The Honeywell NOTIFIER LCM-320 is a Loop Control Module used in ONYX Series intelligent fire alarm control panels. It adds Signaling Line Circuit (SLC) capacity to compatible fire alarm systems, allowing additional addressable detectors and control devices to communicate with the main control panel.
The LCM-320 is primarily used with the NFS-3030 and NFS2-3030 fire alarm control panels. These systems support up to five LCM-320 modules, providing multiple independent SLC loops for installations requiring extensive addressable device coverage.
Each LCM-320 provides one SLC loop and can be paired with a LEM-320 Loop Expander Module to provide an additional loop. This modular arrangement allows engineers to expand the detection network according to the number of field devices and the layout of the protected facility.
The module supports NOTIFIER FlashScan and CLIP addressable communication protocols, depending on the connected panel and device configuration. It can accommodate addressable smoke detectors, heat detectors, monitor modules, and control modules on the associated signaling circuit.
A notable feature is its built-in degraded-mode operation, which helps maintain system functionality under specified fault conditions. The plug-in installation arrangement also simplifies integration into the designated ONYX fire alarm control panel chassis.
For large buildings and industrial facilities, the LCM-320 provides a practical way to increase addressable detection capacity while retaining the existing ONYX control panel architecture.
| Parameter | Specification |
|---|---|
| Manufacturer | Honeywell |
| Brand | NOTIFIER |
| Model | LCM-320 |
| Product Series | ONYX |
| Product Type | Loop Control Module |
| Application | Intelligent Fire Alarm Control Panel |
| Circuit Type | Signaling Line Circuit (SLC) |
| Operating Voltage | 24 V DC Nominal |
| Maximum Operating Voltage | 27.6 V DC |
| Maximum Current Consumption | 130 mA |
| Maximum SLC Current | 400 mA |
| Maximum Loop Length | 12,500 ft (3,810 m) with 12 AWG cable |
| Maximum Loop Resistance | 50 Ω |
| Supported Wiring | Class B (Style 4), Class A configurations as applicable |
| Communication Protocols | FlashScan / CLIP |
| Maximum Device Capacity | 159 Detectors and 159 Modules per SLC Loop |
| Installation Type | Plug-in Module |
| Compatible Control Panels | NFS-3030, NFS2-3030 |
| Expansion Module | LEM-320 |
| Degraded Mode | Built-in |
| Certifications | UL, ULC, FM, CSFM |
| Dimensions | 185 × 20 × 120 mm |
| Weight | 0.34 kg |
The LCM-320 operates as an addressable communication interface between the ONYX fire alarm control panel and the field devices connected to its SLC loop.
After installation, the module establishes the signaling circuit through which the control panel communicates with addressable detectors and modules. Each connected device has an assigned address, allowing the panel to identify the source of incoming signals.
During normal operation, the control panel supervises the SLC and exchanges communication with connected devices. Smoke detectors and heat detectors transmit alarm-related information, while monitor modules report the status of external initiating circuits.
Control modules receive commands from the fire alarm panel and operate designated external equipment, such as notification appliances or fire protection interfaces.
A simplified signal arrangement is:
NOTIFIER Fire Alarm Control Panel → LCM-320 → SLC Wiring → Addressable Detectors and Modules
The LCM-320 supports both FlashScan and CLIP communication protocols, subject to the control panel and connected device configuration.
For NFS-3030 and NFS2-3030 installations, multiple LCM-320 modules can be connected through the panel’s internal module communication arrangement. This allows separate SLC loops to serve different areas of a facility.
When an associated LEM-320 is installed, an additional signaling loop can be provided for the corresponding LCM-320 configuration.
The built-in degraded-mode function helps maintain system survivability when specified communication or control conditions are compromised. However, the module does not replace the main fire alarm control panel or independently perform the complete fire alarm processing function.
Within the ONYX fire alarm architecture, the LCM-320 acts as an additional SLC controller. It extends the addressable communication network beyond the capacity of the main control panel’s onboard circuits.
The NFS-3030 and NFS2-3030 support up to five LCM-320 modules and five corresponding LEM-320 expansion modules. This arrangement allows the fire alarm network to be divided into multiple loops according to building areas, device distribution, and wiring requirements.
