• Allen Bradley 1790-0V16X CompactBlock LDX Digital Output Expansion Block
  • Allen Bradley 1790-0V16X CompactBlock LDX Digital Output Expansion Block
  • Allen Bradley 1790-0V16X CompactBlock LDX Digital Output Expansion Block
  • Allen Bradley 1790-0V16X CompactBlock LDX Digital Output Expansion Block
Product Overview The Allen Bradley 1790-0V16X CompactBlock LDX Digital Output Expansion Block is a 16-point DC sinking output expansion module used to increase the digital output capacity of a CompactBl……
Allen Bradley 1790-0V16X CompactBlock LDX Digital Output Expansion Block
  • Allen Bradley
  • 1790-0V16X
  • Digital Output Expansion Block
  • USA
  • 104 × 42 × 52 mm
  • 0.1 kg
  • Xiamen, China
  • New & In Stock
  • T/T, PayPal, Western Union
  • 1 Year
  • 1-3 Working Days
  • DHL, UPS, TNT, FedEx and EMS.
  • 24-Hour Service
  • COO
  • 5

Our advantage

Allen Bradley 1790-0V16X CompactBlock LDX Digital Output Expansion Block

Global Logistics

We have a 10-year logistics and express cooperation agreement, so our products can be shipped to any place in the world.

Allen Bradley 1790-0V16X CompactBlock LDX Digital Output Expansion Block

Brand new and original

Our products are imported in bulk from the place of origin. Because of the cooperative relationship, our products are all original and 100% new.

Allen Bradley 1790-0V16X CompactBlock LDX Digital Output Expansion Block

24-hour service

We provide 7*24 hours service to our customers. We will be there whenever you need us.

Allen Bradley 1790-0V16X CompactBlock LDX Digital Output Expansion Block

Price advantage

All our products are priced very favorably because we have our own warehouse and supply.


Company Information
E-mail [email protected]
Mobile +8615980777398
Whatsapp +8615980777398
WeChat 15980777398

Product Overview

The Allen Bradley 1790-0V16X CompactBlock LDX Digital Output Expansion Block is a 16-point DC sinking output expansion module used to increase the digital output capacity of a CompactBlock LDX distributed I/O assembly. It operates with a nominal 24 V DC field supply and provides additional switching channels for controlling compatible industrial devices.

Unlike the 1790-0B16X, which uses sourcing outputs, the 1790-0V16X uses sinking output circuitry. When an output is activated, the channel switches the connected load toward the DC common (GND), allowing current to flow from the positive field supply through the load and into the module output. This distinction is important when selecting compatible solenoid valves, relay interfaces, and other DC-operated equipment.

The module provides 16 individual output points arranged in two groups of eight. Each output supports up to 0.5 A, with a maximum current rating of 4 A per common. Its 37-pin D-shell connector provides the field wiring interface, while the expansion ribbon cable connects the module to a compatible CompactBlock LDX base block.

A typical application can be found in a conveyor handling system with multiple pneumatic actuators. The main CompactBlock LDX base block communicates with the PLC through DeviceNet, while the 1790-0V16X adds output channels for controlling diverter valves, pneumatic stops, and other machine functions. The PLC activates individual channels according to product position and sensor information.

The sinking output arrangement is particularly relevant when the connected devices are wired with their positive terminals connected to the field supply and their switched return connected to the module outputs. The common terminals must be wired according to the specified 24 V DC supply arrangement.

Another practical feature is the module’s photocoupler isolation between the field I/O circuits and internal logic circuits. This provides electrical separation between the output circuitry and the expansion logic, with a specified isolation voltage of 1250 V AC RMS.

The 1790-0V16X also supports relatively fast output switching, with a maximum delay of 0.5 ms from OFF to ON and 1.0 ms from ON to OFF. Sixteen green status indicators allow maintenance personnel to check individual output conditions during commissioning and troubleshooting.

For existing DeviceNet installations, the expansion architecture makes it possible to add output capacity without installing another independent network node. The base block remains responsible for network communication, while the 1790-0V16X handles additional field switching operations.

The module is suitable for distributed machine-control applications where 24 V DC sinking outputs are required and the existing CompactBlock LDX system needs additional output points.


