The Siemens 6AG1314-6CH04-2AY0 SIPLUS S7-300 CPU 314C-2 DP is a compact programmable logic controller designed for industrial automation applications that require integrated digital and analog signal processing, communication capabilities, and enhanced environmental protection.
Belonging to the Siemens SIPLUS S7-300 product family, this CPU is based on the standard SIMATIC S7-300 CPU 314C-2 DP hardware platform, with additional protection for demanding operating environments. Its conformal coating and specified temperature range make it particularly relevant to applications where environmental conditions may be more challenging than those found in conventional control cabinets.
The module combines a central processing unit with integrated input and output functions. It provides 24 digital inputs, 16 digital outputs, four analog inputs, two analog outputs, and one Pt100 temperature-measurement channel. Four integrated high-speed counters support counting tasks at frequencies of up to 60 kHz.
For communication, the CPU includes an MPI interface and an integrated PROFIBUS DP interface. These interfaces allow it to exchange data with compatible programming devices, operator interfaces, distributed I/O stations, and other automation equipment.
The 6AG1314-6CH04-2AY0 provides 192 KB of integrated work memory and an integrated 24 V DC power supply. A Siemens Micro Memory Card is required for load-memory storage and program operation. The appropriate front connectors and system accessories must also be selected according to the installation requirements.
This model is based on the 6ES7314-6CH04-0AB0 CPU 314C-2 DP, but its SIPLUS configuration is designed for a different environmental operating profile. When replacing an existing controller, engineers should distinguish between the SIPLUS and standard versions rather than selecting a CPU solely because the base model number appears similar.
| Parameter | Specification |
|---|---|
| Brand | Siemens |
| Product Series | SIPLUS S7-300 |
| Model | 6AG1314-6CH04-2AY0 |
| CPU Designation | CPU 314C-2 DP |
| Product Type | Compact CPU / PLC Central Processing Unit |
| Base Model | 6ES7314-6CH04-0AB0 |
| Conformal Coating | Included |
| Environmental Standard | EN 50155 |
| Operating Temperature | -25°C to +60°C |
| Integrated Work Memory | 192 KB |
| Digital Inputs | 24 |
| Digital Outputs | 16 |
| Analog Inputs | 4 voltage/current channels plus 1 resistance/Pt100 channel |
| Analog Outputs | 2 |
| Pt100 Measurement | 1 channel |
| High-Speed Counters | 4 |
| Maximum Counter Frequency | 60 kHz |
| Communication Interfaces | MPI and PROFIBUS DP |
| Integrated Power Supply | 24 V DC |
| Required Memory Card | Siemens Micro Memory Card |
| Front Connector | 2 × 40-pole |
| Dimensions Provided | 120 × 125 × 130 mm |
| Weight Provided | 0.739 kg |
| Application | Industrial automation and railway-related control systems |
Note: The analog input configuration includes four voltage/current measurement channels and one resistance/resistance-temperature measurement channel. The exact channel configuration and measurement ranges should be checked in the hardware documentation before wiring.
The 6AG1314-6CH04-2AY0 operates as the central processing unit of a SIMATIC S7-300 automation system. It executes the control program, processes signals from connected field devices, and coordinates outputs according to the programmed control sequence.
Its integrated I/O reduces the need for separate modules in applications where the onboard channel count is sufficient.
The CPU executes the user program and processes the control logic required by the machine or production process.
During operation, it reads input signals, evaluates program instructions, updates output states, and manages communication with connected automation devices. This process allows the controller to coordinate sensors, actuators, motors, valves, and other equipment.
The integrated 192 KB work memory provides space for program execution and associated working data. A Micro Memory Card is required for load-memory storage, so the card must be included in the system design and configured appropriately.
The CPU provides 24 digital inputs and 16 digital outputs for discrete control tasks.
Digital inputs can receive signals from devices such as:
The 16 digital outputs can be used to control compatible loads and interface circuits, including indicator lamps, relay interfaces, and selected actuator-control devices.
The input and output circuits must be wired according to their electrical specifications. In particular, output load capacity and protection requirements should be checked before connecting field equipment directly.
The integrated analog channels allow the CPU to acquire and generate continuous process signals.
The four voltage/current analog input channels can be used with compatible transmitters and measurement devices. Typical applications include pressure, flow, level, and other process variables.
