The Schneider Electric TM2AMO1HT is a single-channel analog output expansion module for the Modicon M238 logic controller. It converts digital output values generated by the PLC program into proportional voltage or current signals, allowing the controller to regulate equipment that requires continuous analog references rather than simple ON/OFF commands.
The module supports two output signal formats: 0–10 V DC and 4–20 mA. With 12-bit resolution, it can generate different output levels according to the values calculated by the controller. This makes it suitable for applications involving speed references, valve positioning, pressure regulation, and other process-control functions.
For example, in a pumping system, the M238 controller can calculate the required pump speed based on pressure feedback. The TM2AMO1HT converts the programmed output value into a 0–10 V or 4–20 mA reference signal, which can then be connected to a compatible variable-frequency drive. The drive adjusts motor operation according to the received reference.
The same principle applies to modulating valves and other process actuators. Instead of simply switching an output on or off, the controller can send a continuously adjustable signal corresponding to the required operating position or setpoint.
The TM2AMO1HT has one analog output channel and uses a removable screw terminal block for field wiring. It requires an external 24 V DC supply for its analog output circuitry. Photocoupler insulation separates the output channel from the module’s internal logic, helping isolate the signal interface.
One important configuration detail is the relationship between the selected output mode and the physical wiring. The voltage and current output settings must match the connected equipment. Incorrectly configuring a channel for current output when it is physically wired for voltage operation can damage the analog circuit.
For engineers maintaining existing Modicon M238 installations, the TM2AMO1HT is a dedicated solution for adding one configurable voltage/current output without replacing the main controller.
| Parameter | Specification |
|---|---|
| Manufacturer | Schneider Electric |
| Model | TM2AMO1HT |
| Product Series | Modicon M238 |
| Product Type | Analog Output Module |
| Number of Analog Outputs | 1 |
| Analog Output Type | Voltage / Current |
| Voltage Output Range | 0–10 V DC |
| Current Output Range | 4–20 mA |
| Output Resolution | 12 bits |
| Voltage LSB Value | 2.5 mV |
| Current LSB Value | 4.8 µA |
| Load Type | Resistive |
| Voltage Load Impedance | ≥ 2,000 Ω |
| Current Load Impedance | ≤ 300 Ω |
| Stabilization Time | 10 ms |
| Conversion Time | 10 ms + 1 controller cycle |
| Measurement Error | ±0.2% FS at 25°C |
| Temperature Coefficient | ±0.015% FS/°C |
| Repeat Accuracy | ±0.5% FS |
| Non-Linearity | ±0.2% FS |
| Output Ripple | ≤ 1 LSB |
| Total Error | ±1% FS |
| External Supply Voltage | 24 V DC |
| Supply Voltage Limits | 19.2–30 V DC |
| Internal Current Consumption | 50 mA at 5 V DC |
| External Current Consumption | 40 mA at 24 V DC |
| Electrical Connection | 1 Removable Screw Terminal Block |
| Signal Cable | Twisted Shielded Cable |
| Channel Insulation | Photocoupler |
| Dielectric Strength | 500 V |
| Mounting Type | DIN Rail / Panel Mounting |
| Dimensions | 90 × 23.5 × 70 mm |
| Weight | 0.085 kg |
The TM2AMO1HT converts a numerical value calculated by the Modicon M238 controller into an analog electrical signal.
During normal operation, the PLC program determines the output value according to process conditions, operator settings, or feedback from connected sensors. This value is transferred to the module through the controller’s expansion interface.
The module then converts the digital command into the selected analog output format. In voltage mode, it generates a signal between 0 and 10 V DC. In current mode, it generates a signal between 4 and 20 mA.
For example, consider a variable-frequency drive controlling a centrifugal pump. The PLC program calculates the required motor speed based on the pressure measured by a transmitter. The TM2AMO1HT converts the corresponding command into a 4–20 mA reference signal, which the drive interprets as its speed demand.
The relationship between the output signal and the commanded value depends on the configured scaling. A higher output value can represent a higher speed reference, valve opening, or another process setpoint.
The module uses 12-bit conversion resolution. Its output can therefore represent multiple discrete levels across the selected analog range. The actual process response also depends on the connected equipment and its own input characteristics.
A simplified signal path is:
PLC Program → Digital Output Value → TM2AMO1HT Conversion → 0–10 V / 4–20 mA Signal → Drive or Analog Actuator
The module’s output channel is electrically isolated from the internal logic through a photocoupler. This separation helps protect the controller-side circuitry from electrical disturbances associated with the external signal interface.
Correct channel configuration is essential. The physical wiring must correspond to the selected voltage or current mode in the programming software. The connected load must also satisfy the specified impedance requirements.
Within the Modicon M238 automation architecture, the TM2AMO1HT provides an additional analog control channel for applications that require continuously adjustable output signals.
