Product Overview The Honeywell CP-DYNB-2DI is a 32-channel Digital Input Backplane belonging to the MTL CP-DYN interface assembly family. It provides the field termination and electrical connection arra……
Honeywell CP-DYNB-2DI Digital Input Backplane
  • Honeywell
  • CP-DYNB-2DI
  • Digital Input Backplane
  • USA
  • 308 × 30 × 128.3 mm
  • 1.36 kg
  • Xiamen, China
  • New & In Stock
  • T/T, PayPal, Western Union
  • 1 Year
  • 1-3 Working Days
  • DHL, UPS, TNT, FedEx and EMS.
  • 24-Hour Service
  • COO
  • 6

Our advantage

Honeywell CP-DYNB-2DI Digital Input Backplane

Global Logistics

We have a 10-year logistics and express cooperation agreement, so our products can be shipped to any place in the world.

Honeywell CP-DYNB-2DI Digital Input Backplane

Brand new and original

Our products are imported in bulk from the place of origin. Because of the cooperative relationship, our products are all original and 100% new.

Honeywell CP-DYNB-2DI Digital Input Backplane

24-hour service

We provide 7*24 hours service to our customers. We will be there whenever you need us.

Honeywell CP-DYNB-2DI Digital Input Backplane

Price advantage

All our products are priced very favorably because we have our own warehouse and supply.


Company Information
E-mail [email protected]
Mobile +8615980777398
Whatsapp +8615980777398
WeChat 15980777398

Product Overview

The Honeywell CP-DYNB-2DI is a 32-channel Digital Input Backplane belonging to the MTL CP-DYN interface assembly family. It provides the field termination and electrical connection arrangement for compatible MTL4500-series intrinsic safety interface modules, allowing discrete field signals to be transferred to a distributed control system (DCS) or programmable logic controller (PLC).

The CP-DYNB-2DI uses a Size B configuration and supports MTL4513, MTL4516, and MTL4517 interface modules. Its 32-channel arrangement accommodates a larger number of discrete input signals within a single field termination assembly, making it suitable for process installations with extensive equipment status and condition monitoring requirements.

In industrial automation systems, digital input signals are commonly generated by limit switches, proximity sensors, pressure switches, level switches, and other field devices. These signals indicate operating states such as equipment running, valve position, pressure conditions, and fault status. The CP-DYNB-2DI provides the connection platform through which these signals are organized and routed to the associated control system.

The backplane uses Tyco Dynamic 20-pin connectors for connections between the field termination assembly and the control system interface card. This cable-connected arrangement allows the intrinsic safety interfaces to be installed remotely from the main control system while maintaining an organized signal connection structure.

For system expansion and replacement projects, the CP-DYNB-2DI is particularly relevant when additional digital input channels are required without redesigning the entire field interface arrangement. Its compatibility with the designated MTL interface modules must be considered when selecting a replacement.


Technical Specifications

Parameter Specification
Manufacturer Honeywell / MTL
Model CP-DYNB-2DI
Product Series CP-DYN
Product Type Digital Input Backplane
Product Range MTL4500
Signal Type Digital Input
Channel Configuration 32 Channels
Module Size Size B
Compatible Interface Modules MTL4513, MTL4516, MTL4517
Connector Type Tyco Dynamic 20-Pin Connector
Mounting Type Surface Mounting / DIN Rail Mounting
Interface Function Field Termination Assembly
Application Intrinsic Safety Signal Interface
Dimensions 308 × 30 × 128.3 mm
Weight 1.36 kg

Product Features

  • 32-Channel Digital Input: Accommodates 32 discrete input channels for monitoring multiple field devices.
  • Size B Configuration: Uses the Size B arrangement within the MTL CP-DYN backplane family.
  • MTL4500 Compatibility: Supports designated MTL4513, MTL4516, and MTL4517 interface modules.
  • Tyco Dynamic Connectors: Uses 20-pin Dynamic connectors for connections between the FTA and control system interface card.
  • Remote Field Termination: Allows intrinsic safety interfaces to be installed separately from the main control system.
  • Grouped Signal Connections: Consolidates multiple digital input connections within a common interface assembly.
  • Flexible Mounting: Supports surface mounting and installation using the designated DIN rail mounting kit.
  • Industrial Signal Monitoring: Suitable for collecting discrete operating and equipment status signals in process automation systems.

