• Schneider TM2ARI8LT Modicon M238 Analog Input Module
  • Schneider TM2ARI8LT Modicon M238 Analog Input Module
  • Schneider TM2ARI8LT Modicon M238 Analog Input Module
  • Schneider TM2ARI8LT Modicon M238 Analog Input Module
Product Overview The Schneider Electric TM2ARI8LT is an 8-channel temperature input expansion module for the Modicon M238 logic controller. It is used to acquire temperature measurements from PT100 and ……
Schneider TM2ARI8LT Modicon M238 Analog Input Module
  • Schneider
  • TM2ARI8LT
  • Analog Input Module
  • France
  • 90 × 70 × 90 mm
  • 0.19 kg
  • Xiamen, China
  • New & In Stock
  • T/T, PayPal, Western Union
  • 1 Year
  • 1-3 Working Days
  • DHL, UPS, TNT, FedEx and EMS.
  • 24-Hour Service
  • COO
  • 7

Our advantage

Schneider TM2ARI8LT Modicon M238 Analog Input Module

Global Logistics

We have a 10-year logistics and express cooperation agreement, so our products can be shipped to any place in the world.

Schneider TM2ARI8LT Modicon M238 Analog Input Module

Brand new and original

Our products are imported in bulk from the place of origin. Because of the cooperative relationship, our products are all original and 100% new.

Schneider TM2ARI8LT Modicon M238 Analog Input Module

24-hour service

We provide 7*24 hours service to our customers. We will be there whenever you need us.

Schneider TM2ARI8LT Modicon M238 Analog Input Module

Price advantage

All our products are priced very favorably because we have our own warehouse and supply.


Company Information
E-mail [email protected]
Mobile +8615980777398
Whatsapp +8615980777398
WeChat 15980777398

Product Overview

The Schneider Electric TM2ARI8LT is an 8-channel temperature input expansion module for the Modicon M238 logic controller. It is used to acquire temperature measurements from PT100 and PT1000 resistance temperature detectors (RTDs), allowing the PLC to monitor multiple temperature points within a machine or industrial process.

Unlike general-purpose analog input modules that accept standard voltage or current signals, the TM2ARI8LT is specifically configured for resistance temperature measurement. It supports PT100 probes over a range of -200 to 600°C and PT1000 probes over a range of -50 to 200°C.

This configuration is useful in applications where several temperature measurement points must be monitored by one controller. For example, an industrial heating system may require separate measurements from heating chambers, process pipes, fluid tanks, and equipment surfaces. The TM2ARI8LT collects these sensor signals and transfers the measured values to the PLC for processing.

The module uses 12-bit conversion resolution and provides eight independent temperature input channels. Its self-scanning acquisition arrangement allows the controller to receive measurements from multiple connected probes without requiring a separate temperature transmitter for every measurement point.

The TM2ARI8LT also supports broken-wire detection and out-of-range detection. These functions help identify sensor connection problems and abnormal measurement conditions during machine operation.

Electrical isolation between the input circuitry and internal logic is provided through photocoupler-based isolation. The module uses an external 24 V DC supply and two removable screw terminal blocks, one for sensor connections and another for power supply wiring.

For existing Modicon M238 installations, the TM2ARI8LT is particularly useful when additional RTD temperature measurement channels are required without changing the main PLC configuration.


Technical Specifications

Parameter Specification
Manufacturer Schneider Electric
Model TM2ARI8LT
Product Series Modicon M238
Product Type Analog Input Module
Number of Analog Inputs 8
Input Type Temperature Probe / RTD
Supported Sensor Types PT100 / PT1000
PT100 Measurement Range -200 to 600°C
PT1000 Measurement Range -50 to 200°C
Analog Input Resolution 12 bits
PT100 LSB Value 0.2°C
PT1000 LSB Value 0.006°C
Input Impedance ≥ 10 kΩ
Sampling Duration ≤ 160 ms
Acquisition Period 320 ms per channel group + 1 controller cycle
Measurement Error (PT100) ±0.5% FS at 25°C
Measurement Error (PT1000) ±0.3% FS at 25°C
Temperature Coefficient ±0.01% FS/°C
Repeat Accuracy ±0.1°C
Total Error (PT100) 4°C
Total Error (PT1000) 1°C
Broken-Wire Detection Yes
Out-of-Range Detection Yes
Isolation Type Photocoupler
External Supply Voltage 24 V DC
Supply Voltage Limits 19.2–30 V DC
Internal Current Consumption 90 mA at 5 V DC
External Current Consumption ≤ 140 mA at 24 V DC
Electrical Connection 2 Removable Screw Terminal Blocks
Mounting Type DIN Rail / Panel Mounting
Dimensions 90 × 70 × 90 mm
Weight 0.19 kg

