• Schneider MT20H1b Circuit Breaker
  • Schneider MT20H1b Circuit Breaker
  • Schneider MT20H1b Circuit Breaker
  • Schneider MT20H1b Circuit Breaker
Product Overview The Schneider MT20H1b Circuit Breaker is an industrial air circuit breaker associated with the Masterpact MT family. Designed for high-current low-voltage power distribution systems, it……
Schneider MT20H1b Circuit Breaker
  • Schneider
  • MT20H1b
  • Circuit Breaker
  • France
  • 439 x 556 x 395 mm
  • 70 kg
  • Xiamen, China
  • New & In Stock
  • T/T, PayPal, Western Union
  • 1 Year
  • 1-3 Working Days
  • DHL, UPS, TNT, FedEx and EMS.
  • 24-Hour Service
  • COO
  • 4

Our advantage

Schneider MT20H1b Circuit Breaker

Global Logistics

We have a 10-year logistics and express cooperation agreement, so our products can be shipped to any place in the world.

Schneider MT20H1b Circuit Breaker

Brand new and original

Our products are imported in bulk from the place of origin. Because of the cooperative relationship, our products are all original and 100% new.

Schneider MT20H1b Circuit Breaker

24-hour service

We provide 7*24 hours service to our customers. We will be there whenever you need us.

Schneider MT20H1b Circuit Breaker

Price advantage

All our products are priced very favorably because we have our own warehouse and supply.


Company Information
E-mail [email protected]
Mobile +8615980777398
Whatsapp +8615980777398
WeChat 15980777398

Product Overview

The Schneider MT20H1b Circuit Breaker is an industrial air circuit breaker associated with the Masterpact MT family. Designed for high-current low-voltage power distribution systems, it provides protection against electrical faults such as overloads and short circuits. Its 2000 A frame rating makes it suitable for applications where substantial electrical loads must be controlled and protected.

Air circuit breakers (ACBs) are commonly installed in main distribution boards, industrial switchboards, generator panels, and large electrical distribution assemblies. They provide a means of switching and isolating power circuits while incorporating protective functions that help prevent electrical faults from causing damage to cables, busbars, transformers, motors, and connected equipment.

The MT20H1b designation identifies a 2000 A Masterpact MT configuration with an H1b breaking-capacity class. Published product-family information associates the H1b class with an ultimate short-circuit breaking capacity of up to 85 kA under specified electrical conditions. The actual breaking capacity must always be verified against the exact breaker nameplate and applicable technical documentation.

The MT20H1b should not be confused with the newer MasterPact MTZ2 20H1b. Although the product families share similar naming conventions and current ratings, they belong to different generations and may have different dimensions, accessories, trip units, connection arrangements, and maintenance requirements.

For industrial maintenance and replacement projects, checking the complete model designation, pole configuration, mounting arrangement, trip unit, and accessory configuration is essential before purchasing or installing this breaker.

Technical Specifications

Parameter Specification
Brand Schneider Electric
Product Model MT20H1b
Product Family Masterpact MT
Product Type Air Circuit Breaker (ACB)
Rated Frame Current 2000 A
Breaking Capacity Class H1b
H1b Breaking Capacity Up to 85 kA under specified conditions; verify nameplate
Electrical System Low-voltage AC power distribution
Mounting Arrangement Verify fixed or drawout configuration
Pole Configuration Verify exact 3P or 4P version
Protection Function Overload and short-circuit protection, according to installed trip unit
Trip Unit Depends on the installed configuration
Dimensions Provided 439 × 556 × 395 mm
Weight Provided 70 kg
Typical Installation Industrial switchboards and main distribution panels

Important: The dimensions and weight are supplied listing values. Confirm them against the physical breaker and its configuration. Do not use specifications for MasterPact MTZ2 as a substitute for the original Masterpact MT documentation.

Function and Working Principle

The Schneider MT20H1b is designed to protect high-current electrical distribution circuits. It combines switching contacts, an arc-interruption arrangement, and a protective release or trip unit. When a fault is detected, the trip mechanism operates the breaker to interrupt the current.

1. Overload Protection

An overload occurs when a circuit carries more current than its intended operating level for an extended period. This can cause cables, busbars, and electrical equipment to overheat.

The breaker works with its installed trip unit to detect overload conditions and initiate a trip when the configured protection threshold and time characteristics are exceeded. Correct protection settings help coordinate the breaker with the capacity of the protected circuit.

2. Short-Circuit Protection

A short circuit can produce a very high fault current within a short period. If not interrupted, this current may cause severe thermal and mechanical stress on electrical equipment.

