The Schneider TM3AM6G is a mixed analog input/output expansion module in the Modicon TM3 family. Unlike the TM3AI4 and TM3AI8, which are dedicated analog input modules, the TM3AM6G combines four analog input channels and two analog output channels in one compact unit. This allows a Modicon PLC to acquire process measurements and send analog control signals through the same expansion module.
The module supports both voltage and current signals. Its input and output channels accommodate 0–10 V, -10–10 V, 0–20 mA, and 4–20 mA ranges, making it suitable for applications where field instruments and controlled devices use different analog interfaces.
A typical example is a pump station with pressure transmitters and variable speed drives. The four input channels can collect pressure, flow, or other process measurements, while the two output channels send voltage or current reference signals to external equipment. The PLC processes the incoming values and adjusts its outputs according to the programmed control strategy.
This arrangement is also useful in process machinery where several measurement points must be monitored while one or two actuators receive continuous control references. Instead of installing separate input and output modules, the TM3AM6G handles both signal directions within one I/O position.
The TM3AM6G uses removable spring terminal blocks for electrical connections. Its terminal design is particularly relevant in control cabinets where maintenance personnel prefer spring-clamp wiring rather than screw-terminal connections.
When selecting this module for an existing installation, check the controller compatibility, input and output signal ranges, terminal arrangement, and PLC channel configuration. The TM3AM6G and TM3AM6 share the same basic mixed-I/O functionality, but use different terminal connection methods.
| Parameter | Specification |
|---|---|
| Manufacturer | Schneider Electric |
| Model | TM3AM6G |
| Product Family | Modicon TM3 |
| Product Type | Input/Output Analog Module |
| Number of Analog Inputs | 4 |
| Number of Analog Outputs | 2 |
| Analog Input Type | Voltage / Current |
| Analog Output Type | Voltage / Current |
| Input Voltage Range | 0–10 V / -10–10 V |
| Input Current Range | 0–20 mA / 4–20 mA |
| Output Voltage Range | 0–10 V / -10–10 V |
| Output Current Range | 0–20 mA / 4–20 mA |
| Analog Input Resolution | 12 bits / 11 bits + sign |
| Analog Output Resolution | 12 bits / 11 bits + sign |
| Rated Supply Voltage | 24 V DC |
| Supply Voltage Range | 20.4–28.8 V DC |
| Input Impedance | ≤ 50 Ω (Current) / ≥ 1 MΩ (Voltage) |
| Permissible Continuous Input Overload | 13 V (Voltage) / 40 mA (Current) |
| Output Load Impedance | ≥ 1 kΩ (Voltage) / ≤ 300 Ω (Current) |
| Stabilisation Time | 1 ms |
| Conversion Time | 1 ms + 1 ms per channel + 1 controller cycle time |
| Output Ripple | 20 mV |
| Non-Linearity | ±0.2% FS |
| Repeat Accuracy | ±0.5% FS (Input) |
| Temperature Drift | ±0.01% FS/°C |
| Cross Talk | ≤ 1 LSB |
| Output Load Type | Resistive |
| Input Connection | Removable Spring Terminal Block |
| Terminal Pitch | 3.81 mm |
| Cable Requirement | Twisted Shielded Pair, Maximum 30 m |
| Protection Degree | IP20 |
| Compatible Controllers | Modicon M221 / M241 / M251 / M262 |
| Input-to-Internal Logic Insulation | 500 V AC |
| Input-to-Supply Insulation | 1500 V AC |
| Output-to-Internal Logic Insulation | 500 V AC |
| Output-to-Supply Insulation | 1500 V AC |
| Dimensions | 90 × 23.6 × 70 mm |
| Weight | 0.1 kg |
The TM3AM6G handles two different signal operations: acquiring analog measurements from field instruments and generating analog reference signals for external equipment.
Its signal flow can be represented as:
Field Transmitters → TM3AM6G Analog Inputs → Modicon PLC → TM3AM6G Analog Outputs → Controlled Devices
On the input side, four channels receive voltage or current signals from connected instruments. For example, a pressure transmitter may send a 4–20 mA signal representing the pressure inside a pipeline. The module converts this electrical signal into a digital value that the PLC can use in its control program.
On the output side, two channels convert the controller’s digital output values into corresponding analog signals. These outputs can be configured for voltage or current operation, depending on the connected equipment.
Consider a variable-speed pump application. The PLC receives pressure feedback through one of the TM3AM6G input channels. If the measured pressure falls below the required setpoint, the control program can adjust the analog output sent to the drive’s speed reference input. As pump speed changes, the pressure transmitter continues sending updated measurements to the input side.
This creates a continuous feedback process rather than a simple digital start/stop command.
The input and output channels support several standard signal ranges, but the physical wiring and software configuration must match. The output load must also remain within the specified impedance limits. For voltage outputs, the load impedance must be at least 1 kΩ, while current outputs require a load impedance not exceeding 300 Ω.