Technical Specifications

Parameter Specification
Manufacturer Allen-Bradley
Model 1790-0V16X
Product Type CompactBlock LDX 16-Point Digital Output Expansion Block
Product Family CompactBlock LDX
Module Category Digital Output Expansion Module
Network System DeviceNet through Compatible Base Block
Number of Outputs 16 Points
Output Type DC Sinking
Output Isolation Non-Isolated Outputs
Nominal Field Voltage 24 V DC
Field Supply Voltage Range 10–28.8 V DC
Maximum Output Current 0.5 A per Output
Maximum Current per Common 4 A
Output On-State Voltage 10 V DC Minimum, 24 V DC Nominal, 28.8 V DC Maximum
Maximum On-State Voltage Drop 0.5 V DC
Minimum On-State Current 1 mA per Channel
Maximum Off-State Voltage 28.8 V DC
Maximum Off-State Leakage 0.5 mA
Output Signal Delay 0.5 ms Maximum OFF to ON; 1.0 ms Maximum ON to OFF
Output Indicators 16 Green Status LEDs
Common Arrangement 8 Points / 2 COM
Field Power Dissipation 2.76 W at 28.8 V DC
Field Connector 37-Pin D-Shell
Expansion Connection Ribbon Cable
I/O-to-Logic Isolation Photocoupler Isolation
Isolation Voltage 1250 V AC RMS
Mounting Type DIN Rail or Panel Mounting
Dimensions 104 × 42 × 52 mm
Weight 0.1 kg

Product Features

  • 16 Sinking Output Points: Adds 16 DC sinking output channels to a compatible CompactBlock LDX assembly.
  • 24 V DC Operation: Supports a nominal 24 V DC field supply with an operating range of 10–28.8 V DC.
  • 0.5 A Per-Point Rating: Handles individual output loads up to 0.5 A.
  • 4 A Per-Common Rating: Supports a maximum current of 4 A for each common connection.
  • Eight-Point Grouping: Arranges the outputs into two groups of eight with separate common connections.
  • 37-Pin D-Shell Connection: Provides the electrical interface for external field wiring.
  • Ribbon Cable Expansion: Connects to a compatible CompactBlock LDX base block.
  • Photocoupler Isolation: Provides 1250 V AC RMS isolation between field I/O and logic circuits.
  • Individual Output Indicators: Uses 16 green LEDs to display output status.
  • Fast Switching Response: Supports maximum OFF-to-ON and ON-to-OFF delays of 0.5 ms and 1.0 ms, respectively.
  • Distributed Output Expansion: Adds local output capacity without requiring an independent DeviceNet connection.

Working Principle

The 1790-0V16X operates as a sinking digital output stage within a CompactBlock LDX distributed I/O assembly. It receives output commands through the expansion connection and switches the corresponding field circuits toward the DC common.

Its basic control arrangement is:

PLC Controller → DeviceNet → CompactBlock LDX Base Block → Expansion Ribbon Cable → 1790-0V16X → Field Devices

Output Command Processing

When the PLC activates an output address, the DeviceNet-connected base block receives the corresponding control data. The output information is transferred to the 1790-0V16X through the ribbon cable connection.

The expansion module then activates the selected output channel, allowing the connected field device to operate.

For example, when a PLC program activates an output assigned to a pneumatic diverter, the corresponding output channel switches toward DC common. Current flows through the connected solenoid valve, causing the valve to change state and operate the pneumatic cylinder.

Sinking Output Operation

The main characteristic of this module is its sinking output configuration.

In a typical 24 V DC circuit, the positive side of the field supply connects to the load. The other side of the load connects to the output channel. When the output is activated, the module provides the current return path toward GND.

The basic current path is:

+24 V DC → Field Load → 1790-0V16X Output → DC Common

This wiring arrangement differs from a sourcing output module, where the output supplies positive voltage to the load.

For this reason, the 1790-0V16X must be matched with field devices and wiring arrangements compatible with sinking outputs.

Independent Channel Switching

The module provides 16 output channels that can be controlled individually through the I/O data received from the base block.

In an automated assembly machine, separate channels may control pneumatic clamps, material stops, indicator circuits, and relay interfaces. The PLC can switch each device according to the production sequence without requiring a separate expansion module for every actuator.

