The Schneider Electric NW20H1 MasterPact Circuit Breaker is a low-voltage air circuit breaker designed for high-capacity power distribution and electrical protection systems. It belongs to the MasterPact NW series, a product family developed for demanding industrial, commercial, and infrastructure power-distribution applications.
With a 2000 A rated current frame and a three-pole drawout configuration, the NW20H1 is intended for use in main distribution boards, power control centers, and large electrical switchboards. It provides a means of switching and isolating electrical circuits while supporting protection arrangements designed to manage overloads and short-circuit faults.
The H1 performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 440 V AC. The circuit breaker is also specified for a rated operational voltage of up to 690 V AC, subject to the applicable electrical ratings and installation conditions.
This product reference identifies a circuit breaker frame supplied without a trip unit. This distinction is important when planning a complete protection system. The trip unit is responsible for detecting specified abnormal electrical conditions and initiating the opening operation. Therefore, the correct compatible protection unit and accessories must be selected separately where they are not included in the supplied configuration.
The drawout design allows the circuit breaker to be withdrawn from its associated chassis for inspection, testing, and maintenance procedures. This arrangement is particularly useful in installations where maintenance access and equipment replacement are important operational considerations.
The NW20H1 is suited to power distribution systems where high current capacity, coordinated protection, and maintainable switchgear construction are required. Before installation or replacement, engineers should verify the complete catalog number, pole configuration, trip-unit requirements, chassis compatibility, and electrical ratings.
| Parameter | Specification |
|---|---|
| Brand | Schneider Electric |
| Product Family | MasterPact NW |
| Model | NW20H1 |
| Product Type | Air Circuit Breaker |
| Device Application | Power Distribution Protection |
| Rated Current Frame | 2000 A |
| Pole Configuration | 3 Poles |
| Mounting Type | Drawout |
| Control Unit | Without trip unit |
| Performance Level | H1 |
| Rated Operational Voltage | Up to 690 V AC, 50/60 Hz |
| Rated Ultimate Short-Circuit Breaking Capacity | 65 kA at 440 V AC |
| Rated Service Short-Circuit Breaking Capacity | 65 kA at 440 V AC |
| Rated Short-Time Withstand Current | 65 kA for 1 second |
| Rated Insulation Voltage | 1000 V AC |
| Rated Impulse Withstand Voltage | 12 kV |
| Control Type | Push-button |
| Suitability for Isolation | Yes, subject to applicable standards |
| Standards | EN/IEC 60947-1 and EN/IEC 60947-2 |
| Protection Degree | IP30 |
| Dimensions | 439 × 441 × 395 mm |
| Weight | 90 kg |
| Product Series | MasterPact NW |
| Product Lifecycle | Discontinued configuration; verify replacement status |
Note: The NW20H1 designation covers a product family with different configurations. Confirm the complete catalog number and nameplate before purchasing. The specifications above describe the referenced three-pole drawout frame without a trip unit.
The NW20H1 is designed to switch and isolate high-current electrical circuits while forming part of a coordinated power-protection system. Its operation involves mechanical switching components, electrical contacts, and a compatible protection arrangement.
During normal operation, the circuit breaker remains closed and allows current to flow through its main contacts. The contact system is designed for the specified current rating and operating conditions.
For a 2000 A frame, correct conductor sizing, connection design, ventilation, and temperature management are important. The actual permitted current and operating performance must be evaluated against the complete switchgear assembly and its rated conditions.
A circuit breaker protection system must detect abnormal current conditions and interrupt the circuit when the configured protection criteria are met.
The NW20H1 frame referenced here is supplied without a trip unit. A compatible protection unit must be selected and installed as required by the intended application. The protection settings should be coordinated with the upstream and downstream devices, conductor ratings, transformer characteristics, and system fault levels.
When the breaker opens under load or fault conditions, an electrical arc may form between the separating contacts. The air circuit breaker’s arc-control and interruption system is designed to extinguish this arc and interrupt the current.
