Our advantage
Global Logistics
We have a 10-year logistics and express cooperation agreement, so our products can be shipped to any place in the world.
Brand new and original
Our products are imported in bulk from the place of origin. Because of the cooperative relationship, our products are all original and 100% new.
24-hour service
We provide 7*24 hours service to our customers. We will be there whenever you need us.
Price advantage
All our products are priced very favorably because we have our own warehouse and supply.
| Company Information | |||
| [email protected] | |||
| Mobile | +8615980777398 | ||
| +8615980777398 | |||
| 15980777398 |

The Schneider NW40N2 Masterpact Circuit Breaker is a large-frame low-voltage air circuit breaker designed for power distribution and electrical protection in industrial facilities, commercial buildings, and large electrical installations. It belongs to Schneider Electric’s Masterpact NW family, a range developed for high-current distribution systems that require reliable switching, overload protection, and short-circuit protection.
Air circuit breakers are commonly installed in main distribution boards, switchgear assemblies, generator panels, and other electrical systems where large electrical loads must be controlled and protected. They help disconnect a circuit when abnormal electrical conditions occur, reducing the risk of equipment damage and supporting the safe operation of the distribution network.
The NW40N2 belongs to the 4000 A frame class. Its exact rated current, trip characteristics, and short-circuit performance depend on the installed trip unit, rating plug, voltage, and complete breaker configuration. These details should be checked against the product nameplate and the relevant Schneider Electric technical documentation before installation or replacement.
The Masterpact NW platform is designed for demanding power distribution applications. Depending on the selected configuration, the series can be supplied in fixed or drawout construction, with different connection arrangements, protection units, and accessories. These options allow electrical engineers to configure a breaker according to the requirements of a specific switchboard or distribution system.
The NW40N2 is particularly relevant to maintenance and replacement projects involving existing Masterpact NW installations. When sourcing this model, it is important to verify the complete catalog designation, number of poles, mounting arrangement, trip unit, connection type, and accessory configuration.
| Parameter | Specification |
|---|---|
| Brand | Schneider Electric |
| Product Series | Masterpact NW |
| Model | NW40N2 |
| Product Type | Air Circuit Breaker |
| Circuit Breaker Category | Low-Voltage Power Circuit Breaker |
| Frame Class | NW40 |
| Frame Rating | 4000 A |
| Rated Operating Voltage | Verify according to nameplate and configuration |
| Number of Poles | Confirm from the actual unit |
| Mounting Type | Verify fixed or drawout construction |
| Protection Type | Overload and short-circuit protection, according to trip-unit configuration |
| Trip Unit | Verify installed Micrologic or compatible protection unit |
| Connection Type | Verify front or rear connection arrangement |
| Dimensions Provided | 352 × 537 × 297 mm |
| Weight Provided | 80 kg |
| Application | Main power distribution and industrial switchgear |
Important: The frame class does not independently establish the complete breaker’s rated operating current or interrupting capacity. Confirm the trip unit, rating plug, voltage, pole count, and full product configuration from the nameplate and technical documentation. Dimensions and weight are the supplied listing values.
The NW40N2 is designed to provide switching and protection in high-current electrical distribution systems. Its operating mechanism and protection unit work together to detect abnormal electrical conditions and interrupt the circuit when required.
An overload occurs when a circuit carries more current than its intended operating capacity for a sustained period. If the condition continues, cables, busbars, transformers, and connected equipment may experience excessive heating.
The circuit breaker’s protection system monitors current and operates according to the selected trip settings. When an overload exceeds the configured protection threshold for the specified time, the breaker trips and disconnects the affected circuit.
The exact long-time protection settings depend on the installed trip unit and rating plug.
A short circuit can produce a very high current within a short period. Such faults may cause serious thermal and mechanical stress on electrical equipment.
The breaker is designed to interrupt fault current within its specified operating limits. Its short-circuit performance must be selected according to the prospective fault current at the installation point.
The applicable interrupting capacity depends on the exact breaker version and system voltage. Engineers should never assume that all NW40 models have identical short-circuit ratings.
Masterpact NW circuit breakers are used to switch electrical circuits during normal operation and to disconnect circuits when maintenance or fault conditions require isolation.
Depending on the configuration, the breaker may be equipped with operating mechanisms and accessories for local or remote operation. Electrical and mechanical interlocks can also be used in switchgear designs to help prevent unsafe operating sequences.
The breaker can form part of a coordinated protection system involving upstream and downstream circuit breakers, fuses, transformers, and other protective devices.
Correct coordination helps ensure that a fault is cleared by the appropriate protective device while limiting unnecessary interruption to unaffected sections of the electrical network.
Protection settings must be calculated and reviewed by qualified electrical engineers using the actual system parameters.
Depending on the installed accessories, a Masterpact NW breaker may provide auxiliary contacts and other status or control functions.
These signals can be connected to a PLC, building management system, or electrical monitoring platform. The available functions depend on the installed accessory package and should be checked before system integration.
The NW40N2 can serve as a main or feeder circuit breaker in large electrical distribution systems. It is generally installed in a switchboard or switchgear assembly and works with other power distribution components.