Output Current Management

Each output supports a maximum current of 0.5 A, while the maximum current per common is 4 A.

Both limits must be considered when planning the field wiring. For example, several solenoid valves may each operate within the individual channel rating, but their combined current must also remain within the permitted common rating.

The two groups of eight outputs have their own common connections, allowing the field circuits to be arranged according to the module’s wiring configuration.

Photocoupler Isolation

The module uses photocoupler isolation between the field I/O circuitry and the internal logic circuitry. The specified isolation voltage is 1250 V AC RMS.

This arrangement helps separate field-side electrical disturbances from the logic circuitry. However, the output channels themselves are non-isolated, so the specified common connections and field supply arrangement must be observed.

Expansion Assembly Communication

The 1790-0V16X does not communicate directly with the PLC as an independent DeviceNet node. Instead, it relies on a compatible CompactBlock LDX base block.

The base block receives network commands and transfers output information through the expansion ribbon cable. This allows the 16 additional output channels to become part of the existing distributed I/O assembly.


Role in the CompactBlock LDX Control Architecture

The Allen Bradley 1790-0V16X serves as a digital output expansion stage within the CompactBlock LDX architecture. Its function is to increase the number of available sinking output channels while using the base block for network communication.

A typical system arrangement follows this structure:

PLC Controller → DeviceNet Scanner → CompactBlock LDX Base Block → 1790-0V16X → DC Field Devices

System Component Function
Allen Bradley 1790-0V16X Provides 16 additional sinking digital output points
CompactBlock LDX Base Block Handles the main I/O assembly and DeviceNet communication
DeviceNet Scanner Exchanges I/O data between the PLC and distributed I/O
PLC Controller Executes machine logic and output commands
Expansion Ribbon Cable Transfers output data between the base block and expansion module
24 V DC Field Power Supply Supplies the connected output loads
Pneumatic Solenoid Valve Controls pneumatic actuators through electrical switching
Interface Relay Provides an intermediate switching interface
Indicator Lamp Displays machine status and operating conditions
Field Wiring Connects output channels and common terminals to external loads

In this arrangement, the base block acts as the communication interface between the controller and the expansion module. The 1790-0V16X handles the actual field output switching.

For example, a material-handling machine may use the expansion block to operate several pneumatic stops and sorting gates. The PLC receives product-position information from the input modules and activates the required outputs through the DeviceNet assembly.

Because the output channels use sinking circuitry, the field wiring must be arranged with the correct positive supply and common connections. This is particularly important when combining sourcing and sinking output devices within the same machine panel.


Industrial Applications

Application Typical Use
Conveyor Systems Operating pneumatic stops, diverters, and material transfer mechanisms
Packaging Machinery Switching solenoid valves and auxiliary machine-control devices
Automated Assembly Controlling pneumatic clamps and positioning actuators
Material Handling Operating sorting gates and product-routing mechanisms
Pneumatic Control Systems Switching compatible 24 V DC field devices
Production Lines Expanding local output capacity for distributed machine functions
Automated Sorting Equipment Controlling diverters and mechanical sorting actuators
Industrial Machine Panels Adding sinking output points to existing CompactBlock LDX assemblies
Process Equipment Switching compatible DC control loads and interface relays
Factory Automation Providing additional output channels in DeviceNet-based I/O installations

Installation and Maintenance

  1. Verify the Module Model: Confirm that Allen Bradley 1790-0V16X is the required 16-point DC sinking output expansion block.
  2. Check Base Block Compatibility: Ensure that the selected CompactBlock LDX base block supports the 1790-0V16X expansion module.
  3. Inspect the Module: Examine the housing, 37-pin connector, expansion interface, and mounting points for physical damage.
  4. Prepare the Mounting Location: Select a suitable DIN rail or panel mounting position with sufficient access for field wiring.
  5. Isolate the Power Supply: Disconnect the relevant field and control power sources before installation or wiring work.
  6. Mount the Expansion Block: Secure the module using the specified mounting arrangement and check its mechanical position.
  7. Connect the Ribbon Cable: Connect the expansion interface to the compatible base block and verify that the cable is correctly seated.
  8. Wire the Field Connector: Connect the external loads through the 37-pin D-shell interface according to the module’s terminal assignment.
  9. Verify Sinking Output Polarity: Connect the common terminals and positive field supply according to the specified sinking output wiring arrangement.
  10. Check Load Current: Ensure that each output remains below 0.5 A and that the current through each common connection does not exceed 4 A.
  11. Test Individual Outputs: Restore power and activate each channel through the controller to verify switching behavior and the corresponding green status indicator.
  12. Record the Wiring Configuration: Document the output assignments, common connections, connected loads, and field supply arrangements for future maintenance.