The H1 performance level identifies the breaker’s specified short-circuit interruption capability. The rated breaking capacity must always be considered at the applicable system voltage and under the manufacturer’s stated test conditions.
The drawout construction allows the breaker to be moved between its operating and disconnected positions within a compatible chassis.
This design supports maintenance and inspection procedures without requiring the entire switchgear assembly to be dismantled. The correct racking procedure, interlocking arrangements, and electrical isolation steps must be followed to prevent unsafe operation.
The NW20H1 is suitable for isolation according to the applicable EN/IEC 60947-2 requirements. Isolation is an important function in industrial distribution systems, where electrical equipment must be separated from the supply before maintenance.
Isolation procedures must still follow the installation’s safety rules, including verification of the de-energized condition and the use of appropriate lockout and tagging practices.
The NW20H1 can serve as a main or feeder circuit breaker in a low-voltage distribution architecture. Its role depends on the system design, protection coordination, and the position of the breaker within the switchboard.
In a suitable distribution system, a high-capacity air circuit breaker may be installed at the incoming supply point. It provides switching and protection functions for the main distribution assembly.
The NW20H1’s 2000 A frame rating makes it relevant to systems with substantial current demand, provided that the actual load, fault level, and protection configuration are appropriate.
The breaker may also be used in a feeder arrangement supplying downstream distribution boards, motor control centers, or large industrial loads.
Protection settings must be coordinated with downstream breakers and the characteristics of the connected equipment. This helps ensure that faults are cleared by the appropriate protective device wherever the system design permits.
Large industrial facilities often use centralized switchgear to distribute electrical power to production equipment, utilities, and auxiliary systems.
A MasterPact NW circuit breaker can form part of this arrangement, providing a switching and isolation point for a high-capacity circuit.
The drawout construction supports maintenance planning by allowing the breaker to be withdrawn from its chassis under the required safe conditions.
Maintenance personnel can inspect the breaker and associated connections according to the manufacturer’s procedures without treating the complete switchboard as a single inseparable assembly.
The MasterPact NW20H1 is intended for high-capacity low-voltage power distribution applications. Its suitability depends on the available fault current, system voltage, rated current, and the protection design.
Manufacturing plants often contain large electrical distribution systems supplying production lines, process equipment, motors, and auxiliary services.
A high-capacity circuit breaker can be used in the main distribution or feeder section to support controlled switching and electrical protection.
Main distribution switchboards require circuit breakers capable of carrying substantial current and interrupting specified fault levels.
The NW20H1’s 2000 A frame and H1 interruption performance make it relevant to appropriately engineered low-voltage distribution assemblies.
Large commercial buildings, transportation facilities, and infrastructure installations may use high-capacity low-voltage switchgear to distribute power to multiple sections of a facility.
A compatible MasterPact NW circuit breaker can provide a switching and protection point within the distribution architecture.
Data centers require carefully coordinated power distribution systems to supply server rooms, cooling equipment, UPS systems, and auxiliary infrastructure.
High-capacity circuit breakers may be used in main or feeder distribution sections. Selection must consider system redundancy, fault levels, selectivity, and the required continuity of service.
Low-voltage distribution sections within substations may use air circuit breakers to control and protect outgoing feeders and auxiliary power systems.
The NW20H1 can be considered where its voltage, current, breaking capacity, and mounting configuration match the electrical design.
Installation of a 2000 A air circuit breaker requires detailed engineering and strict compliance with the manufacturer’s instructions. The work should be carried out by qualified electrical personnel.
Before installation, confirm the system voltage, rated operating current, prospective short-circuit current, and required breaking capacity.
The NW20H1 H1 configuration is specified for 65 kA at 440 V AC. The actual installation must remain within the applicable voltage and fault-interruption ratings.
Do not select a breaker based only on the 2000 A frame rating. The protection design must also account for load current, conductor capacity, system grounding, and fault-clearing requirements.
The referenced configuration is supplied without a trip unit. A suitable compatible trip unit must be identified according to the intended protection functions and the breaker configuration.