A typical system arrangement is:
ONYX Fire Alarm Control Panel → LCM-320 → LEM-320 (Optional) → SLC Field Devices
| System Component | Function |
|---|---|
| NOTIFIER NFS-3030 | Intelligent fire alarm control panel |
| NOTIFIER NFS2-3030 | Main fire alarm controller with expandable SLC architecture |
| NOTIFIER LCM-320 | Adds an additional SLC to the control panel |
| NOTIFIER LEM-320 | Expands an associated LCM-320 with another SLC |
| Addressable Smoke Detectors | Detect smoke and transmit alarm information |
| Addressable Heat Detectors | Monitor temperature-related fire conditions |
| Monitor Modules | Monitor external initiating circuits |
| Control Modules | Interface the fire alarm system with external equipment |
The LCM-320 is suitable for addressable fire alarm systems requiring additional signaling circuits and greater field device capacity.
| Application | Typical Use |
|---|---|
| Industrial Manufacturing | Connecting additional detectors and monitoring modules across production areas |
| Power Generation | Expanding fire detection coverage in electrical and equipment rooms |
| Oil and Gas Facilities | Supporting addressable detection networks in process areas |
| Chemical Processing | Separating fire detection circuits across different production zones |
| Commercial Buildings | Expanding addressable fire alarm coverage across multiple floors |
| Hospitals | Connecting additional detection devices in healthcare facilities |
| Airports | Supporting distributed fire detection across terminal areas |
| Data Centers | Expanding fire detection circuits in server and utility rooms |
| Warehouses | Connecting addressable detectors across storage areas |
| Infrastructure Facilities | Supporting multi-loop fire alarm installations |
If an entire SLC loop becomes unavailable, inspect the module connection, communication ribbon cable, and field wiring before troubleshooting individual detectors. Also check for short circuits, excessive loop resistance, and incorrect device addressing.
Because the LCM-320 is part of a life-safety system, installation and commissioning should be performed by qualified fire alarm technicians in accordance with the applicable NOTIFIER documentation and local fire protection regulations.
| Component | Function |
|---|---|
| NOTIFIER NFS-3030 | ONYX intelligent fire alarm control panel |
| NOTIFIER NFS2-3030 | ONYX intelligent fire alarm control panel |
| NOTIFIER LEM-320 | Loop Expander Module for additional SLC capacity |
| NOTIFIER NFS-640 | ONYX fire alarm control panel |
| NOTIFIER NFS2-640 | ONYX fire alarm control panel |
| NOTIFIER FlashScan Detectors | Addressable fire detection devices |
| NOTIFIER CLIP Devices | Addressable devices using CLIP communication |
| NOTIFIER Monitor Modules | Interface external initiating circuits |
| NOTIFIER Control Modules | Control external fire protection equipment |
| Model / Product | Product Type | Typical Application |
|---|---|---|
| NOTIFIER LEM-320 | ONYX Loop Expander Module | Expands an associated LCM-320 with another SLC |
| NOTIFIER NFS2-3030 | ONYX Intelligent Fire Alarm Control Panel | Large-scale addressable fire alarm systems |
| NOTIFIER NFS-3030 | ONYX Intelligent Fire Alarm Control Panel | Multi-loop fire detection installations |
| NOTIFIER NFS2-640 | ONYX Intelligent Fire Alarm Control Panel | Mid-sized addressable fire alarm systems |
| NOTIFIER NFS-640 | ONYX Intelligent Fire Alarm Control Panel | Addressable fire detection and control |
| NOTIFIER FCM-1 | Addressable Control Module | Interfaces external control circuits |
The LCM-320 is the Loop Control Module that adds an SLC to the ONYX control panel. The LEM-320 is an expansion module that provides an additional SLC when paired with an LCM-320. They perform different functions and are not interchangeable.
An NFS2-3030 can support up to five LCM-320 modules and five LEM-320 modules. Each LCM-320 can be paired with an associated LEM-320 to provide an additional signaling loop.
The documented configuration supports up to 159 detectors and 159 addressable modules per SLC loop. The actual device arrangement must also comply with the selected communication protocol and control panel configuration.
The affected loop shuts down while the short-circuit condition remains present. The wiring fault must be located and corrected before normal loop operation can resume. The panel should then be checked to confirm that all connected addressable devices communicate correctly.