Our advantage
Global Logistics
We have a 10-year logistics and express cooperation agreement, so our products can be shipped to any place in the world.
Brand new and original
Our products are imported in bulk from the place of origin. Because of the cooperative relationship, our products are all original and 100% new.
24-hour service
We provide 7*24 hours service to our customers. We will be there whenever you need us.
Price advantage
All our products are priced very favorably because we have our own warehouse and supply.
| Company Information | |||
| [email protected] | |||
| Mobile | +8615980777398 | ||
| +8615980777398 | |||
| 15980777398 |

The Schneider TSXDSY08R5 is an eight-channel relay output module belonging to the Modicon Premium automation platform. It provides relay-based switching between PLC control logic and external electrical loads, allowing a Premium controller to operate equipment supplied by either AC or DC circuits.
Unlike transistor output modules, which are generally used for electronic switching, the TSXDSY08R5 uses mechanical relay contacts. Each of its eight outputs has one normally open (NO) contact. This makes the module suitable for applications involving contactor coils, solenoid valves, auxiliary relays, and other electrical devices that require isolated switching contacts.
A typical application is an industrial pumping station. The PLC can use individual relay outputs to operate pump contactors, control auxiliary ventilation, switch lubrication equipment, and activate alarm circuits. Each output follows the corresponding control command from the PLC, allowing several electrical loads to be managed through one module.
The module supports nominal output voltages of 12–24 V DC and 24–240 V AC, with corresponding operating limits of 10–34 V DC and 20–264 V AC. Its conventional free-air thermal current is 3 A. These characteristics make it suitable for switching a range of industrial control loads, provided the actual load current and switching category remain within the specified electrical ratings.
The TSXDSY08R5 uses a screw terminal block for field connections and occupies a standard module position in a Modicon Premium rack. External fast-acting fuses are required for output overload and short-circuit protection. When switching inductive loads, appropriate suppression components must also be installed to control voltage spikes generated when relay contacts open.
For maintenance and replacement work, particular attention should be paid to the output contact arrangement, external fuse protection, operating voltage, and load characteristics. The TSXDSY08R5 should also be distinguished from the TSXDSY08R5A, which has a different relay protection arrangement and electrical ratings.
| Parameter | Specification |
|---|---|
| Manufacturer | Schneider Electric |
| Model | TSXDSY08R5 |
| Product Family | Modicon Premium |
| Product Type | Discrete Output Module |
| Number of Discrete Outputs | 8 |
| Discrete Output Type | Relay, Not Protected |
| Contact Type | 1 NO per Output |
| Nominal DC Output Voltage | 12–24 V DC |
| DC Output Voltage Limits | 10–34 V DC |
| Nominal AC Output Voltage | 24–240 V AC |
| AC Output Voltage Limits | 20–264 V AC |
| Conventional Free-Air Thermal Current | 3 A |
| Activation Response Time | < 8 ms |
| Deactivation Response Time | < 10 ms |
| AC Inductive Load Protection | RC Circuit and MOV on Each Preactuator |
| DC Inductive Load Protection | Discharge Diode on Each Preactuator |
| Overload Protection | External Fast-Acting Fuse per Channel or Group of Channels |
| Short-Circuit Protection | External Fast-Acting Fuse per Channel or Group of Channels |
| Insulation Resistance | > 10 MΩ at 500 V |
| Power Dissipation | 0.25 W + 0.2 W × Number of Outputs in State 1 |
| Electrical Connection | Screw Terminal Block |
| Current Consumption | 70 mA at 24 V DC Rack / 55 mA at 5 V DC |
| Module Format | Standard |
| Dimensions | 55 × 180 × 260 mm |
| Weight | 0.554 kg |
The TSXDSY08R5 receives discrete output commands from the Modicon Premium PLC and uses its internal relay contacts to switch external electrical circuits.
Its operating sequence can be represented as:
PLC Logic → Modicon Premium Rack → TSXDSY08R5 → Relay Contacts → External Electrical Load
When the PLC program activates an output channel, the corresponding relay operates and closes its normally open contact. Current can then flow through the external circuit, energizing the connected device.
When the PLC removes the output command, the relay returns to its normal state and the contact opens, interrupting the external circuit.
For example, consider a machine with several motor-driven sections. The PLC can assign individual outputs to motor contactor coils, allowing each section to be started or stopped according to the production sequence. Other channels can operate solenoid valves or auxiliary equipment.
The module supports AC and DC switching circuits, but the appropriate external protection depends on the connected load.
When switching an AC inductive load, such as a contactor coil, an RC suppression circuit and MOV are used to limit switching overvoltage. For DC inductive loads, a discharge diode is installed across the preactuator to suppress the voltage generated when the circuit is interrupted.
An important distinction is that the TSXDSY08R5 is a relay output module without built-in output overload and short-circuit protection. External fast-acting fuses must therefore be installed for each channel or an appropriate group of channels.
