The Epro PR6426/010-110 + CON021/916-240 32 mm Eddy Current Sensor System is a non-contact displacement measurement solution designed for monitoring the operating condition of large rotating machinery. It combines a PR6426/010-110 eddy current sensor with a CON021 signal converter configured for an extended measurement range.
Manufactured for industrial machinery protection and condition monitoring applications, this sensor system can measure shaft displacement without requiring physical contact with the rotating target. It is particularly relevant to steam turbines, gas turbines, hydro turbines, compressors, pumps, and large industrial fans.
In rotating equipment, shaft movement can provide important information about machine condition. Changes in radial or axial position, shaft eccentricity, and mechanical movement may indicate developing problems involving bearings, alignment, vibration, thermal expansion, or mechanical loading. Continuous measurement allows monitoring systems to identify abnormal operating conditions and provide information for maintenance decisions.
The PR6426 sensor has a nominal tip diameter of 32 mm and is designed for applications involving relatively large shafts. Its operating principle is based on electromagnetic induction: the sensor generates an alternating electromagnetic field, and the presence and movement of a conductive target influence the electrical characteristics of that field. The resulting measurement signal is processed by the associated converter.
The CON021/916-240 configuration is important because it identifies the extended measurement-range version of the system. The 916-240 converter designation corresponds to a 24 mm extended range for the PR6426 sensor family. This makes the combination relevant to applications requiring a wider displacement measurement range than standard configurations.
The sensor and converter should be treated as a matched measurement system. Sensor type, converter configuration, cable characteristics, target material, mounting arrangement, and calibration all influence the final measurement result. Replacing only one component with a different configuration may affect measurement accuracy and system compatibility.
| Parameter | Specification |
|---|---|
| Brand | Epro |
| Manufacturer / Product Family | Epro / Emerson |
| Sensor Model | PR6426/010-110 |
| Signal Converter | CON021/916-240 |
| Complete Model | PR6426/010-110 + CON021/916-240 |
| Product Type | Eddy Current Sensor and Signal Converter |
| Sensor Category | 32 mm Eddy Current Sensor |
| Sensor Head Diameter | 32 mm |
| Measurement Technology | Non-contact eddy current measurement |
| Converter Configuration | 24 mm Extended Measurement Range |
| Standard PR6426 Sensitivity | 2 V/mm (50.8 mV/mil), subject to the applicable standard configuration |
| Standard PR6426 Center Air Gap | Approximately 5.5 mm nominal |
| Standard PR6426 Static Range | ±4.0 mm |
| Target Material | Ferromagnetic steel |
| Typical Reference Material | 42CrMo4 steel |
| Sensor Mounting | 80 × 40 mm mounting plate |
| Sensor Sleeve Material | Stainless steel |
| Cable Material | PTFE |
| Sensor Operating Temperature | Approximately -35 to +175°C, depending on specification revision |
| Short-Term Temperature Excursion | Up to 200°C for less than 4 hours, subject to manufacturer conditions |
| Maximum Cable Temperature | Up to 200°C, subject to cable installation conditions |
| Dimensions Provided | Not specified |
| Weight Provided | 0.92 kg |
| Typical Applications | Turbines, compressors, pumps, fans, and large rotating machinery |
Important: The 2 V/mm sensitivity and ±4.0 mm static range describe the standard PR6426 sensor specifications. The complete 916-240 extended-range system must be configured and calibrated according to its dedicated converter documentation. Do not use standard-range values as a substitute for the extended-range transfer characteristics.
The PR6426/010-110 sensor uses the eddy current principle to measure the position and movement of a conductive metallic target. Because the measurement is non-contact, the sensor can monitor rotating shafts without introducing mechanical contact between the probe and the target surface.
The sensor generates a high-frequency electromagnetic field around its sensing tip. When a conductive metal target enters this field, eddy currents are induced in the target material.
These currents influence the electromagnetic field and change the electrical characteristics of the sensor circuit. The resulting signal varies according to the distance between the sensor tip and the target.
By processing this variation, the monitoring system can determine changes in the target’s position relative to the installed sensor.
In rotating machinery, the sensor is mounted near a suitable shaft surface with a controlled initial gap. As the shaft moves, the distance between the target surface and the sensor changes.
