Troubleshooting the Allen-Bradley 1336-SN-SP6A Inverter Snubber PCB

2026-11-25 

The Allen-Bradley 1336-SN-SP6A inverter snubber PCB is part of the power-stage protection arrangement in specified 1336STEF variable frequency drives. When a drive develops inverter-related faults, visible PCB damage, abnormal operation, or repeated power-stage failures, the snubber circuit should be included in the investigation. However, a drive fault alone does not establish that the 1336-SN-SP6A has failed.

Effective troubleshooting requires technicians to separate symptoms caused by the snubber assembly from faults originating in the inverter switching devices, gate-drive circuitry, DC bus, motor cable, motor insulation, or operating conditions. This guide presents a structured diagnostic approach for maintenance personnel working with compatible 1336 drive configurations.

Quick Navigation for 1336-SN-SP6A Fault Diagnosis

  1. Snubber PCB function and failure symptoms
  2. Safety and diagnostic preparation
  3. Common symptoms and possible causes
  4. Visual inspection and electrical checks
  5. Step-by-step troubleshooting workflow
  6. Repair and replacement decisions
  7. Illustrative engineering scenario
  8. Technical troubleshooting FAQs

Understanding the 1336-SN-SP6A Inverter Snubber PCB in Fault Diagnosis

The inverter section of a variable frequency drive switches DC bus energy to produce a variable-frequency output for the motor. These switching events can generate transient voltage stress due to the behavior of the power devices and the parasitic characteristics of the circuit. The snubber network helps manage these electrical transients within the design limits of the inverter assembly.

The 1336-SN-SP6A is identified as an inverter snubber PCB for specified 1336STEF configurations. The applicable spare-parts listing specifies three boards for the relevant assembly. It is important to distinguish this inverter-side component from converter snubber boards, pre-charge boards, and other power-stage circuit boards.

A defective snubber PCB may contribute to abnormal inverter operation or damage to related power components. Nevertheless, technicians should avoid replacing the board solely because an inverter fault appears on the drive display. A fault code identifies a detected operating condition; it does not always identify the failed component.

Electrical Safety Before Troubleshooting the Allen-Bradley 1336-SN-SP6A

Inspection inside a 1336 drive must be performed by qualified personnel. The drive contains hazardous voltage and capacitors that may retain energy after the incoming supply has been disconnected.

  • Stop the machine and follow the approved shutdown procedure.
  • Disconnect and lock out incoming power and relevant auxiliary supplies.
  • Wait for the DC bus discharge period specified in the exact drive manual.
  • Verify the DC bus condition at the designated test points using a properly rated meter.
  • Apply appropriate PPE, ESD precautions, and site electrical safety procedures.
  • Do not remove or reconnect PCB assemblies while the drive is energized.

A blank display, extinguished indicator, or stopped motor is not proof that the internal DC bus is safe. Never bypass the manufacturer’s discharge and verification procedure.

Common 1336-SN-SP6A Fault Symptoms and Possible Causes

The following table links common observations to areas that should be investigated. These are diagnostic possibilities rather than confirmed failure characteristics unique to the 1336-SN-SP6A.

Observed symptom Possible causes Recommended investigation
Visible damage on a snubber PCB Electrical overstress, component aging, contamination, or a secondary power-stage fault Inspect the board and investigate associated inverter components
Repeated inverter-related faults Power-device damage, gate-drive problems, wiring faults, or abnormal motor conditions Review fault history and inspect the complete inverter circuit
Drive trips during acceleration Excessive load, motor-circuit problems, incorrect application settings, or power-stage damage Compare operating conditions and check the motor and drive configuration
Faults after PCB replacement Incorrect part, wrong board position, loose connection, or an unresolved underlying fault Verify the catalog number, installation arrangement, and surrounding components
Repeated damage to replacement boards Uncorrected electrical stress, defective switching devices, or an incompatible replacement Stop repeated replacement and perform a complete power-stage investigation
Abnormal heating or discoloration Loose connections, damaged components, contamination, or inadequate cooling Inspect the assembly, terminals, enclosure, and cooling system

Visual Inspection and Electrical Checks for the 1336-SN-SP6A

Begin with the available drive fault history and maintenance records. Record when the problem occurs, whether it appears during startup or under load, and whether any recent electrical or mechanical changes were made. This information helps narrow the investigation before the enclosure is opened.

