of 24 V, 48 V, 72 V, 96 V, and 110 V DC. The documented operating range is 16.8–138 V DC.
The module provides 24 V DC at a rated output current of 2 A, equivalent to 48 W at the nominal output rating.
No. The 6AG1305-1BA80-2AA0 is a DC-input power supply module. It should only be connected to a compatible DC source within its specified input range.
Both are related to the PS 305 2 A power supply design. The 6AG1305-1BA80-2AA0 is the SIPLUS version and includes conformal coating and enhanced environmental characteristics. The standard 6ES7305-1BA80-0AA0 does not provide the same SIPLUS environmental configuration.
Yes. It includes electronic short-circuit protection. The output is interrupted under a short-circuit condition and can recover automatically after the fault is removed, according to the documented behavior.
Yes, provided the devices require 24 V DC and their combined current consumption remains within the module’s rated output capacity. Check the startup current and operating current of every connected device.
The green LED indicates that the 24 V DC output voltage is present. If it is off or flashing, technicians should investigate the input supply, output load, and wiring conditions.
The SIPLUS version is specified for an operating temperature range of −25 to +60 °C. Actual suitability depends on the complete installation and applicable operating conditions.
Verify the complete order number, input voltage, output current, physical dimensions, terminal arrangement, environmental requirements, and condition of the unit. If replacing a SIPLUS module, confirm whether the standard version provides sufficient environmental protection for the application.
When purchasing the Siemens 6AG1305-1BA80-2AA0, confirm that the complete SIPLUS order number matches the equipment specification. Do not confuse it with the standard 6ES7305-1BA80-0AA0, even though the two models share the PS 305 design.
For replacement projects, verify the DC input supply, output current requirement, mounting arrangement, terminal connections, and environmental conditions. The 2 A output rating should be compared with the combined current consumption of all connected loads.
For used or surplus units, inspect the housing, terminals, connectors, and visible condition of the electronic assembly. Request clear nameplate photographs and functional test information where possible. Confirm whether the quoted weight refers to the module alone or includes packaging.
During maintenance, inspect wiring and grounding connections, check the input supply, measure the 24 V DC output, and monitor the connected load. Investigate repeated overload indications rather than allowing the module to operate continuously under abnormal conditions.
Keep the power supply clean and maintain suitable ventilation around the installed equipment. Record the connected loads and final wiring arrangement so that future replacement and troubleshooting can be performed accurately.
The Siemens 6AG1305-1BA80-2AA0 SIPLUS S7-300 PS 305 is a stabilized DC power supply module designed to convert a wide range of DC input voltages into a regulated 24 V DC output at 2 A. Its conformal coating and specified operating temperature range make it suitable for selected industrial installations requiring enhanced environmental characteristics.
With electronic short-circuit protection, output-voltage indication, and electrical isolation, the module supports dependable 24 V DC power distribution for compatible automation equipment. For maintenance and replacement applications, verifying the complete SIPLUS order number, DC input range, output load, and environmental requirements is essential for ensuring correct system integration.