In a main distribution board, the breaker may be installed at the incoming supply point. It provides a means of switching and protecting the downstream distribution network.
Its frame class makes it relevant to high-current installations, but the actual protection settings must be selected according to the supply system, connected load, and prospective fault current.
The breaker may be used on the low-voltage side of a transformer to protect downstream distribution equipment. The protection design must consider transformer capacity, impedance, inrush current, cable ratings, and coordination with upstream protection.
In generator installations, circuit breakers are used to connect and disconnect generator supplies and protect distribution circuits. Correct selection requires consideration of generator short-circuit characteristics, transient behavior, and synchronization arrangements where applicable.
Although the circuit breaker is primarily a power protection device, its auxiliary contacts and compatible accessories may provide information to a PLC or electrical monitoring system.
This can support remote indication of breaker position, trip status, and selected operating conditions. The actual signals and communication capabilities depend on the installed accessories.
Large manufacturing facilities require high-capacity electrical distribution systems to supply production lines, motors, process equipment, and auxiliary services.
A Masterpact NW breaker can be used as part of the main distribution protection arrangement, subject to the system’s current and fault-level requirements.
Power generation plants use circuit breakers to control and protect electrical distribution circuits. Breakers may be installed in generator auxiliary systems, station service distribution, and other low-voltage switchgear applications.
The breaker must be selected according to the generator’s electrical characteristics and the distribution system’s protection requirements.
Industrial substations use low-voltage circuit breakers to protect outgoing feeders and distribution sections. The NW40N2 may be considered for high-current applications where its complete configuration meets the system design requirements.
Data centers require reliable power distribution to support servers, cooling equipment, UPS systems, and auxiliary infrastructure.
Large-frame circuit breakers can form part of the main low-voltage distribution architecture. Selection must account for load current, fault levels, selective coordination, and the availability of suitable maintenance arrangements.
Steel production, chemical processing, mining, and other heavy industrial operations often require high-capacity electrical distribution equipment.
A suitable Masterpact NW breaker can help protect major distribution circuits supplying transformers, large motor control centers, and process equipment.
Large commercial buildings, transport facilities, and infrastructure projects may use high-current air circuit breakers in their main electrical rooms.
The breaker can be incorporated into a coordinated switchgear design that supports controlled distribution and maintenance of the electrical network.
The installation of a large-frame air circuit breaker requires careful attention to mechanical mounting, electrical connections, protection settings, and switchgear compatibility.
Before installation, confirm the full model designation and the details shown on the nameplate.
Important information includes:
The NW40 frame class alone is not sufficient to determine all these characteristics.
The supplied dimensions are 352 × 537 × 297 mm. Confirm the actual height, width, and depth against the manufacturer’s dimensional drawing for the exact breaker configuration.
Check the available switchgear space, mounting supports, busbar alignment, connection clearances, and access for operation and maintenance.
Do not rely on dimensions from a visually similar Masterpact NW model because different pole counts and connection arrangements can change the installation envelope.
The breaker must be connected to busbars or conductors with suitable electrical and mechanical ratings.
Connection design should consider:
All electrical connections should follow the manufacturer’s instructions and applicable electrical standards.
The trip unit must be configured according to the electrical system’s protection study.
Depending on the installed protection unit, settings may include long-time, short-time, instantaneous, and ground-fault protection functions.
Incorrect settings can cause unnecessary trips or insufficient protection. Protection coordination should be reviewed by qualified engineers before the breaker is placed into service.
If the breaker is part of a remote monitoring or control system, verify the installed auxiliary contacts, shunt trip, undervoltage release, motor mechanism, and other accessories.
Check the control voltage and terminal assignments before connecting the breaker to PLC or supervisory control circuits.
Not every NW40N2 configuration includes the same accessory package.
Before energizing the equipment, inspect the breaker, switchgear, busbar connections, grounding, and control wiring.
Commissioning should include appropriate mechanical and electrical checks, verification of protection settings, and functional testing according to the manufacturer’s procedures.
Testing of high-current circuit breakers should be performed by qualified personnel using suitable equipment and approved safety procedures.
The NW40N2 is normally used with other power distribution and protection components.
| Component | Function | Integration Considerations |
|---|---|---|
| Low-voltage switchgear | Houses and supports the breaker | Confirm frame dimensions, mounting arrangement, and clearances |
| Busbar system | Distributes electrical power | Verify current rating, connection geometry, and short-circuit withstand |
| Micrologic trip unit | Provides electronic protection functions | Confirm exact trip-unit type and compatibility |
| Rating plug | Establishes the applicable current rating settings | Verify compatibility and protection requirements |
| Auxiliary contacts | Provide breaker status signals | Check contact ratings and terminal assignments |
| Shunt trip accessory | Enables remote tripping | Confirm control voltage and accessory compatibility |
| Undervoltage release | Trips or prevents operation under specified voltage conditions | Verify control supply and operating characteristics |
| Motor operating mechanism | Supports electrical charging or operation where configured | Confirm the installed mechanism and supply requirements |
| PLC | Monitors and coordinates selected breaker signals | Requires suitable auxiliary contacts or compatible communication hardware |
| Power monitoring system | Monitors electrical distribution conditions | Verify measurement devices and communication architecture |
The components listed above are possible elements of a complete installation. They are not necessarily included with the NW40N2 breaker.