PCB visual inspection

After the drive has been safely isolated and the DC bus verified safe, inspect the snubber PCB assembly for:

  • Burn marks, darkened areas, or localized discoloration.
  • Cracked or damaged components.
  • Damaged PCB tracks or lifted copper areas.
  • Loose, bent, or contaminated connectors.
  • Corrosion, moisture residue, or conductive dust.
  • Evidence of arcing or carbon tracking around the mounting area.

Visible damage is useful evidence, but an apparently clean PCB is not necessarily electrically healthy. Some component failures may not produce obvious external signs.

Check the inverter power section

Inspect the associated inverter power devices and their connections for evidence of short circuits, overheating, or physical damage. A failed switching device can impose abnormal electrical stress on related circuits. Replacing the snubber PCB without addressing such a fault may lead to repeated failure.

Review the DC bus and supply conditions

Review recorded supply conditions and drive diagnostics for abnormal voltage events or repeated DC bus-related faults. Any live measurements must follow the manufacturer’s approved procedure and be performed by personnel qualified for energized power-electronic equipment. Do not improvise test points or probing methods.

Inspect the motor and output circuit

  • Check motor cable insulation and terminal condition.
  • Look for damaged cable glands, loose terminations, or grounding problems.
  • Review motor insulation test results where appropriate and only with the motor safely disconnected from the drive.
  • Check whether the mechanical load is binding or operating outside its normal range.
  • Review acceleration and deceleration settings against the application requirements.

Step-by-Step Troubleshooting Workflow for 1336-SN-SP6A Faults

Step 1: Capture the fault information

Before resetting the drive, record the displayed fault code, operating frequency, load condition, and the event that occurred immediately before the trip. If the drive provides a fault history, preserve it for comparison.

A useful maintenance record may contain the following fields:

Drive catalog number:
Drive serial number:
Installed snubber PCB:
Fault code:
Operating condition:
Motor current:
DC bus diagnostic information:
Recent maintenance:
Visible damage:

Use the drive’s own diagnostic definitions when interpreting fault codes. Do not assume that a code from another 1336 model or firmware revision has exactly the same diagnostic meaning.

Step 2: Confirm the installed part number

Verify that the installed board is 1336-SN-SP6A and that the drive’s voltage class, horsepower rating, frame, and power-stage arrangement match the applicable parts documentation. The 1336 family contains multiple snubber PCB variants. A board that physically fits may still be electrically incorrect.

Step 3: Check for obvious physical damage

Inspect the PCB, connectors, mounting points, nearby power devices, and wiring. Record any burn marks, cracked components, loose connections, or carbon tracking. If the board is visibly damaged, investigate the cause before installing a replacement.

Step 4: Evaluate related inverter components

Check the inverter switching devices and associated gate-drive circuitry using the test procedures specified for the exact drive model. A shorted or otherwise defective power device can create conditions that damage the snubber circuit. Do not use an improvised resistance or diode-test interpretation as a substitute for the manufacturer’s service procedure.

Step 5: Examine the motor circuit and application

Review motor insulation condition, cable routing, grounding, load behavior, and acceleration or deceleration demands. If the drive trips only under a particular load condition, compare the event with the machine’s normal operating profile. A mechanical overload or motor-circuit fault may be the primary issue rather than the snubber PCB.

Step 6: Decide whether replacement is justified

Replace the 1336-SN-SP6A only when inspection and testing indicate that the board is defective, or when the approved maintenance procedure requires replacement. Confirm the correct kit quantity and exact board arrangement for the drive. The applicable spare-parts listing identifies three boards for the specified assembly.

Step 7: Verify the repair under controlled conditions

After replacement, complete the mechanical inspection, restore protective covers, and follow the approved startup procedure. Monitor the drive during a controlled operating test. If the same fault returns, stop the test and continue diagnosis rather than repeatedly resetting the drive.

Repair or Replacement Decisions for the Allen-Bradley 1336-SN-SP6A

The appropriate repair depends on the condition of the PCB and the availability of reliable replacement parts. Snubber boards are part of a designed power-electronic circuit. Component-level repair should only be attempted by personnel with the required technical capability, circuit information, and suitable test equipment.

When replacement is generally appropriate

  • The PCB has visible electrical or physical damage.
  • Testing identifies a failed component or damaged circuit path.
  • The board has suffered contamination or corrosion that cannot be reliably corrected.
  • The manufacturer’s service procedure specifies replacement of the board or complete set.