The MT20H1b belongs to the H1b breaking-capacity class. Its short-circuit interruption capability must be evaluated at the actual system voltage and against the available prospective fault current.

The installed breaker must have an adequate interrupting rating for the electrical system. The H1b designation alone should not be used without checking the applicable rating table.

3. Switching and Isolation

An air circuit breaker can be used to connect or disconnect an electrical distribution circuit. Depending on its configuration and installation, it may support routine switching, maintenance isolation, and emergency disconnection as part of the wider electrical protection system.

Isolation procedures must follow the applicable electrical safety rules. Operating the breaker handle or opening the contacts does not replace verification that the circuit is electrically safe to work on.

4. Arc Interruption

When a circuit breaker opens while carrying current, an electrical arc can form between its contacts. The breaker uses an arc-control and interruption arrangement to extinguish this arc and safely interrupt the circuit within its rated capability.

The interruption performance depends on the breaker design, condition, electrical rating, and maintenance status.

5. Protective Coordination

The trip unit and upstream or downstream protective devices must be coordinated with the electrical distribution system. Proper coordination helps isolate the affected section while maintaining power to unaffected parts of the facility where possible.

Protection settings should be established through an appropriate electrical study and verified by qualified personnel.

Role in Industrial Power Distribution Systems

The MT20H1b is intended for use in high-current electrical distribution assemblies. It can serve as a main incoming breaker, a bus-section breaker, or a feeder breaker, depending on the switchboard design and electrical protection strategy.

Main Incoming Protection

In a main distribution board, an ACB may be installed at the incoming supply to protect the main busbar system and downstream circuits. The breaker must be selected according to the supply capacity, fault level, system grounding arrangement, and protection coordination requirements.

Generator and Transformer Distribution

Industrial facilities may use ACBs in generator output panels or transformer secondary distribution assemblies. In these installations, the breaker provides switching and protective functions appropriate to the system design.

Generator and transformer applications require particular attention to fault-current characteristics, protection settings, and coordination with other protective devices.

Busbar Sectionalizing

Some switchboards use a bus-section breaker to connect or separate two sections of a distribution busbar. This arrangement can support maintenance procedures and distribution flexibility.

The breaker configuration and interlocking arrangement must be designed to prevent unsafe switching operations.

Feeder Protection

An ACB can also protect a high-current outgoing feeder supplying a large machine, distribution panel, or industrial process area. The trip settings must be matched to the feeder cable, downstream equipment, and available fault current.

Industrial Applications

1. Manufacturing Plants

Manufacturing facilities use large distribution boards to supply production lines, motor control centers, heating equipment, and auxiliary systems. A 2000 A air circuit breaker may be used in a main or sectional distribution position when its ratings match the electrical installation.

2. Power Distribution Rooms

Industrial power distribution rooms often contain main switchboards and sub-distribution assemblies. The MT20H1b can be used in a compatible switchboard design to provide switching and circuit protection.

3. Generator Systems

Generator switchboards require protective devices that can handle the generator’s rated current and interrupt fault currents under the relevant operating conditions. An ACB may form part of the generator’s main protection arrangement.

The exact breaker and trip-unit configuration must be checked against the generator manufacturer’s requirements and the protection study.

4. Transformer Secondary Panels

A high-current ACB may be installed on the secondary side of a distribution transformer to protect downstream busbars and feeders. Selection must consider transformer rating, impedance, prospective fault current, and coordination with upstream protection.

5. Industrial Infrastructure

Large facilities such as water treatment plants, processing facilities, and industrial utility buildings require dependable power distribution. ACBs help protect the electrical infrastructure supplying pumps, compressors, ventilation systems, and other large loads.

Installation and System Integration

Air circuit breakers are high-energy electrical devices. Installation, testing, and maintenance must be carried out by qualified personnel using the manufacturer’s instructions and applicable electrical standards.

1. Verify the Complete Breaker Configuration

Before installation, check the full model designation and the nameplate. Confirm:

  • Rated current and applicable voltage.
  • H1b short-circuit breaking rating.
  • Three-pole or four-pole configuration.
  • Fixed or drawout mounting arrangement.
  • Installed trip unit and protection functions.
  • Terminal and busbar connection arrangement.
  • Auxiliary contacts and electrical accessories.
  • Mechanical and electrical interlocks.

A breaker with the same 2000 A frame rating may have a different pole configuration or trip unit and may not be a direct replacement.