The Masterpact NW family includes several frame ratings and performance versions. Replacement selection should be based on electrical ratings and mechanical configuration rather than frame appearance alone.
| Alternative or Related Model | Description | Replacement Considerations |
|---|---|---|
| Masterpact NW08 | 800 A frame class | Lower frame rating; not a direct substitute for an NW40 application |
| Masterpact NW10 | 1000 A frame class | Suitable only where the required current and fault ratings permit |
| Masterpact NW20 | 2000 A frame class | Different frame capacity and installation requirements |
| Masterpact NW25 | 2500 A frame class | Check system current and protection coordination |
| Masterpact NW32 | 3200 A frame class | May be considered only after electrical and mechanical evaluation |
| Masterpact NW40 | 4000 A frame class | Compare trip unit, interrupting capacity, pole count, and connection arrangement |
| Current-generation Masterpact products | Newer Schneider Electric circuit breaker ranges | May require switchgear modifications and engineering review |
Before selecting a replacement, compare:
A replacement with the same frame rating is not automatically interchangeable. The complete breaker configuration must match the electrical and mechanical requirements of the installation.
The NW40 frame class is designed for high-current applications, making it relevant to large industrial and commercial distribution systems.
The Masterpact NW family supports configurable protection arrangements. The available protection functions depend on the installed trip unit and accessories.
The product family offers different mounting and connection arrangements, allowing engineers to select a configuration suited to the switchgear design.
Compatible auxiliary contacts and accessories can provide breaker status information to control and monitoring systems.
The Masterpact NW platform is designed for low-voltage power distribution applications in industrial facilities and large electrical installations.
The product’s established installed base makes accurate identification of the breaker, trip unit, and accessories important for maintenance planning and spare-parts sourcing.
The Schneider NW40N2 is a Masterpact NW series low-voltage air circuit breaker intended for high-current electrical distribution and protection applications.
NW40 identifies the 4000 A frame class within the Masterpact NW product family. The actual trip rating and operating settings depend on the installed trip unit and rating plug.
The NW40 frame class is 4000 A. The actual rated current and applicable protection settings should be verified from the breaker nameplate and installed trip-unit configuration.
A fixed breaker is mounted directly into the switchgear structure. A drawout breaker is installed in a compatible cradle and can be moved between defined positions for operation, testing, or isolation, following the manufacturer’s procedures.
It can be used in a suitable transformer feeder protection arrangement if its voltage, current, interrupting capacity, trip unit, and protection settings meet the system requirements.
Selected breaker status and control functions can be integrated into a PLC system through compatible auxiliary contacts and accessories. The available signals depend on the installed configuration.
A compatible Micrologic trip unit provides electronic protection functions. Depending on the model, these may include overload, short-time, instantaneous, and ground-fault protection.
Check the complete catalog number, nameplate, rated voltage, current, interrupting capacity, pole count, mounting arrangement, trip unit, and accessory configuration. Also confirm whether the breaker is new, used, or refurbished.
The supplied listing weight is 80 kg. Actual weight can vary according to pole count, mounting arrangement, connection configuration, trip unit, and accessories. Confirm the physical unit’s weight before calculating shipping costs or handling requirements.
Not automatically. Other NW models may have different frame ratings, dimensions, interrupting capacities, and accessory configurations. A replacement must be evaluated against the original electrical and mechanical specifications.
When sourcing the Schneider NW40N2, begin by checking the complete breaker designation and nameplate information. The frame class alone does not identify every electrical and mechanical characteristic needed for a safe replacement.
For new, used, or refurbished equipment, request clear photographs of the front, side, rear connections, nameplate, trip unit, and accessory compartments. Confirm the pole count, fixed or drawout arrangement, and whether the breaker is supplied with the required cradle or accessories.
For maintenance, follow the manufacturer’s inspection and service procedures. Relevant checks may include operating mechanism condition, contact wear, connection integrity, insulation condition, protection-unit settings, and accessory operation.
High-current circuit breakers should be inspected and tested by qualified personnel. Before maintenance, isolate the equipment, apply the required lockout procedures, and verify the absence of hazardous voltage.
For replacement projects, review the protection coordination study and switchgear design before ordering. Confirm that the replacement has suitable electrical ratings, mechanical dimensions, connection arrangements, and accessory compatibility.
The Schneider NW40N2 Masterpact Air Circuit Breaker is a large-frame low-voltage protection device designed for high-current industrial and commercial power distribution systems. Its NW40 frame class corresponds to 4000 A, while the actual trip rating, breaking capacity, and operating characteristics depend on the complete breaker configuration.
For maintenance and replacement applications, engineers should verify the nameplate, trip unit, pole count, mounting arrangement, and connection design before selecting the unit. Accurate configuration matching is essential for safe installation and reliable operation in industrial switchgear.