Product Working Principle

The CP-DYNB-2DI functions as a field termination and connection platform for digital input signals within an industrial automation system.

Field devices such as proximity switches, limit switches, pressure switches, and level switches generate discrete electrical signals according to their operating conditions. These signals are connected to the corresponding MTL4513, MTL4516, or MTL4517 interface modules installed in the backplane arrangement.

The MTL interface modules provide the designated signal isolation and conditioning functions. The CP-DYNB-2DI organizes the electrical connections and provides the interface between these modules and the control system.

A simplified signal arrangement is:

Field Switches and Sensors → MTL4513 / MTL4516 / MTL4517 Interface Modules → CP-DYNB-2DI → Tyco Dynamic Cable → DCS / PLC Digital Input System

During operation, changes in the states of field devices are transferred through the corresponding interface channels. The control system receives these discrete signals and uses them for equipment monitoring, interlocking, alarm processing, and programmed control sequences.

For example, a limit switch installed on an industrial valve can report whether the valve has reached its open or closed position. The corresponding digital input signal passes through the field interface arrangement and reaches the control system for status monitoring.

The backplane does not independently execute control logic or perform the complete signal isolation function. Its primary role is to provide the physical and electrical connection arrangement for the compatible interface modules.


Role in Honeywell / MTL Control Architecture

Within the MTL CP-DYN architecture, the CP-DYNB-2DI serves as a 32-channel digital input Field Termination Assembly (FTA). It connects compatible MTL4500 interface modules with the control system through a dedicated multiway cable connection.

Its Size B configuration accommodates the designated interface modules and groups multiple discrete field signals into a common connection assembly.

A typical connection arrangement is:

Field Devices → MTL4500 Digital Input Interfaces → CP-DYNB-2DI → CABDYN20 Cable → DCS / PLC System Card

System Component Function
CP-DYNB-2DI Provides the 32-channel digital input field termination arrangement
MTL4513 Compatible digital input interface module
MTL4516 Compatible digital input interface module
MTL4517 Compatible digital input interface module
CABDYN20 Cable Connects the FTA to the control system interface card
DCS Controller Processes discrete field status information
PLC Controller Executes programmed logic and equipment interlocks
Limit Switches Detect mechanical position and movement
Proximity Sensors Detect the presence or position of objects
Pressure Switches Report discrete pressure conditions
Level Switches Monitor high-level and low-level conditions

Industrial Applications

The CP-DYNB-2DI is suitable for industrial installations requiring a high-density digital input interface for equipment status monitoring and process condition detection.

Industrial Application Typical Use
Oil and Gas Processing Monitoring valve positions, equipment status, and process switches
Petrochemical Plants Collecting discrete signals from field instruments and machinery
Chemical Processing Monitoring equipment interlocks and operating conditions
Power Generation Acquiring switch status and auxiliary equipment signals
Water Treatment Monitoring pump operation, tank level switches, and valve positions
Pharmaceutical Manufacturing Collecting equipment status and process interlock signals
Refining Operations Monitoring field switch conditions across process units
Industrial Utilities Connecting discrete signals from utility equipment
Manufacturing Facilities Monitoring machine states, limit switches, and safety-related status contacts
Distributed Control Systems Organizing multiple field digital input signals within a remote interface arrangement