2. Check Switchboard Compatibility

Confirm that the breaker is designed for the intended switchboard and chassis. Check mounting dimensions, busbar spacing, terminal positions, connection pitch, and required clearances.

The supplied dimensions of 439 × 556 × 395 mm should be treated as listing information until verified against the exact product drawing. The mounting arrangement can affect the overall installation envelope.

3. Inspect Electrical Connections

Inspect the breaker terminals, contact surfaces, busbar connections, and insulating components before installation. Damaged or contaminated contact surfaces can increase resistance and cause localized heating.

Connection torque must follow the applicable manufacturer’s documentation. Do not use generic torque values for high-current connections.

4. Configure the Protection System

The installed trip unit must be configured for the protected circuit. Protection settings should reflect cable capacity, load characteristics, system fault levels, and coordination requirements.

Do not increase protection settings simply to prevent nuisance tripping. Any setting changes should be supported by an appropriate protection study and approved engineering procedures.

5. Verify Mechanical and Electrical Interlocks

For drawout or multi-breaker installations, confirm that the operating and interlocking mechanisms work correctly. Interlocks help prevent unsafe operations, including prohibited switching sequences.

Check the breaker position indicators and verify that the mechanism operates as intended before energizing the switchboard.

6. Commissioning and Functional Testing

Before returning the breaker to service, perform the inspections and tests required by the manufacturer’s instructions and the facility’s commissioning procedures.

Depending on the installation, checks may include insulation condition, contact resistance, mechanical operation, trip-unit testing, auxiliary-contact operation, and verification of protective settings.

Record the test results and final configuration for future maintenance.

Compatible System Components

The MT20H1b operates as part of a larger low-voltage power distribution assembly. The exact accessories and supporting components depend on the installed breaker configuration.

Component Function Compatibility Considerations
Masterpact MT chassis Supports a compatible drawout breaker Must match the breaker generation, frame, and configuration
Electronic trip unit Provides configurable protection functions Verify exact trip-unit type and protection features
Auxiliary contacts Provide breaker status signals Confirm contact arrangement and electrical ratings
Shunt trip release Enables remote electrical tripping Check operating voltage and accessory compatibility
Undervoltage release Trips or prevents closing under specified voltage conditions Verify coil rating and control-circuit design
Closing release Supports electrical closing operation Confirm the correct operating voltage and mechanism
Switchboard busbars Carry the main distribution current Check current rating, spacing, and connection arrangement
PLC or power management system Monitors or coordinates electrical distribution Requires compatible auxiliary signals or communication accessories
Protection relay Provides additional system protection where required Coordinate with the ACB trip unit and protection design

Not all components are supplied with the breaker. Confirm the installed accessories and required parts before ordering.

Alternative Models and Replacement Considerations

The MT20H1b belongs to the Masterpact MT generation. A replacement must be selected according to the original electrical and mechanical configuration.

Related Product or Option Replacement Considerations
Another Masterpact MT20H1b May be considered for like-for-like replacement after verifying poles, mounting, trip unit, and accessories
Masterpact MT20H1 Similar family designation but different breaking-capacity class; do not assume equivalent protection
Masterpact MT20H2 Different breaking-capacity class; requires engineering verification
MasterPact MTZ2 20H1b Newer product generation, not automatically a direct mechanical or electrical replacement
Other 2000 A Masterpact ACB Must be checked for voltage, breaking capacity, frame, trip unit, chassis, and connection compatibility

Before selecting a replacement, compare:

  • Rated current and operating voltage.
  • Ultimate and service short-circuit breaking capacity.
  • Pole configuration.
  • Fixed or drawout installation.
  • Trip-unit type and protection settings.
  • Busbar and terminal dimensions.
  • Chassis and mounting compatibility.
  • Auxiliary contacts and control accessories.
  • Interlocking arrangements.
  • Switchboard clearance and overall dimensions.

A newer breaker may require a compatible chassis, revised busbar connections, new control wiring, or modifications to the switchboard. A qualified electrical engineer should approve the replacement design.

Key Advantages

High-Current Distribution Capability

The 2000 A frame rating makes the MT20H1b suitable for appropriately designed high-current distribution applications.

Short-Circuit Protection

Its H1b breaking-capacity class is intended for systems with demanding fault-current requirements. The exact interrupting capability must be checked at the applicable system voltage.

Integrated Switching and Protection

An ACB combines circuit switching with protective tripping functions, supporting the operation of industrial distribution assemblies.

Industrial Switchboard Integration

The Masterpact MT family is designed for industrial power distribution equipment. Its installation and accessories must match the corresponding switchboard configuration.