The analog output channels can provide control references to compatible devices, such as valve positioners or other equipment that accepts analog commands.
Correct signal type, wiring, scaling, grounding, and channel configuration are essential for reliable measurement and control.
The CPU includes one resistance-temperature measurement channel for Pt100 sensors.
A Pt100 sensor changes its electrical resistance according to temperature. The controller can use this signal to monitor temperature in machinery, equipment housings, or industrial processes.
This integrated function can reduce the need for a separate temperature input module in suitable applications. Sensor wiring and measurement configuration must follow the specified connection method.
Four integrated high-speed counters support counting applications with frequencies up to 60 kHz.
These counters are useful when the controller needs to process pulse signals faster than ordinary cyclic program processing would conveniently allow.
Possible applications include:
The maximum supported frequency depends on the counter configuration and applicable signal conditions.
The CPU includes MPI and PROFIBUS DP interfaces.
MPI supports communication with compatible Siemens programming and operator-interface equipment. PROFIBUS DP provides a fieldbus connection for compatible distributed I/O stations, drives, and other automation devices.
These interfaces allow the CPU to exchange process data with equipment distributed throughout a machine or control system.
The 6AG1314-6CH04-2AY0 can serve as the main controller in a compact automation system or as part of a larger SIMATIC S7-300 installation.
Its integrated I/O and communication interfaces allow it to coordinate multiple control functions without requiring a separate module for every signal type.
The CPU can execute logic for machine sequences, interlocks, operating modes, and automatic production cycles.
For example, a packaging machine may use digital inputs to detect product position, analog inputs to monitor process conditions, and digital outputs to operate pneumatic valves or relay interfaces.
The CPU processes these signals according to the programmed sequence and coordinates the connected equipment.
The integrated PROFIBUS DP interface allows the CPU to communicate with compatible distributed I/O stations.
This is useful when sensors and actuators are located at different positions around a machine or production line. Instead of routing every field signal directly to the main control cabinet, distributed I/O can collect local signals and exchange data with the CPU through the fieldbus.
The selected remote I/O equipment, bus connectors, cable, and configuration must be compatible with the installed system.
A compatible Siemens HMI can provide operators with access to machine status, alarms, process values, and control commands.
The HMI can communicate through an appropriate supported interface, allowing operators to monitor the production process without accessing the PLC program directly.
The integrated analog channels and Pt100 input support applications involving continuous process measurements.
The controller can acquire temperature and other process values, compare them with configured limits, and execute control actions according to the application logic.
The SIPLUS configuration is designed for an environmental profile associated with EN 50155 railway applications. Its conformal coating and specified operating temperature range make it relevant to selected railway-related automation installations.
The exact suitability for a railway project must still be evaluated against the applicable equipment category, installation location, temperature class, vibration requirements, and project-specific approval conditions.
The 6AG1314-6CH04-2AY0 is particularly relevant to automation systems where environmental protection and railway-related operating requirements are important.
Potential applications include selected onboard auxiliary control functions, monitoring systems, and equipment-control installations.
Project engineers should verify the complete EN 50155 requirements and the applicable environmental classification before using the CPU in a railway installation.
The CPU can manage compact industrial machines that require a combination of discrete control, analog measurement, and fieldbus communication.
Examples include assembly equipment, production machines, material-handling systems, and automated workstations.
Its integrated I/O can support applications where the number of required signals falls within the available onboard capacity.
The integrated Pt100 channel allows direct temperature-measurement functions within a suitable control configuration.
It can be used to monitor selected machine or process temperatures and provide information for alarms, operating interlocks, and process sequences.
The CPU can coordinate sensors, actuators, and distributed I/O equipment across a production line.
Digital signals can be used for product detection and machine sequencing, while analog channels can acquire process values from compatible instruments.
PROFIBUS DP communication allows the controller to exchange data with suitable field devices and remote I/O stations.
In suitable systems, the CPU can manage pump start/stop sequences, operating interlocks, alarm conditions, and analog process measurements.
It may also communicate with compatible drive equipment through the supported control architecture.
The actual motor-control method depends on the connected drive and the system’s communication and wiring design.
The conformal-coated SIPLUS design may be considered for selected installations where environmental conditions require additional protection for electronic components.
However, conformal coating does not make the CPU waterproof or suitable for unrestricted exposure to condensation, corrosive chemicals, or direct contamination.