The measurement system converts this distance variation into an electrical signal that can be evaluated by a machinery monitoring or protection system.
This arrangement is useful for measuring:
The exact measurement function depends on the sensor orientation, number of installed probes, mechanical arrangement, and monitoring-system configuration.
The PR6426 sensor operates as part of a measurement chain. The CON021 converter processes the sensor signal and provides an output suitable for the connected monitoring equipment.
The converter configuration determines the applicable measurement range and signal characteristics. In this model, the 916-240 designation identifies the 24 mm extended-range configuration.
The converter must be matched to the PR6426 sensor type and its associated cable arrangement. Using a converter with an incorrect range or sensor configuration can lead to inaccurate readings or incorrect engineering interpretation.
Large rotating machinery may require a wider displacement measurement range than smaller equipment. The 916-240 configuration provides an extended range of 24 mm for the PR6426 sensor system.
This can be useful in applications where shaft position changes over a wider operating interval, such as certain axial-position or expansion-monitoring arrangements.
The extended range should not be interpreted as a guarantee of the same linearity or sensitivity across every operating condition. The converter’s specified transfer characteristics and calibration procedure must be followed.
When connected to an appropriate machinery monitoring system, the sensor can provide continuous displacement information. Monitoring equipment can evaluate the signal, compare it with configured limits, and generate alarms when operating conditions move outside acceptable ranges.
This supports condition-based maintenance and can help plant personnel identify abnormal shaft movement before it develops into a more serious mechanical problem.
The PR6426/010-110 + CON021/916-240 is intended for use as part of a wider machinery measurement and protection architecture. It is not a standalone machine protection controller. Its measurements must be interpreted by compatible monitoring equipment.
Steam and gas turbines operate with high-speed rotating shafts and tightly controlled mechanical clearances. Changes in axial or radial shaft position can be important indicators of mechanical condition.
A properly installed sensor system can provide position measurements to a turbine monitoring system. These measurements may be used alongside vibration, speed, temperature, and other operating parameters.
Large compressors operate under changing pressure, temperature, and mechanical loading conditions. Shaft movement can provide additional information about rotor behavior and mechanical stability.
The PR6426’s large sensing diameter makes it relevant to applications involving large shaft surfaces, provided the shaft material and installation geometry meet the manufacturer’s requirements.
A machinery monitoring system may transmit measurement values, alarm states, and equipment status to a distributed control system or programmable logic controller.
The sensor itself does not replace the PLC or DCS. Its role is to provide a measurement input to compatible signal-processing and monitoring equipment.
Before integration, engineers should verify the converter output type, signal range, wiring arrangement, and input requirements of the receiving system.
Displacement measurements can be included in machine protection logic. Depending on the monitoring architecture, the system may use configured alarm and trip thresholds to respond to excessive shaft movement.
Alarm and trip settings must be based on machine design, manufacturer recommendations, operating conditions, and the applicable protection philosophy. They should not be selected solely from the sensor’s maximum measurement range.
The PR6426/010-110 + CON021/916-240 is designed for large rotating equipment where non-contact displacement measurement is required.
Steam turbines operate under substantial thermal and mechanical loads. Shaft position and movement can change during startup, normal operation, load changes, and shutdown.
The sensor system can be used in suitable turbine monitoring arrangements to measure shaft displacement and provide information about rotor position.
Gas turbines require continuous monitoring of critical rotating components. Shaft displacement measurements can contribute to an overall machinery condition-monitoring strategy.
The sensor must be installed at an appropriate measurement location, with correct alignment and clearance from the shaft surface.
Hydroelectric generating units contain large rotating assemblies that may require axial and radial position monitoring. A suitable eddy current sensor system can provide non-contact measurement of shaft movement.
The extended-range converter configuration may be relevant where the required displacement measurement range exceeds that of a standard configuration.
Large compressors are used in chemical processing, oil and gas facilities, gas transportation, and other industrial operations.
Shaft movement can provide useful information about rotor condition, bearing behavior, and mechanical alignment. The PR6426 system can form part of a larger compressor monitoring arrangement.
Critical pumps in power plants and process facilities may require continuous monitoring of shaft position and movement.
A non-contact sensor can measure the relative position of a suitable metallic shaft target without introducing mechanical wear at the measurement point.