Configurable Protection

The installed trip unit determines the available protection functions and settings. This allows the breaker to be configured as part of a coordinated electrical protection system.

Maintenance and Replacement Use

The MT20H1b may be relevant to maintenance and spare-parts requirements in facilities operating legacy Masterpact MT switchboards.

Technical FAQs

1. What is the Schneider MT20H1b?

The MT20H1b is a Masterpact MT air circuit breaker associated with a 2000 A frame rating and H1b breaking-capacity class. It is designed for high-current low-voltage AC power distribution protection.

2. What does 2000 A mean?

The 2000 A designation identifies the breaker frame’s rated current class. Actual permissible operating current depends on the complete breaker configuration, ambient conditions, installation, and applicable derating requirements.

3. What does H1b mean?

H1b identifies a short-circuit breaking-capacity class. Published product-family information associates this class with up to 85 kA under specified conditions. The exact rating must be confirmed at the relevant operating voltage and from the breaker nameplate.

4. Is the MT20H1b the same as the MTZ2 20H1b?

No. The MT20H1b designation is associated with the older Masterpact MT generation, while MTZ2 20H1b belongs to a newer product family. Their mechanical dimensions, accessories, trip units, and maintenance requirements should not be assumed to be interchangeable.

5. Is the breaker fixed or drawout?

The model name alone does not establish the complete mounting arrangement. Confirm whether the specific unit is fixed-mounted or drawout and check its chassis and switchboard configuration.

6. Does the breaker include an electronic trip unit?

The installed trip-unit configuration must be confirmed from the product label and physical inspection. Different Masterpact MT configurations may use different trip units and accessories.

7. Can it be used in a 2000 A industrial switchboard?

It may be suitable when the system voltage, rated current, short-circuit level, pole configuration, mounting arrangement, and protection requirements match the breaker specifications. A qualified engineer should verify the complete installation.

8. Can it replace a Masterpact MTZ2 breaker?

Not automatically. The MT and MTZ2 generations may differ in chassis, connections, trip units, dimensions, and accessories. A replacement assessment is necessary before installation.

9. What should be checked before purchasing a used MT20H1b?

Check the complete nameplate, rated current, breaking-capacity class, pole configuration, mounting arrangement, trip unit, contact condition, operating mechanism, and accessory inventory. For critical applications, request suitable inspection and functional test records.

10. Are the supplied dimensions and weight confirmed manufacturer values?

The dimensions of 439 × 556 × 395 mm and weight of 70 kg are the supplied listing values. They should be verified against the exact physical breaker and its mounting configuration before being used for panel engineering or shipping.

Procurement and Maintenance Recommendations

When purchasing a Schneider MT20H1b, begin by identifying the exact breaker configuration. The MT20H1b designation is not sufficient on its own to confirm the number of poles, mounting arrangement, trip unit, or installed accessories.

Request clear photographs of the nameplate, front panel, terminals, and operating mechanism. Confirm the H1b breaking-capacity designation and the applicable voltage rating. For drawout versions, check whether the matching chassis is included or must be sourced separately.

For used or refurbished breakers, ask for inspection records and appropriate functional test information. Check the condition of the contacts, arc-interruption components, insulation, mechanism, and accessories. Confirm the supplier’s warranty and return terms before placing an order.

During maintenance, follow the manufacturer’s inspection intervals and procedures. Keep the breaker clean, inspect connections for signs of overheating, and verify the condition of the operating mechanism and trip unit. Any protection-setting changes should be documented and approved by qualified personnel.

For replacement projects, do not select a breaker based only on the 2000 A rating. Verify the short-circuit rating, system voltage, pole arrangement, mounting dimensions, trip-unit functions, and switchboard compatibility. If replacing an older Masterpact MT unit with a newer MTZ product, plan for a full engineering review.

Conclusion

The Schneider MT20H1b Masterpact air circuit breaker is a high-current protection device associated with a 2000 A frame rating and H1b short-circuit breaking-capacity class. It is intended for industrial low-voltage distribution systems where reliable circuit switching and fault protection are required.

For maintenance and procurement, accurate identification is essential. The MT20H1b should be distinguished from the newer MTZ2 generation, and its pole configuration, mounting arrangement, trip unit, accessories, and electrical ratings should be verified before installation. Careful inspection and correct protection coordination help support safe and dependable operation in industrial power distribution systems.



Related Products

Get the latest price? We will reply as soon as possible (within 12 hours)

No:77501