Product Features

  • Eight Temperature Input Channels: Supports simultaneous acquisition from eight PT100 or PT1000 temperature probes.
  • PT100 Measurement Capability: Measures temperatures from -200 to 600°C, covering a broad range of industrial heating and process applications.
  • PT1000 Sensor Support: Accepts PT1000 probes over a measurement range of -50 to 200°C.
  • 12-Bit Conversion Resolution: Converts temperature measurements into digital values for PLC processing.
  • Broken-Wire Detection: Identifies disconnected temperature sensor wiring to assist fault diagnosis.
  • Out-of-Range Detection: Helps identify measurements outside the configured sensor operating range.
  • Photocoupler Isolation: Provides electrical isolation between the input circuitry and the controller’s internal logic.
  • External 24 V DC Supply: Uses a dedicated external supply within the specified voltage limits.
  • Removable Terminal Blocks: Provides separate terminal connections for sensor wiring and module power.
  • Multiple Controller Applications: Listed compatibility includes Modicon M238, Twido, and Advantys OTB configurations.

Product Working Principle

The TM2ARI8LT measures temperature by monitoring the resistance changes of connected PT100 or PT1000 sensors.

An RTD sensor changes its electrical resistance according to temperature. The module measures this resistance-related signal and converts it into a digital temperature value that can be processed by the PLC.

For example, in an industrial heating system, PT100 probes may be installed at different positions inside a heating chamber. As the temperature changes, the resistance of each probe changes accordingly. The TM2ARI8LT acquires these signals through its eight input channels and converts them into digital measurement values.

The PLC program can then compare the measured temperatures with configured setpoints. If a heating zone falls below its target temperature, the controller can activate the corresponding heating output. If a temperature exceeds the permitted operating range, the control program can initiate an alarm or protective action.

The module supports two sensor types:

  • PT100: Suitable for a wider temperature range, from -200 to 600°C.
  • PT1000: Suitable for temperature measurement from -50 to 200°C, with a smaller LSB value.

Each channel must be configured according to the actual sensor type. Selecting PT1000 in the programming software while connecting a PT100 sensor, or vice versa, can produce incorrect measurement results.

A simplified signal path is:

PT100 / PT1000 Sensors → TM2ARI8LT → Resistance Measurement and Conversion → Digital Temperature Values → Modicon PLC → Heating / Cooling Control

The module uses a self-scanning acquisition method. It continuously acquires temperature information from the connected channels and transfers the resulting values to the controller.

Broken-wire and out-of-range detection provide additional diagnostic information. These functions are useful when a sensor becomes disconnected or when the measured temperature exceeds the supported measurement range.


Role in Schneider Electric Modicon M238 Control Architecture

Within the Modicon M238 architecture, the TM2ARI8LT functions as a dedicated temperature acquisition module. It extends the controller’s ability to monitor multiple RTD measurement points through a single expansion module.

The M238 controller executes the main control program, while the TM2ARI8LT handles the acquisition and conversion of temperature signals. This arrangement separates temperature measurement from the main logic-processing function.

A typical temperature control arrangement is:

PT100 / PT1000 Sensors → TM2ARI8LT → Modicon M238 Controller → Heating Elements / Cooling Equipment

System Component Function
Schneider Electric TM2ARI8LT Acquires temperature signals from eight PT100/PT1000 sensors
Schneider Electric Modicon M238 Processes temperature values and executes control logic
Schneider Electric TM2AMI4LT Provides additional analog input channels for temperature and other supported signals
Schneider Electric TM2ARI8LRJ Provides eight RTD input channels using RJ11 connections
Schneider Electric TM2ARI8HT Provides temperature-related input channels for NTC/PTC sensors
Schneider Electric Heating Controller Regulates heating equipment according to temperature setpoints
Industrial Temperature Sensors Measures process, equipment, or ambient temperature
Cooling System Reduces process temperature according to controller commands

The TM2ARI8LT is particularly suitable when multiple temperature measurement points must be integrated into an existing M238-based machine control system.


Industrial Applications

The TM2ARI8LT is suitable for industrial equipment that requires multi-point temperature monitoring using PT100 or PT1000 resistance temperature detectors.

Industrial Application Typical Use
Industrial Ovens Monitoring temperatures at multiple heating zones
Heat Treatment Equipment Measuring furnace and workpiece temperatures
Plastic Processing Monitoring barrel, mold, and heating-zone temperatures
Food Processing Monitoring temperatures in cooking, heating, and processing equipment
Chemical Processing Measuring temperatures in tanks, pipes, and process vessels
HVAC Systems Monitoring temperature at multiple points in heating and cooling equipment
Pharmaceutical Equipment Acquiring temperature measurements in controlled processing systems
Industrial Dryers Monitoring heating chambers and drying zones
Water Treatment Measuring temperatures in tanks and process pipelines
Manufacturing Equipment Monitoring motor, machine, and process temperatures