Large fans and blowers used in power generation, steel production, cement plants, and other facilities may operate continuously under changing process conditions.
Where shaft displacement monitoring is required, the PR6426 system can be evaluated as part of the machinery instrumentation design.
The performance of an eddy current measurement system depends on correct sensor mounting, target preparation, cable installation, converter configuration, and calibration.
The PR6426/010-110 uses a mounting plate arrangement. The mounting surface should be sufficiently rigid to prevent unwanted movement during machine operation.
The sensor must be aligned with the intended target surface. Incorrect positioning can introduce measurement errors or reduce the usable measurement range.
Maintain the required clearance around the sensing area. The manufacturer’s installation documentation specifies the necessary target geometry and clearance from surrounding ferrous materials.
The initial gap between the sensor tip and the target surface is an important installation parameter.
For the standard PR6426 configuration, the nominal center air gap is approximately 5.5 mm. The exact adjustment procedure for the 24 mm extended-range configuration must follow the corresponding converter documentation.
The initial gap should be set using the prescribed installation and calibration procedure rather than estimated visually.
Eddy current sensors respond to the electrical and magnetic characteristics of the target material. The standard PR6426 specifications identify ferromagnetic steel, with 42CrMo4 used as a reference material.
If the actual shaft material differs, the measurement response may also differ. Engineers should verify material compatibility before commissioning.
Surface condition, shaft geometry, and nearby metallic structures should also be considered.
The sensor cable should be routed in accordance with the manufacturer’s requirements. Avoid unnecessary bending, mechanical tension, and routing close to high-power conductors where electromagnetic interference may affect the measurement circuit.
Protect the cable from excessive heat, abrasion, oil exposure, and vibration. Maintain the specified minimum bending radius and use suitable cable support.
The CON021/916-240 converter must be configured for the PR6426 sensor and its extended measurement range.
Verify the complete converter designation, cable arrangement, output characteristics, and receiving-system input requirements before connection.
Do not substitute a different CON021 range configuration without confirming its compatibility with the required measurement function.
Before placing the machine into service, check the sensor installation, initial gap, cable connections, converter configuration, and output signal.
Verify the measurement response using the manufacturer’s calibration procedure and appropriate test equipment. Confirm that the monitoring system displays the correct engineering units and that alarm thresholds are configured according to the machine’s protection requirements.
The PR6426/010-110 + CON021/916-240 operates as part of a measurement chain. The following components may be involved in a complete installation.
| Component | Function | Integration Considerations |
|---|---|---|
| PR6426/010-110 Sensor | Detects shaft displacement without physical contact | Must match the target material, mounting geometry, and converter configuration |
| CON021/916-240 Converter | Processes the sensor signal for the 24 mm extended range | Confirm the exact range and output characteristics |
| Sensor Extension Cable | Connects the sensor to the signal-processing equipment | Verify cable type, length, connectors, and compatibility |
| Machinery Monitoring System | Processes and evaluates measurement signals | Confirm supported input type and measurement range |
| PLC | Receives relevant process or status information | Integration may require a compatible monitoring-system output |
| DCS | Displays equipment condition and process information | Verify signal scaling and communication architecture |
| Turbine Protection System | Uses measurements for machinery alarm and protection functions | Configure thresholds according to machine-specific requirements |
| Sensor Mounting Hardware | Holds the probe in the required position | Ensure mechanical rigidity and correct alignment |
Not every component listed above is necessarily included in the supplied product package. Confirm the actual bill of materials before purchasing.
The PR6426 family includes different sensor and converter configurations. Replacement selection should be based on the measurement range, sensor diameter, cable arrangement, and converter characteristics.
| Alternative or Related Model | Main Consideration |
|---|---|
| PR6426 with CON021/916-120 | Related 32 mm sensor configuration with a different extended measurement range |
| PR6426 with CON021/916-160 | Related extended-range configuration; verify range and linearity requirements |
| PR6426 with CON021/916-200 | Related extended-range configuration for applications requiring a different measurement span |
| PR6426 with CON021/916-240 | The 24 mm extended-range configuration associated with this product |
| PR6425 Eddy Current Sensor | Smaller sensor family; not a direct substitute for the 32 mm PR6426 |
| PR6424 Eddy Current Sensor | Different sensor diameter and measurement characteristics; application review required |
Before replacing the system, compare:
A different converter range may change the relationship between physical displacement and electrical output. A replacement should therefore be treated as a measurement-system change unless full compatibility has been confirmed.