Compatible System Components

Component Function
Allen Bradley 1790-0V16X 16-point DC sinking output expansion block
CompactBlock LDX Digital I/O Base Block Provides the main DeviceNet-connected I/O assembly
Allen Bradley 1790-0B16X 16-point DC sourcing output expansion alternative
Allen Bradley 1790-16BV0X 16-point universal input expansion block
Allen Bradley 1790-8BV8VX Combined 8-input / 8-output expansion block
Allen Bradley 1790-7CMCBL CompactBlock LDX expansion ribbon cable
Allen Bradley 1790-15CMBL CompactBlock LDX expansion ribbon cable
DeviceNet Scanner Handles network communication with the base block
PLC Controller Executes machine logic and output commands
24 V DC Power Supply Supplies the field output circuits
37-Pin D-Shell Connector Provides the external field wiring interface
DC Solenoid Valve Operates pneumatic or hydraulic switching mechanisms
Interface Relay Provides an intermediate switching interface for external equipment

Recommended Related Models

Model Product Type Typical Application
Allen Bradley 1790-0B16X CompactBlock LDX 16-Point Digital Output Expansion Block 24 V DC sourcing output expansion
Allen Bradley 1790-16BV0X CompactBlock LDX 16-Point Universal Input Expansion Block Additional digital input capacity
Allen Bradley 1790-8BV8VX CompactBlock LDX 8-Input / 8-Output Expansion Block Combined universal input and sinking output expansion
Allen Bradley 1790-8BV8BX CompactBlock LDX 8-Input / 8-Output Expansion Block Combined universal input and sourcing output expansion
Allen Bradley 1790-0W8X CompactBlock LDX 8-Point Relay Output Expansion Block Relay-based output switching
Allen Bradley 1790D-0V16 CompactBlock LDX 16-Point Digital Output Base Block Standalone DeviceNet base block with sinking outputs

Key Advantages

  • Adds 16 sinking digital output points to a compatible CompactBlock LDX assembly.
  • Supports nominal 24 V DC field operation.
  • Handles up to 0.5 A per output and 4 A per common.
  • Provides a 37-pin D-shell field wiring interface.
  • Includes photocoupler isolation between field I/O and logic circuits.
  • Uses individual green indicators for output status monitoring.
  • Supports fast output switching for machine-control sequences.
  • Extends existing distributed I/O capacity without requiring an independent DeviceNet connection.

Technical FAQs

What is the difference between the Allen Bradley 1790-0V16X and 1790-0B16X?

The main difference is the output switching configuration. The 1790-0V16X has 16 DC sinking outputs, while the 1790-0B16X has 16 DC sourcing outputs. The sinking version switches the load toward DC common, whereas the sourcing version supplies positive voltage to the load. The correct selection depends on the field device wiring and electrical interface.

How should the 1790-0V16X sinking outputs be wired?

For the specified sinking arrangement, the COM0 and COM2 connections are wired to the positive 24 V DC field supply, while COM1 and COM3 are connected to field power negative (GND). The load is connected between the positive supply and its corresponding output channel. Correct common-terminal wiring is essential for normal operation.

What is the maximum current supported by the output channels?

Each output supports up to 0.5 A, with a maximum of 4 A per common. Both ratings must be observed when connecting multiple loads. The total current of simultaneously energized devices should be calculated before assigning the output channels.

Can the 1790-0V16X connect directly to a DeviceNet network?

No. It is an expansion block rather than an independent DeviceNet communication module. It connects to a compatible CompactBlock LDX base block through the expansion ribbon cable. The base block provides the DeviceNet connection and transfers the output commands to the expansion module.



Related Products

Get the latest price? We will reply as soon as possible (within 12 hours)

No:77501