This module blends the thermocouple conditioning unit (163179‑01) with a non‑isolated I/O board (133819‑01), delivering a six‑channel temperature monitor. It supports both RTDs and thermocouples, offering customizable dual setpoint alarms, and integrates seamlessly into a 3500 Rack System for robust temperature condition monitoring.
| Parameter | Details |
|---|---|
| Model | 3500/61 (163179‑01 + 133819‑01) |
| Input Channels | 6 (RTDs or Thermocouples) |
| Input Types Supported | RTDs (2-/3‑wire), Thermocouples (J, K, T, E, R, S, B, N, etc.) |
| Input Impedance | Greater than 10 MΩ |
| Measurement Accuracy | ± 1 °C (typical) |
| Resolution | Approximately 0.1 °C |
| Alarm Functionality | Two levels per channel: Alert and Danger |
| Power Supply | Supplied via 3500 Rack backplane |
| Operating Temperature | –30 °C to +65 °C |
| Storage Temperature | –40 °C to +85 °C |
| Humidity Range | 0–95% RH, non‑condensing |
| Dimensions (mm) | 241.3 (H) × 24.4 (W) × 163.1 (D) |
| Weight (kg) | 0.9 kg |
| I/O Isolation | None (non‑isolated version) |
| Rack Integration | Fits standard 3500 rack slot |
| Certifications | Industrial safety rated (e.g., CE, CSA, ATEX/IECEx Zone 2 capable) |
Motors & Generators – Monitor bearing and winding temperatures.
Turbomachinery – Protect turbines and compressors from thermal stress.
Pumps & Gearboxes – Detect overheating early in bearings or gear trains.
Process Loops – Keep reactor and vessel temperatures within safe limits.
Electrical Panels – Monitor cabinet or enclosure heat buildup.
Mixed Sensor Support – Allows RTD and thermocouple use on any channel.
Compact & Efficient – Six configurable channels in a single slot.
Custom Alarm Logic – Two-tier alarms for timely warning and action.
Reliable Construction – Handles industrial conditions and thermal stress.
System-ready – Seamlessly integrates with existing 3500 Series infrastructure.
| Model | Purpose |
|---|---|
| 3500/60 | Thermocouple inputs with standard I/O module |
| 3500/65 | Two-channel tachometer / Keyphasor module |
| 3500/50M | Two-channel tachometer input module |
| 3500/42M | Proximity / seismic displacement monitoring module |
| 3500/53M | Dual-channel overspeed detection module |
| Model | Function |
|---|---|
| 3500-TIV-CPU | Rack CPU with trending and alarm handling |
| 3500/22M | Dual displacement monitoring module |
| 3500/44M | Compact vibration detection module |
| 3500/33 | Relay output module for alarms and controls |
| 3500/15 | Rack power supply module |
Q1: Can I mix RTDs and thermocouples per channel?
A1: Yes, each of the six channels can be individually configured for either RTD or thermocouple input.
Q2: Are the inputs isolated?
A2: No. This version uses a non-isolated input board. Isolation is available via other module versions if required.
Q3: What are the module’s size and weight?
A3: Measures 241.3 × 24.4 × 163.1 mm, and weighs approximately 0.9 kg.
Q4: What types of alarms are supported?
A4: Each channel supports both Alert (warning) and Danger (shutdown) threshold settings.
Q5: What environmental conditions can it handle?
A5: Rated for –30 °C to +65 °C ambient and up to 95% non-condensing humidity.
Q6: Is the module compatible with older systems?
A6: Yes, it’s fully compatible with existing 3500 rack infrastructure and configuration tools.
Q7: Does it require external power?
A7: No, power is drawn from the 3500 Rack backplane.
Q8: Can it be used redundantly?
A8: Yes, identical modules can be deployed to form redundant protection schemes.
Q9: What certification does it carry?
A9: Meets industrial safety standards and is suitable for use in hazardous zones (ATEX/IECEx Zone 2).
Q10: How is configuration handled?
A10: Configuration is typically performed via associated rack configuration or diagnostic software tools.
Authenticity guarantee
All product specifications are original and authentic imported products. We have an annual sales volume of 300 million yuan, and we only produce original and authentic products. All customers who cooperate with us directly online can enjoy low discounts.
Free warehouse
We have a complete range of product models, 80% of conventional models are in stock, and we have established channels in Asia, Africa, North America, South America, and Europe, effectively shortening the order processing time and satisfying customers in a timely manner.
Technical Team
Fast delivery. Spot goods can be shipped on the same day, and the delivery time transaction is 20% faster than that of peers on average, with a delivery time accuracy rate of 99%.
Thoughtful after-sales service
24-hour after-sales service guarantee team, professional and standardized management service system.