The eddy current principle allows shaft displacement to be measured without physical contact, avoiding mechanical contact between the sensor and the rotating target.
The 32 mm sensing diameter is intended for large-shaft measurement applications and is suitable for selected turbomachinery installations.
The CON021/916-240 configuration provides a 24 mm extended range, supporting applications that require a wider measurement span than standard configurations.
The sensor family is designed for monitoring applications involving turbines, compressors, pumps, and fans.
When connected to compatible monitoring equipment, the system can provide ongoing displacement information for machinery condition assessment.
The sensor uses a stainless-steel sleeve and PTFE cable construction, with temperature characteristics suited to demanding machinery environments when installed within the specified limits.
The measurement signal can be incorporated into a wider machinery monitoring architecture, allowing relevant information to be made available to plant control and protection systems.
It is a non-contact eddy current measurement system consisting of a 32 mm PR6426 sensor and a CON021 signal converter configured for a 24 mm extended measurement range.
The PR6426/010-110 has a nominal sensor head diameter of 32 mm.
It identifies the converter configuration associated with the PR6426 sensor family and its 24 mm extended measurement range.
Depending on its mounting arrangement, the system can be used for radial or axial shaft displacement, position, eccentricity, and other relative shaft movement measurements.
No. It uses electromagnetic induction to measure the distance between the sensing tip and a conductive target without physical contact.
The standard PR6426 specification identifies ferromagnetic steel, with 42CrMo4 as a reference material. Other target materials should be evaluated against the manufacturer’s measurement requirements.
The standard PR6426 specification gives a sensitivity of 2 V/mm (50.8 mV/mil), with a maximum deviation of approximately ±1.5%. The extended-range converter’s transfer characteristics must be checked separately.
No. The ±4 mm figure describes the standard PR6426 static measurement range, while CON021/916-240 identifies an extended-range configuration of 24 mm. These values describe different configurations and should not be interchanged.
The sensor should be used with its compatible signal converter and an appropriate receiving system. Direct PLC connection should not be assumed. Verify the converter output and the PLC input requirements before integration.
Confirm the complete sensor and converter model numbers, sensor diameter, measurement range, cable length, connector type, mounting arrangement, and output characteristics. Also verify the condition of the sensor head, cable, and converter.
When sourcing the Epro PR6426/010-110 + CON021/916-240, verify that the sensor and converter are supplied as the correct matched configuration. The 916-240 suffix is especially important because it identifies the extended measurement range.
For replacement projects, compare the complete model numbers with the existing installation records. Check whether the sensor is supplied with the required cable, connector, mounting hardware, and signal converter. A sensor supplied without its matching converter may not provide a complete operational measurement system.
For used or refurbished equipment, inspect the sensor head, cable sheath, connector, mounting plate, and converter enclosure. Request clear photographs of the identification labels and ask for available functional-test or calibration information.
During routine maintenance, inspect cable routing and mechanical mounting for signs of wear, vibration, heat damage, or loosening. Verify the initial gap and measurement output according to the manufacturer’s maintenance procedure.
Changes to the sensor, converter, cable, or mounting arrangement should be documented. After replacement, perform the required calibration and verify the measurement scaling in the machinery monitoring system before returning the equipment to normal operation.
The Epro PR6426/010-110 + CON021/916-240 is a 32 mm eddy current sensor system designed for non-contact shaft displacement measurement in large rotating machinery. Its PR6426 sensor provides the sensing function, while the CON021/916-240 converter establishes the associated 24 mm extended measurement configuration.
The system is suitable for selected applications involving steam turbines, gas turbines, hydro turbines, compressors, pumps, and industrial fans. Correct sensor mounting, target material compatibility, cable installation, converter configuration, and calibration are essential for reliable measurement.
For maintenance and replacement projects, verifying the complete sensor and converter designation is particularly important. Matching the measurement range and signal characteristics helps maintain consistency with the existing machinery monitoring and protection system.