Protection requirements may include long-time, short-time, instantaneous, and ground-fault protection, depending on the selected unit and system design.
Do not assume that a trip unit from another MasterPact model is compatible. Confirm the manufacturer’s approved combinations and installation instructions.
The breaker must be installed in a compatible drawout chassis and switchboard arrangement.
Before installation, verify the frame size, pole arrangement, connection system, racking mechanism, interlocks, and auxiliary connections. A breaker that looks similar may not fit or operate correctly in a different chassis configuration.
The supplied dimensions are 439 × 441 × 395 mm. Confirm the exact mechanical drawing and required installation clearances before preparing the switchgear compartment.
Consider the space needed for:
The IP30 protection rating should also be considered when evaluating the overall switchgear enclosure and installation environment.
Power connections must be designed for the rated current and installation conditions. Use appropriate conductors, busbars, connection hardware, and tightening procedures.
Auxiliary wiring may include indication, control, interlocking, and trip-related circuits, depending on the installed accessories. Follow the applicable wiring diagrams rather than relying on terminal appearance.
Before energizing the equipment, inspect the mechanical installation, electrical connections, grounding, and auxiliary wiring.
Verify the correct operation of the racking mechanism, mechanical interlocks, opening and closing functions, indication circuits, and the installed protection unit. Protection testing should follow the approved commissioning procedure.
All testing and commissioning should be performed by qualified personnel using suitable equipment and established electrical safety procedures.
The NW20H1 operates as part of a complete switchgear assembly. The following components may be required depending on the application and supplied configuration.
| Component | Function | Compatibility Considerations |
|---|---|---|
| Compatible trip unit | Provides electronic protection functions | This referenced frame is supplied without a trip unit; verify approved compatibility |
| Drawout chassis | Supports breaker mounting and withdrawal | Confirm the correct MasterPact NW frame and chassis arrangement |
| Primary connection system | Connects the breaker to the main power circuit | Check current rating, connection layout, and busbar design |
| Secondary disconnects | Connects auxiliary and control circuits | Confirm terminal configuration and wiring requirements |
| Auxiliary contacts | Provide breaker position and status signals | Verify contact arrangement and accessory compatibility |
| Shunt trip accessory | Enables electrical remote opening | Confirm coil voltage and compatible accessory reference |
| Undervoltage release | Supports opening under specified undervoltage conditions | Verify control voltage and accessory configuration |
| Closing release | Supports electrical closing operation | Confirm the required voltage and control arrangement |
| Switchboard enclosure | Houses the breaker and associated components | Check compartment dimensions, protection rating, and thermal design |
| Protection coordination system | Coordinates protective devices across the network | Verify settings, fault levels, and selectivity requirements |
The components listed above are not necessarily included with the NW20H1 frame. Confirm the actual bill of materials and accessory configuration before procurement.
The NW20H1 belongs to the MasterPact NW family. Replacement selection must account for frame rating, voltage, short-circuit performance, pole configuration, mounting arrangement, and trip-unit compatibility.
| Alternative or Related Model | Replacement Considerations |
|---|---|
| MasterPact NW20H2 | Same general frame class but a different interruption performance level; verify the system fault requirements |
| MasterPact NW20H3 | Higher interruption performance class in the NW20 family; check the complete configuration |
| MasterPact NW20L1 | Different performance class and application characteristics; not an automatic substitute |
| Schneider Electric LV948287 | Identified as a replacement reference for the specific NW20H1 configuration described in the product documentation; verify complete technical equivalence |
| Current-generation MasterPact circuit breaker | May be suitable for an upgrade, but chassis, connections, protection settings, and switchboard modifications may be required |
Before selecting a replacement, compare:
A replacement should never be approved solely because it carries the same 2000 A rating. The protection coordination and complete switchgear design must be reviewed.
The 2000 A frame rating makes the NW20H1 relevant to large low-voltage distribution systems that require substantial current-carrying capability.