The module’s response time is below 8 ms during activation and below 10 ms during deactivation. These switching characteristics should be considered when coordinating output commands with machine sequences and external contactors.
Within a Modicon Premium control system, the TSXDSY08R5 provides the electrical switching interface between PLC logic and external equipment.
The CPU executes the control program and updates the output states through the rack backplane. The TSXDSY08R5 responds to these commands by operating its eight relay contacts.
A typical arrangement is:
Field Inputs → Modicon Premium CPU → Rack Backplane → TSXDSY08R5 → Contactors / Valves / Auxiliary Loads
| System Element | Function |
|---|---|
| TSXDSY08R5 | Switches eight external electrical circuits through relay contacts |
| Modicon Premium CPU | Executes machine logic and determines output states |
| Premium Rack | Houses the controller and I/O modules |
| Rack Backplane | Transfers control information between the CPU and installed modules |
| Power Supply Module | Supplies the required power to the Premium rack |
| Digital Input Module | Collects feedback from limit switches and other discrete sensors |
| Contactor | Switches motor power circuits according to relay output commands |
| Solenoid Valve | Controls pneumatic or hydraulic circuit operation |
| Auxiliary Relay | Provides additional switching contacts for external circuits |
| Fast-Acting Fuse | Protects output wiring and circuits against excessive current |
| RC Suppressor / MOV | Limits switching overvoltage on AC inductive loads |
| Discharge Diode | Suppresses voltage spikes from DC inductive loads |
In a production machine, the CPU may monitor safety interlocks, limit switches, and operating conditions before activating a corresponding relay output. The TSXDSY08R5 then switches the external control circuit.
For example, one channel may energize a contactor coil, another may operate a lubrication solenoid, and a third may activate an alarm relay. This arrangement keeps the PLC’s control logic separate from the electrical loads being switched.
| Application | Typical Use |
|---|---|
| Industrial Pumping Stations | Switching pump contactors and auxiliary equipment |
| Manufacturing Machinery | Operating contactors, solenoid valves, and machine auxiliaries |
| Material Handling Systems | Controlling conveyor contactors and switching devices |
| Packaging Equipment | Activating pneumatic valves and electrical actuators |
| HVAC Systems | Switching fans, auxiliary relays, and control circuits |
| Water Treatment Plants | Operating pumps, valves, and alarm circuits |
| Compressor Systems | Switching auxiliary equipment and compatible control circuits |
| Chemical Processing | Controlling electrical actuators and process auxiliaries |
| Industrial Utilities | Operating ventilation, lubrication, and auxiliary loads |
| Automated Production Lines | Coordinating multiple discrete electrical loads through PLC logic |
| Component | Function |
|---|---|
| TSXDSY08R5A | Eight-channel protected relay output module |
| Modicon Premium CPU | Executes PLC control programs |
| Modicon Premium Rack | Provides module mounting and backplane connections |
| Premium Power Supply Module | Supplies operating power to the PLC rack |
| Premium Digital Input Module | Collects discrete field signals |
| Premium Analog Input Module | Acquires continuous process measurements |
| Contactor | Switches external motor power circuits |
| Auxiliary Relay | Provides additional electrical switching contacts |
| Fast-Acting Fuse | Protects relay output circuits |
| RC Suppression Circuit | Reduces switching overvoltage from AC inductive loads |
| MOV | Limits transient voltage across AC inductive circuits |
| Discharge Diode | Suppresses voltage spikes from DC inductive loads |
| Model | Product Type | Typical Application |
|---|---|---|
| Schneider TSXDSY08R5A | Discrete Relay Output Module | Eight-channel protected relay switching |
| Schneider TSXDSY16R5 | Discrete Relay Output Module | Multi-channel relay-based output control |
| Schneider TSXDSY16T2 | Discrete Transistor Output Module | DC transistor switching applications |
| Schneider TSXDSY32T2K | Discrete Transistor Output Module | High-density DC output control |
| Schneider TSXDSY32T3K | Discrete Transistor Output Module | High-density discrete transistor output applications |
| Schneider TSXDEY16A2 | Discrete Input Module | Collecting field status and switching feedback |
Yes. The module supports nominal output voltages of 24–240 V AC and 12–24 V DC. The corresponding operating limits are 20–264 V AC and 10–34 V DC. The connected load must also comply with the applicable current and electrical switching ratings.
No. The TSXDSY08R5 is specified as a relay output module with unprotected outputs. External fast-acting fuses must be installed for each channel or an appropriate group of channels to protect against overload and short circuits.
The required suppression method depends on the coil supply. For AC inductive loads, an RC circuit and MOV are used to limit switching overvoltage. For DC inductive loads, a discharge diode is installed across the preactuator. Correct suppression helps reduce electrical stress on relay contacts.
The module should not be used as a direct motor power switching device. Its relay contacts are intended for compatible control circuits, such as contactor coils. For a three-phase motor, the PLC output should operate a suitably rated contactor or motor control arrangement, with the motor power circuit handled by the appropriate switching and protection equipment.