Installation and Maintenance

  1. Verify Backplane Compatibility: Confirm that the CP-DYNB-2DI matches the installed CP-DYN system configuration and required 32-channel digital input arrangement.
  2. Inspect the Assembly: Check the backplane, connector contacts, mounting points, and circuit connections for visible damage before installation.
  3. Confirm Module Selection: Verify that the installed interface modules are MTL4513, MTL4516, or MTL4517 as required by the backplane configuration.
  4. Isolate the Equipment: Follow the site’s electrical isolation procedures before removing or installing the field termination assembly.
  5. Prepare the Mounting Position: Select a suitable control cabinet position that provides access to the backplane, interface modules, and cable connections.
  6. Check Mounting Hardware: Verify that the mounting pillars or designated DIN rail mounting kit are correctly prepared.
  7. Install the Backplane: Secure the CP-DYNB-2DI using the appropriate mounting arrangement and avoid excessive mechanical force.
  8. Install Interface Modules: Fit the compatible MTL interface modules according to the designated channel configuration and installation instructions.
  9. Connect the Dynamic Cable: Check the connector orientation and connect the Tyco Dynamic cable to the designated control system interface card.
  10. Verify Channel Wiring: Compare field wiring assignments with the system drawings and confirm that each digital input is connected to the intended channel.
  11. Perform Functional Testing: Test the connected field switches and sensors and verify that their state changes are correctly received by the control system.
  12. Complete Routine Inspection: Inspect connector contacts, cable condition, mounting security, field wiring, and digital signal performance during scheduled maintenance.

If multiple digital input channels become unavailable simultaneously, inspect the common connector, cable, and interface module connections before troubleshooting individual field devices. Also verify the correct module type and channel assignment.

Because the assembly may form part of an intrinsic safety installation, replacement and maintenance work should follow the applicable MTL installation documentation and hazardous-area requirements.


Compatible System Components

Component Function
MTL4513 Compatible digital input interface module
MTL4516 Compatible digital input interface module
MTL4517 Compatible digital input interface module
CABDYN20-0.5 0.5-meter Dynamic connector cable
CABDYN20-1 1-meter Dynamic connector cable
CABDYN20-2 2-meter Dynamic connector cable
CABDYN20-3 3-meter Dynamic connector cable
DCS System Interface Card Receives digital signals through the FTA cable connection
PLC Digital Input System Processes discrete field status signals
Field Switches and Sensors Generate discrete input signals

Recommended Related Models

Model / Product Product Type Typical Application
Honeywell CP-DYNB-DI Digital Input Backplane 16-channel digital input interface
Honeywell CP-DYNB-DILF Digital Input Backplane with LFD 16-channel digital input with line fault detection
Honeywell CP-DYNB-4DI Digital Input Backplane 48-channel digital input interface
Honeywell CP-DYNB-DO Digital Output Backplane 16-channel digital output interface
Honeywell CP-DYNA-DO Digital Output Backplane 8-channel digital output interface
Honeywell CP-DYNB-AIO Analog I/O Backplane 16-channel analog input/output interface

Key Advantages

  • Supports 32 digital input channels.
  • Uses the Size B CP-DYN backplane configuration.
  • Compatible with MTL4513, MTL4516, and MTL4517 modules.
  • Uses Tyco Dynamic 20-pin connector technology.
  • Supports remote field termination arrangements.
  • Consolidates multiple discrete signal connections.
  • Supports surface and DIN rail mounting arrangements.
  • Suitable for industrial process monitoring and automation systems.

Technical FAQs

1. How many digital input channels does the CP-DYNB-2DI support?

The CP-DYNB-2DI supports 32 digital input channels. This makes it suitable for installations requiring a larger number of discrete field signals within one Size B field termination assembly.

2. Which MTL4500 modules are compatible with the CP-DYNB-2DI?

The designated compatible modules are MTL4513, MTL4516, and MTL4517. These modules should be selected according to the required input interface configuration and the system design.

3. What is the difference between CP-DYNB-DI and CP-DYNB-2DI?

The CP-DYNB-DI supports 16 digital input channels and is used with MTL4511 and MTL4514 modules. The CP-DYNB-2DI supports 32 digital input channels and is used with MTL4513, MTL4516, and MTL4517 modules. Their channel capacities and compatible interface modules are different.

4. How does the CP-DYNB-2DI connect to a DCS or PLC?

The backplane uses a Tyco Dynamic 20-pin connector arrangement. A compatible CABDYN20 cable connects the field termination assembly to the designated control system interface card. Cable length should be selected according to the installation distance and wiring layout.