The H1 performance level provides a specified 65 kA short-circuit breaking capacity at 440 V AC, subject to the manufacturer’s rating conditions.
The drawout design supports inspection, maintenance, and replacement procedures within a compatible switchgear assembly.
The three-pole arrangement is designed for three-phase power distribution applications where the specified configuration is appropriate.
The breaker is suitable for isolation according to the applicable EN/IEC 60947-2 requirements.
The MasterPact NW family is designed for integration into low-voltage distribution assemblies used in industrial and infrastructure environments.
The drawout arrangement and availability of compatible accessories support planned maintenance and equipment lifecycle management.
The NW20H1 is a MasterPact NW low-voltage air circuit breaker designed for high-capacity power distribution protection. The referenced configuration is a 2000 A, three-pole drawout frame supplied without a trip unit.
The rated current frame is 2000 A at the specified operating conditions. The actual protection settings and permitted current depend on the installed trip unit and complete system configuration.
The H1 performance level is rated at 65 kA at 440 V AC. The applicable breaking capacity must be checked against the system voltage and the manufacturer’s technical documentation.
The referenced configuration is specified without a trip unit. A compatible protection unit must be selected separately if required for the installation.
The referenced product configuration is drawout. It is designed for use with a compatible chassis and racking arrangement.
The published rated operational voltage is up to 690 V AC at 50/60 Hz. The short-circuit performance and other ratings vary according to the operating voltage.
The supplied dimensions are 439 × 441 × 395 mm, and the net weight is approximately 90 kg.
It may be used in a main incoming position when the system voltage, current, fault level, protection coordination, and switchgear design are appropriate. A qualified electrical engineer should verify the complete installation.
The referenced product documentation identifies a planned discontinuation at the end of 2025 and lists LV948287 as its replacement reference. Availability should be confirmed with Schneider Electric or an authorized supplier.
Confirm the complete catalog number, pole configuration, drawout arrangement, trip-unit requirements, breaking capacity, chassis compatibility, auxiliary accessories, and physical condition. Also verify whether the quoted item includes the trip unit and associated mounting components.
When purchasing the Schneider Electric NW20H1, begin by confirming the exact catalog number and configuration. The product name alone does not establish whether the breaker includes a trip unit, chassis, auxiliary contacts, or other accessories.
For replacement projects, compare the original equipment nameplate with the proposed replacement documentation. Pay particular attention to the three-pole drawout arrangement, 2000 A frame rating, H1 performance level, and 65 kA breaking capacity at 440 V AC.
For new-old-stock or used equipment, request clear photographs of the nameplate, front panel, terminals, racking mechanism, and accessory positions. Confirm whether the breaker has been inspected or tested and establish the condition of the main contacts and mechanical operating mechanism.
Because the unit weighs approximately 90 kg, transportation and handling require suitable lifting equipment and an appropriate handling plan. Protect the breaker against impact, moisture, and contamination during storage and shipment.
Maintenance should follow the manufacturer’s procedures and the facility’s electrical safety program. Inspection may include mechanical operation, contact condition, connection integrity, auxiliary circuits, interlocks, and protection-unit testing where applicable.
For critical power systems, protection settings and coordination should be reviewed whenever a breaker is replaced or modified. A physically compatible breaker is not necessarily electrically equivalent.
The Schneider Electric NW20H1 MasterPact Circuit Breaker is a 2000 A, three-pole drawout air circuit breaker designed for high-capacity low-voltage power distribution. Its H1 performance level provides a 65 kA rated short-circuit breaking capacity at 440 V AC, while the drawout construction supports maintenance and equipment replacement in compatible switchgear assemblies.
The referenced configuration is supplied without a trip unit, so the required protection unit and accessories must be verified separately. With dimensions of 439 × 441 × 395 mm and a weight of approximately 90 kg, the NW20H1 is intended for substantial industrial and infrastructure switchgear installations.
For maintenance and replacement projects, confirm the full catalog number, electrical ratings, trip-unit requirements, and chassis compatibility before procurement or installation.