The M238 controller executes the machine or process program, while the TM2AMO1HT handles the conversion of the programmed output value into a physical analog signal. This division allows the controller to manage process logic without requiring a separate signal-conversion device for the corresponding output.
A typical arrangement in a pump-control application is:
Pressure Transmitter → Modicon M238 Controller → TM2AMO1HT → 4–20 mA Reference → Variable-Frequency Drive → Pump Motor
The module can also be used in applications involving modulating valves, proportional actuators, and other compatible analog-input equipment.
| System Component | Function |
|---|---|
| Schneider Electric Modicon M238 | Executes machine and process control programs |
| Schneider Electric TM2AMO1HT | Converts PLC output values into 0–10 V or 4–20 mA signals |
| Schneider Electric TM2AMM3HT | Provides mixed analog input and output expansion |
| Schneider Electric TM2AMM6HT | Provides additional analog input and output channels |
| Schneider Electric TM2AVO2HT | Provides two voltage analog output channels |
| Schneider Electric Altivar Drive | Receives compatible analog references for motor speed control |
| Analog Pressure Transmitter | Supplies process feedback to the controller |
| Modulating Control Valve | Adjusts fluid flow according to an analog reference |
| Industrial Actuator | Converts the analog command into mechanical movement |
The TM2AMO1HT is particularly useful when an existing M238 installation requires one additional analog control point without changing the main controller architecture.
The TM2AMO1HT is used in automation systems where PLC-generated analog signals are required to regulate equipment operation.
| Industrial Application | Typical Use |
|---|---|
| Pumping Systems | Sending speed reference signals to variable-frequency drives |
| HVAC Systems | Controlling compatible modulating valves and air-handling equipment |
| Water Treatment | Adjusting chemical dosing equipment and regulating process flow |
| Chemical Processing | Providing analog references for proportional control devices |
| Packaging Machinery | Controlling compatible variable-speed equipment |
| Food and Beverage Processing | Regulating pumps, valves, and process equipment |
| Industrial Manufacturing | Providing adjustable analog commands to machine actuators |
| Material Handling | Controlling compatible drive systems through analog references |
| Process Automation | Converting PLC calculations into voltage or current control signals |
| Utility Equipment | Supporting analog regulation of pumps and other process machinery |
During troubleshooting, incorrect signal-mode configuration should be checked before replacing the module. A mismatch between the physical wiring and software settings can damage the analog circuit. Also inspect the external 24 V DC supply and connected load impedance when the output signal is outside the expected range.
| Component | Function |
|---|---|
| Schneider Electric Modicon M238 | Main logic controller for the TM2 expansion system |
| Schneider Electric TM2AMO1HT | Single-channel voltage/current analog output module |
| Schneider Electric TM2AMM3HT | Mixed analog input/output expansion module |
| Schneider Electric TM2AMM6HT | Multi-channel analog input/output expansion module |
| Schneider Electric TM2AVO2HT | Two-channel voltage analog output module |
| Schneider Electric TM2ALM3LT | Low-level analog input and output expansion module |
| Schneider Electric Advantys OTB | Compatible distributed I/O system |
| Schneider Electric Twido | Compatible controller range listed for the module |
| Schneider Electric Altivar Drives | Receives compatible analog speed references |
| Analog Control Valves | Regulates process flow through analog command signals |
| Model / Product | Product Type | Typical Application |
|---|---|---|
| Schneider TM2AVO2HT | Modicon TM2 Analog Output Module | Two-channel ±10 V voltage output applications |
| Schneider TM2AMM3HT | Modicon TM2 Analog Mixed I/O Module | Applications requiring two analog inputs and one analog output |
| Schneider TM2AMM6HT | Modicon TM2 Analog Mixed I/O Module | Applications requiring four analog inputs and two analog outputs |
| Schneider TM2ALM3LT | Modicon TM2 Low-Level Analog Mixed I/O Module | Temperature measurement and analog output applications |
| Schneider TM2AMI2HT | Modicon TM2 Analog Input Module | Two-channel analog signal acquisition |
| Schneider TM2ARI8HT | Modicon TM2 Analog Input Module | Eight-channel temperature input applications using NTC/PTC sensors |
No. The module has one configurable analog output channel. It can operate in either 0–10 V voltage mode or 4–20 mA current mode, but it does not provide two independent outputs or simultaneous voltage and current signals.
The specified load impedance for current operation is no more than 300 Ω. The connected device and cable arrangement should remain within this limit to maintain the required output performance.
Analog signals can be affected by electromagnetic interference from motor drives, contactors, and power cables. Twisted shielded cable helps reduce induced noise and improves signal quality, particularly in industrial control cabinets with multiple electrical devices.
An incorrect combination of physical wiring and software configuration can damage the analog output circuit. The wiring arrangement must be checked against the selected output mode in the programming software before commissioning or changing the configuration.