The controller must still be installed within an enclosure and environment that meet the manufacturer’s requirements.
Correct installation is essential for reliable PLC operation and long-term system stability.
The CPU has an integrated 24 V DC power supply arrangement. The specified supply voltage is 24 V DC, with a permitted operating range of 19.2 V to 28.8 V DC.
For this EN 50155 configuration, the power supply must meet the applicable railway-related requirements. Siemens specifies the use of a power supply according to EN 50155.
The supply circuit should be protected using appropriately selected protective devices. The power supply, grounding, and wiring arrangement must follow the relevant installation documentation.
The supplied dimensions are 120 × 125 × 130 mm, with a listed weight of 0.739 kg.
Before panel design, verify the dimensions and mounting arrangement against the product drawing. Provide adequate access for front connectors, memory-card installation, wiring, and maintenance.
The CPU should be installed in a suitable control cabinet with appropriate environmental protection and ventilation.
Digital inputs and outputs must be connected according to the specified electrical characteristics.
For analog channels, confirm whether the connected instrument uses voltage, current, resistance, or Pt100 measurement. Configure each channel for the correct signal type and range.
Use appropriate cable shielding and grounding practices, particularly for low-level analog signals and installations containing electrically noisy equipment.
When connecting remote I/O or other PROFIBUS DP devices, verify the bus address, transmission rate, cable type, connector arrangement, and termination settings.
The network configuration should match the installed hardware and the project configuration in the engineering software.
Incorrect bus addresses, termination, or cabling can cause communication errors and prevent connected devices from exchanging data reliably.
A Siemens Micro Memory Card is required for this CPU. The memory card must be compatible with the controller and contain the appropriate load-memory data.
The CPU uses two 40-pole front connectors for its integrated I/O connections. Select the correct connector accessories and verify the terminal assignment before wiring.
The CPU is configured using compatible Siemens STEP 7 engineering software and the applicable hardware support package.
Before commissioning, verify the CPU order number, hardware configuration, firmware requirements, I/O addresses, communication parameters, and memory-card contents.
After downloading the program, test all digital and analog signals, high-speed counter functions, communication links, and safety-related interlocks as required by the application.
The 6AG1314-6CH04-2AY0 is designed for use within a compatible SIMATIC S7-300 automation architecture.
| Component | Function | Integration Considerations |
|---|---|---|
| Siemens Micro Memory Card | Provides required load-memory storage | Confirm card compatibility and program requirements |
| Siemens S7-300 signal modules | Expand digital and analog I/O | Check rack configuration and module compatibility |
| PROFIBUS DP remote I/O | Collects distributed field signals | Verify bus address, configuration, and communication settings |
| Siemens HMI | Provides operator monitoring and control | Confirm the supported communication interface |
| 24 V DC power supply | Supplies the CPU and related control circuits | Use a supply suitable for the required EN 50155 conditions |
| PROFIBUS DP cable | Connects distributed field devices | Use suitable cable and termination components |
| PROFIBUS connectors | Provide network connections | Check connector type and termination arrangement |
| Digital sensors | Provide discrete field signals | Verify voltage, polarity, and input characteristics |
| Analog transmitters | Provide continuous measurement signals | Match voltage/current ranges and channel configuration |
| Pt100 temperature sensor | Provides resistance-based temperature measurement | Confirm sensor wiring and measurement configuration |
| DIN rail and mounting accessories | Support cabinet installation | Verify mechanical compatibility and available space |
The components listed above are typical examples for a complete installation. They are not necessarily included with the CPU.
The 6AG1314-6CH04-2AY0 is based on the standard 6ES7314-6CH04-0AB0 CPU 314C-2 DP platform. However, the SIPLUS version has additional environmental characteristics that should be considered when selecting a replacement.
| Model | Description | Replacement Considerations |
|---|---|---|
| 6ES7314-6CH04-0AB0 | SIMATIC S7-300 CPU 314C-2 DP | Base hardware relationship, but environmental protection and operating conditions differ |
| 6AG1314-6CH04-7AB0 | SIPLUS S7-300 CPU 314C-2 DP | Related SIPLUS configuration; compare environmental and ordering specifications |
| 6AG1314-6EH04-7AB0 | SIPLUS S7-300 CPU 314C-2 PN/DP | Different communication configuration; not a direct substitute without system review |
| 6ES7314-6EH04-0AB0 | SIMATIC S7-300 CPU 314C-2 PN/DP | Includes a different communication architecture and requires compatibility assessment |
Before replacing the CPU, compare:
A standard CPU with a similar base designation should not automatically be considered equivalent to the SIPLUS version. The environmental requirements of the installation must be preserved.