Installation and Maintenance

  1. Verify Sensor Compatibility: Confirm whether each connected temperature probe is PT100 or PT1000 before wiring the module.
  2. Prepare the Mounting Position: Select a suitable DIN rail or panel mounting location with sufficient space for terminal access and cable routing.
  3. Inspect the Module: Check the housing, expansion interface, and removable terminal blocks for physical damage.
  4. Install the Module: Secure the TM2ARI8LT in the designated expansion position and verify that the connection to the controller system is properly engaged.
  5. Check External Power: Prepare a 24 V DC supply within the specified 19.2–30 V operating range.
  6. Identify Sensor Channels: Assign each temperature probe to the correct input channel and document its physical measurement location.
  7. Connect RTD Sensors: Wire the PT100 or PT1000 probes according to the manufacturer’s terminal diagram and the applicable sensor wiring arrangement.
  8. Configure Sensor Types: Select PT100 or PT1000 separately for the corresponding channels in the programming software.
  9. Check Measurement Scaling: Verify the configured temperature range and ensure that the PLC application interprets the input values correctly.
  10. Test Sensor Readings: Compare the displayed temperature values with a suitable reference thermometer or calibrated measurement instrument.
  11. Check Diagnostic Functions: Verify broken-wire and out-of-range detection during controlled testing before returning the equipment to normal operation.
  12. Perform Routine Inspection: Inspect sensor cables, terminal connections, external power stability, and measurement consistency during scheduled maintenance.

When troubleshooting inaccurate temperature readings, first check the selected sensor type and wiring arrangement. PT100 and PT1000 probes have different resistance characteristics, so an incorrect software configuration can result in significant measurement errors.


Compatible System Components

Component Function
Schneider Electric Modicon M238 Main logic controller for the TM2 expansion system
Schneider Electric TM2ARI8LT Eight-channel PT100/PT1000 temperature input module
Schneider Electric TM2AMI4LT Four-channel analog input module supporting temperature and other analog signals
Schneider Electric TM2ARI8LRJ Eight-channel PT100/PT1000 input module with RJ11 connections
Schneider Electric TM2ARI8HT Eight-channel NTC/PTC temperature input module
Schneider Electric Modicon Twido Compatible controller family listed for the module
Schneider Electric Advantys OTB Compatible distributed I/O platform
PT100 Temperature Probes Resistance temperature sensors for industrial measurement
PT1000 Temperature Probes Higher-resistance RTD sensors for temperature acquisition
Industrial Heating Equipment Provides temperature regulation according to PLC commands

Recommended Related Models

Model / Product Product Type Typical Application
Schneider TM2ARI8LRJ Modicon TM2 Analog Input Module Eight-channel PT100/PT1000 temperature measurement with RJ11 connection
Schneider TM2ARI8HT Modicon TM2 Analog Input Module Eight-channel NTC/PTC temperature acquisition
Schneider TM2AMI4LT Modicon TM2 Analog Input Module Four-channel temperature and analog signal acquisition
Schneider TM2AMI2LT Modicon TM2 Analog Input Module Two-channel thermocouple temperature input
Schneider TM2AMI8HT Modicon TM2 Analog Input Module Eight-channel voltage/current signal acquisition
Schneider TM2ALM3LT Modicon TM2 Analog Mixed I/O Module Low-level temperature input and analog output applications

Key Advantages

  • Eight independent RTD temperature input channels.
  • Supports PT100 and PT1000 temperature probes.
  • PT100 measurement range up to 600°C.
  • PT1000 measurement range up to 200°C.
  • 12-bit temperature conversion resolution.
  • Broken-wire and out-of-range detection.
  • Photocoupler isolation from internal logic.
  • External 24 V DC power supply.
  • Removable screw terminal connections.

Technical FAQs

1. Can the TM2ARI8LT accept both PT100 and PT1000 sensors?

Yes. The module supports both sensor types. Each input channel must be configured for the corresponding sensor type in the programming software. PT100 supports -200 to 600°C, while PT1000 supports -50 to 200°C.

2. What is the difference between the TM2ARI8LT and TM2ARI8LRJ?

Both modules provide eight temperature input channels for PT100/PT1000 sensors. The main difference is their electrical connection arrangement. The TM2ARI8LT uses removable screw terminal blocks, whereas the TM2ARI8LRJ uses RJ11 connectors.

3. Does the TM2ARI8LT detect a disconnected temperature probe?

Yes. The module supports broken-wire detection, allowing the controller application to identify a disconnected sensor. This diagnostic capability is useful for detecting wiring faults during operation.

4. Can the TM2ARI8LT measure standard 0–10 V or 4–20 mA signals?

No. The TM2ARI8LT is specifically intended for PT100 and PT1000 temperature probes. For standard voltage or current measurements, a compatible high-level analog input module such as the TM2AMI8HT should be selected instead.



Related Products

Get the latest price? We will reply as soon as possible (within 12 hours)

No:77501