When the root cause must be investigated first

  • A replacement PCB has failed shortly after installation.
  • Multiple inverter components show signs of damage.
  • Drive faults recur under the same operating conditions.
  • The installed board’s compatibility is uncertain.
  • There is evidence of abnormal supply, motor, or grounding conditions.

Rockwell Automation lists the 1336-SN-SP6A as discontinued, with a discontinuation date of March 31, 2022. The product listing does not specify a direct replacement category. Therefore, any proposed alternative must be checked against the exact drive documentation and approved parts information. Do not substitute another snubber PCB based on appearance or a similar catalog number.

Illustrative Engineering Scenario: Repeated Inverter Faults After Snubber PCB Replacement

The following is a hypothetical diagnostic example. It is intended to illustrate a troubleshooting method and does not describe a documented customer repair.

A maintenance team replaces a visibly damaged inverter snubber board in a 1336 drive. During the next controlled startup, the drive reports another inverter-related fault. A second board replacement is considered, but the maintenance team pauses the work and reviews the complete power-stage assembly.

The investigation proceeds as follows:

  1. Review the fault record: The team confirms that the fault occurs during the same operating stage as before the repair.
  2. Verify the replacement: The installed catalog number and board arrangement are checked against the drive parts documentation.
  3. Inspect adjacent components: The team finds evidence requiring further evaluation of the inverter power devices.
  4. Check the motor circuit: Cable condition, motor connections, and grounding are reviewed.
  5. Determine the root cause: The power-stage investigation is completed before another snubber board is installed.

The key lesson is that a failed snubber PCB may be a consequence of another electrical problem. Replacing the visible damaged component without identifying the initiating fault can result in repeated downtime and additional component damage.

Technical FAQs About 1336-SN-SP6A Troubleshooting

What does the 1336-SN-SP6A inverter snubber PCB do?

It forms part of the inverter-side snubber arrangement, which helps manage transient electrical stress associated with switching in the drive power stage.

Does an inverter fault always mean the snubber PCB is defective?

No. Inverter faults can also result from power-device damage, gate-drive problems, DC bus abnormalities, motor cable faults, grounding issues, or abnormal load conditions.

How many boards are included in the 1336-SN-SP6A spare-parts configuration?

The applicable spare-parts listing specifies three boards. Confirm the required quantity against the exact drive configuration and parts diagram.

Can a damaged snubber PCB cause repeated drive trips?

A defective snubber circuit may contribute to abnormal inverter operation. However, repeated trips should trigger a broader inspection of the inverter power stage and connected motor circuit.

What visual signs indicate possible PCB damage?

Burn marks, cracked components, damaged circuit tracks, corrosion, carbon tracking, and damaged connectors are common reasons for further investigation.

Should the drive be energized to inspect the snubber PCB?

No. Physical inspection and board replacement require the drive to be isolated, locked out, and verified safe according to the applicable manual. Energized diagnostics require a separate approved procedure and qualified personnel.

Can the 1336-SN-SP6A be repaired at component level?

That depends on the failure and the available technical documentation. Component-level repair should not be attempted without suitable expertise, circuit information, and verification procedures. Replacement may be the more reliable maintenance option.

Why might a replacement snubber PCB fail again?

Possible reasons include an unresolved inverter power-device fault, an incorrect replacement board, a connection error, abnormal electrical conditions, or an unsuitable operating environment.

Is the 1336-SN-SP6A discontinued?

Yes. Rockwell Automation lists this catalog number as discontinued, effective March 31, 2022. Confirm the condition and authenticity of any available replacement stock.

What should be done if the same fault returns after replacement?

Stop repeated reset attempts. Review the fault history, verify the installed board and connections, and investigate the inverter switching devices, gate-drive circuitry, DC bus, motor cable, and load conditions.

Conclusion: Accurate Fault Diagnosis for the 1336-SN-SP6A Inverter Snubber PCB

Troubleshooting the Allen-Bradley 1336-SN-SP6A requires a systematic assessment of the entire inverter power stage. Visible PCB damage is an important finding, but it should be treated as one part of the diagnostic evidence rather than automatic proof of the original fault.

Maintenance personnel should confirm the exact drive configuration, preserve fault records, inspect related power components, and verify the motor circuit before deciding on replacement. Since the 1336-SN-SP6A is discontinued and no direct replacement category is specified in the product listing, compatibility checks are especially important when maintaining legacy 1336 equipment.