The conformal-coated SIPLUS configuration provides additional protection for electronic assemblies compared with an ordinary uncoated configuration.
The CPU is specified for EN 50155-related applications and an operating temperature range of -25°C to +60°C, subject to the applicable installation conditions and temperature classification.
The combination of digital inputs, digital outputs, analog channels, and Pt100 measurement supports a range of machine and process-control functions.
Four integrated high-speed counters support pulse-processing applications with frequencies up to 60 kHz.
The integrated interfaces allow the CPU to communicate with compatible Siemens programming devices, operator interfaces, and distributed automation equipment.
The integrated I/O and processing functions help reduce the number of separate modules required in suitable control applications.
The CPU belongs to the widely used S7-300 architecture, which is relevant to maintenance, spare-parts sourcing, and legacy industrial automation projects.
It is a SIPLUS S7-300 CPU 314C-2 DP compact programmable logic controller. It is based on the 6ES7314-6CH04-0AB0 hardware platform and includes conformal coating for enhanced environmental protection.
The 6AG1314-6CH04-2AY0 is the SIPLUS version with conformal coating and an EN 50155-related environmental specification. The 6ES7314-6CH04-0AB0 is the corresponding standard SIMATIC S7-300 CPU. Their environmental characteristics and application suitability are not identical.
It provides 192 KB of integrated work memory. A compatible Siemens Micro Memory Card is required for load-memory storage.
The CPU provides 24 digital inputs and 16 digital outputs. These integrated channels can handle discrete signals from compatible field devices.
Yes. It provides four voltage/current analog input channels, two analog outputs, and one resistance/Pt100 measurement channel.
The CPU has four integrated high-speed counters, supporting counting frequencies up to 60 kHz under the specified operating conditions.
The CPU includes an MPI interface and an integrated PROFIBUS DP interface. It should not be confused with the related PN/DP CPU versions, which have a different communication configuration.
The CPU uses a 24 V DC supply arrangement. The specified permitted input range is 19.2 V to 28.8 V DC. For this SIPLUS EN 50155 configuration, the power supply must meet the relevant railway-related requirements.
Yes. A Siemens Micro Memory Card is required for load-memory storage and program operation. The correct card and program configuration should be confirmed before commissioning.
Verify the complete order number, environmental specification, I/O configuration, communication interfaces, memory-card requirements, power supply, hardware version, and physical condition. For railway installations, also confirm that the replacement meets the project’s applicable environmental and approval requirements.
When purchasing the Siemens 6AG1314-6CH04-2AY0, confirm the complete order number and distinguish it from the standard 6ES7314-6CH04-0AB0 and other SIPLUS CPU variants.
For replacement projects, check whether the existing installation depends on the conformal coating, temperature range, or EN 50155-related requirements. A standard S7-300 CPU may share a similar hardware platform but may not provide the same environmental characteristics.
For used or surplus equipment, request clear photographs of the nameplate, front connectors, housing, and interface areas. Confirm whether a Micro Memory Card and front connectors are included, since these accessories may be supplied separately.
During maintenance, inspect the control cabinet for dust, moisture, loose wiring, and signs of corrosion. Check power supply stability, terminal connections, PROFIBUS communication status, and the condition of connected I/O devices.
Back up the PLC program and configuration data before making changes. Keep records of the CPU order number, firmware, memory-card contents, and engineering-software version to simplify future maintenance.
The Siemens 6AG1314-6CH04-2AY0 SIPLUS S7-300 CPU 314C-2 DP is a compact PLC designed for industrial automation applications that require integrated digital and analog I/O, high-speed counting, MPI and PROFIBUS DP communication, and enhanced environmental protection.
With 192 KB of work memory, 24 digital inputs, 16 digital outputs, analog signal channels, one Pt100 measurement channel, and four high-speed counters, it combines several control functions in a single CPU.
Its conformal coating and EN 50155-related specification distinguish it from the standard S7-300 CPU configuration. For industrial maintenance and replacement projects, checking the exact order number, environmental requirements, memory-card configuration, and communication compatibility is essential for reliable system operation.