The module’s conversion timing should be considered when configuring applications that depend on frequent measurement updates and output adjustments. The overall timing includes channel conversion and the controller cycle.
The TM3AM6G serves as a mixed analog I/O interface within a Modicon TM3 expansion arrangement. Its main advantage is that measurement acquisition and analog command generation can be handled through the same module.
A typical control arrangement is:
Field Sensors → TM3AM6G Inputs → TM3 Expansion Bus → Modicon PLC → TM3AM6G Outputs → Drives / Control Devices
| System Element | Function |
|---|---|
| TM3AM6G | Acquires four analog signals and generates two analog output signals |
| Pressure Transmitters | Supply continuous pressure measurements |
| Flow Sensors | Provide analog flow feedback |
| Position Sensors | Supply variable position measurements |
| TM3 Expansion Bus | Transfers I/O data between the module and controller |
| Modicon M221 | Processes machine-control and analog I/O data |
| Modicon M241 | Handles machine automation and motion-related control |
| Modicon M251 | Supports connected machine-control architectures |
| Modicon M262 | Handles advanced machine-control applications |
| EcoStruxure Machine Expert | Configures analog channels and PLC application logic |
| Variable Speed Drives | Receive analog speed or reference commands |
| Proportional Control Valves | Receive analog signals for continuous valve positioning |
In a closed-loop pressure control application, the input channels collect measurements from the process while an output channel sends the PLC’s control reference to a drive or proportional actuator. This makes the TM3AM6G suitable for machines where analog feedback and analog commands need to operate together.
The two output channels can also be assigned to separate devices, allowing the PLC to control two independent analog references while continuing to monitor up to four input signals.
| Application | Typical Use |
|---|---|
| Pump Control Systems | Collecting pressure and flow feedback while sending speed references to drives |
| Water Treatment | Monitoring process measurements and controlling proportional equipment |
| HVAC Systems | Acquiring pressure signals and generating analog control references |
| Packaging Machinery | Reading process feedback and controlling analog-positioning devices |
| Chemical Processing | Monitoring process variables and adjusting proportional valves |
| Food and Beverage Production | Collecting flow measurements and controlling process equipment |
| Compressor Control Systems | Monitoring analog operating signals and providing external control references |
| Material Processing | Acquiring sensor feedback and controlling variable-speed equipment |
| Industrial Automation | Combining analog measurement and output control within one PLC expansion module |
| Manufacturing Lines | Monitoring multiple process signals while adjusting connected actuators |
| Component | Function |
|---|---|
| TM3AM6 | Four-channel analog input and two-channel analog output module with screw terminals |
| TM3AI4 | Four-channel analog input module |
| TM3AI8 | Eight-channel analog input module |
| TM3AI4G | Four-channel analog input module with spring terminals |
| TM3AI8G | Eight-channel analog input module with spring terminals |
| TM3TM3 | Temperature and analog input/output expansion module |
| Modicon M221 | PLC controller supporting TM3 expansion I/O |
| Modicon M241 | Machine controller with TM3 expansion capability |
| Modicon M251 | Controller for connected machine architectures |
| 24 V DC Power Supply | Supplies the required external module power |
| Variable Speed Drive | Receives analog speed reference signals |
| Proportional Valve | Uses analog commands for continuous actuator positioning |
| Model | Product Type | Typical Application |
|---|---|---|
| Schneider TM3AM6 | Analog Input/Output Module | Four analog inputs and two analog outputs with screw terminals |
| Schneider TM3AI4 | Analog Input Module | Four-channel voltage and current signal acquisition |
| Schneider TM3AI8 | Analog Input Module | Eight-channel analog measurement applications |
| Schneider TM3AI4G | Analog Input Module | Four-channel analog acquisition with spring terminals |
| Schneider TM3AI8G | Analog Input Module | Eight-channel analog acquisition with spring terminals |
| Schneider TM3TM3 | Temperature and Analog Input/Output Module | Combined temperature measurement and analog control applications |
Yes. The module has four analog input channels and two analog output channels. The inputs collect measurements from field instruments, while the outputs generate voltage or current references for external equipment. Both functions can operate within the same PLC application.
The module supports voltage and current output ranges, including 0–10 V, -10–10 V, 0–20 mA, and 4–20 mA. The required output configuration must match the connected device and the physical wiring. The PLC program must also use the corresponding output channel settings.
Both modules provide four analog inputs and two analog outputs with the same general signal ranges. The main difference is the terminal connection method. TM3AM6 uses removable screw terminal blocks, whereas TM3AM6G uses removable spring terminal blocks. This distinction should be considered when replacing a module in an existing control cabinet.
Yes. One of its analog output channels can generate a voltage or current reference for a compatible drive. For example, a 0–10 V signal can be used as a speed reference when the drive is configured for that input type. The PLC can use the module’s analog input channels to acquire process feedback and adjust the output reference according to the programmed control logic.