The Allen Bradley 1788-FBJB4R is a 4-way redundant intelligent fieldbus junction box designed for FOUNDATION Fieldbus H1 and PROFIBUS-PA networks. It belongs to the Allen-Bradley Bulletin 1788 family and provides a fault-tolerant connection between field instruments and the main fieldbus trunk.
The junction box provides four field device drop-line connections and supports redundant trunk arrangements. Its internal monitoring circuits continuously supervise the connected drops and trunk conditions, helping prevent a fault on one connection from interrupting communication across the entire fieldbus segment.
One of its main functions is automatic fault isolation. When an individual drop develops an overcurrent condition or short circuit, the unit disconnects the affected branch while allowing the remaining field devices to continue operating.
The 1788-FBJB4R also monitors redundant trunk connections. If a trunk cable fault occurs, the junction box can reroute communication through the alternate path, improving fieldbus network availability.
Status LEDs provide information about fieldbus power and fault conditions, allowing maintenance personnel to identify wiring problems during commissioning and routine operation.
The unit is suitable for process automation systems that require protected field instrument connections and redundant fieldbus communication paths.
| Parameter | Specification |
|---|---|
| Manufacturer | Allen-Bradley |
| Brand Owner | Rockwell Automation |
| Model | 1788-FBJB4R |
| Product Series | Bulletin 1788 |
| Product Type | FOUNDATION Fieldbus Redundant Junction Box |
| Official Product Designation | 1788 Redundant FF 4 Way Junction Box |
| Supported Protocols | FOUNDATION Fieldbus H1 and PROFIBUS-PA |
| Field Device Drop Ports | 4 |
| Network Configuration | Redundant Fieldbus |
| Power Supply Input | 12–32V DC, 0.5 A |
| Trunk Output | 12–32V DC, 0.36 A, Resistive Only |
| Drop Output | 12–32V DC, 40 mA, Resistive Only |
| Power Consumption | 40 mA at 24V DC, Maximum |
| Trunk Trip Current | 490 mA |
| Fault Protection | Drop Overcurrent and Trunk Fault Monitoring |
| Trunk Redundancy | Supported |
| Automatic Fault Isolation | Supported |
| Communication Channel Isolation | No Isolation |
| Status Indication | LED Indicators |
| Wiring Type | Copper Wire |
| Wire Size | 0.205–0.823 mm² (24–18 AWG) |
| Terminal Torque | 0.5–0.6 N·m |
| Conductor Temperature Rating | Above 82°C |
| Enclosure Type | Open-Style |
| Operating Temperature | 0–60°C |
| Storage Temperature | 0–60°C |
| Temperature Code | T4 |
| Dimensions | 114.5 × 35.7 × 99 mm |
| Weight | 0.34 kg |
The 1788-FBJB4R operates as an intelligent fieldbus junction box. It distributes the main fieldbus connection to individual field instrument drops while continuously monitoring the electrical condition of the network.
Its operation involves several stages.
1. Fieldbus Trunk Connection
The main FOUNDATION Fieldbus H1 or PROFIBUS-PA trunk connects to the junction box. In a redundant configuration, two trunk paths provide alternative communication routes.
2. Field Device Distribution
The junction box distributes the fieldbus connection to four individual drop-line ports. Each port provides a connection point for a field instrument such as a transmitter or valve positioner.
3. Drop-Line Current Monitoring
The internal protection circuits monitor the current drawn by each field device connection. If a drop develops an overcurrent condition, the affected branch is disconnected to prevent the fault from affecting the other instruments.
4. Trunk Monitoring
The device monitors trunk connections for open-circuit and short-circuit conditions. In redundant installations, the alternate trunk provides another communication path when a cable fault occurs.
5. Trunk Trip Protection
When the trunk current exceeds the specified trip threshold, the protection circuit disconnects the affected trunk. The fault condition is indicated through the red LED.
6. Fault Reset
After the electrical fault has been corrected, the trunk trip can be reset using the reset button or the automatic reset configuration through DIP switches 3 and 4.
A simplified network arrangement is:
Fieldbus Trunk A / Trunk B → 1788-FBJB4R → Four Protected Drop Connections → Field Instruments
The junction box provides network distribution and electrical fault protection rather than performing controller logic or field instrument measurement.
Within a process automation system, the 1788-FBJB4R is installed between the main fieldbus trunk and the individual field instruments.
It provides protected branch connections and supports redundant trunk arrangements, making it particularly useful in installations where a short circuit or wiring fault on one field device should not interrupt the entire communication segment.
| System Component | Function |
|---|---|
| 1788-FBJB4R | Provides four protected fieldbus drop connections |
| 1788-EN2FFR | Connects EtherNet/IP with FOUNDATION Fieldbus H1 |
| 1788-CN2FFR | Connects ControlNet with FOUNDATION Fieldbus H1 |
| 1788-EN2PAR | Connects EtherNet/IP with PROFIBUS-PA |
| 1788-CN2PAR | Connects ControlNet with PROFIBUS-PA |
| FOUNDATION Fieldbus H1 Cable | Carries digital communication and fieldbus power |
| PROFIBUS-PA Cable | Connects PA field instruments |
| Pressure Transmitters | Measure process pressure |
| Temperature Transmitters | Measure process temperature |
| Flow Transmitters | Measure process flow |
| Valve Positioners | Receive valve positioning commands |
The 1788-FBJB4R is used in process installations where fieldbus connections require individual branch protection and redundant communication paths.
| Industrial Application | Typical Use |
|---|---|
| Oil and Gas | Protecting field instrument connections in process facilities |
| Petrochemical Plants | Distributing FOUNDATION Fieldbus instrumentation |
| Chemical Processing | Connecting pressure and temperature transmitters |
| Refining Operations | Supporting redundant fieldbus trunk installations |
| Power Generation | Connecting process monitoring instruments |
| Water Treatment | Distributing fieldbus connections to process sensors |
| Pharmaceutical Manufacturing | Protecting instrument communication branches |
| Pulp and Paper | Connecting field instruments to process networks |
| Offshore Platforms | Supporting redundant fieldbus communication |
| Industrial Process Plants | Isolating faulty instrument drops without affecting other devices |
| Component | Function |
|---|---|
| Allen-Bradley 1788-FBJB4R | 4-Way Redundant Intelligent Fieldbus Junction Box |
| Allen-Bradley 1788-FBJB6 | 6-Way Intelligent Fieldbus Junction Box |
| Allen-Bradley 1788-EN2FFR | EtherNet/IP to FOUNDATION Fieldbus H1 Linking Device |
| Allen-Bradley 1788-CN2FFR | ControlNet to FOUNDATION Fieldbus H1 Linking Device |
| Allen-Bradley 1788-EN2PAR | EtherNet/IP to PROFIBUS-PA Linking Device |
| Allen-Bradley 1788-CN2PAR | ControlNet to PROFIBUS-PA Linking Device |
| FOUNDATION Fieldbus H1 Transmitters | Process measurement devices |
| PROFIBUS-PA Instruments | Field-level process measurement and control equipment |
| Model | Product Type | Application |
|---|---|---|
| Allen-Bradley 1788-FBJB6 | 6-Way Intelligent Fieldbus Junction Box | Multiple field instrument connections |
| Allen-Bradley 1788-EN2FFR | EtherNet/IP to FOUNDATION Fieldbus H1 Linking Device | EtherNet/IP fieldbus integration |
| Allen-Bradley 1788-CN2FFR | ControlNet to FOUNDATION Fieldbus H1 Linking Device | ControlNet fieldbus integration |
| Allen-Bradley 1788-EN2PAR | EtherNet/IP to PROFIBUS-PA Linking Device | PROFIBUS-PA network integration |
| Allen-Bradley 1788-CN2PAR | ControlNet to PROFIBUS-PA Linking Device | ControlNet and PROFIBUS-PA integration |
| Allen-Bradley 1788-FBJB4 | FOUNDATION Fieldbus 4-Way Junction Box | Non-redundant fieldbus distribution |
The 1788-FBJB4R provides four individual drop-line ports. Each port can connect a compatible FOUNDATION Fieldbus H1 or PROFIBUS-PA field instrument, subject to the electrical and network loading limits.
The junction box monitors the individual drop connections and isolates the faulty branch when an overcurrent condition is detected. The remaining fieldbus connections can continue operating without being affected by that individual drop fault.
The device monitors the redundant trunk connections. When an open-circuit or short-circuit condition is detected, it can reroute trunk communication through the alternate path, helping maintain fieldbus network availability.
After the cause of the overcurrent condition has been corrected, the trunk trip can be reset using the dedicated reset button. Alternatively, DIP switches 3 and 4 can be configured for automatic reset.