Allen-Bradley 1336-SN-SP15A Inverter Snubber PCB Installation Guide

2026-11-25 

The Allen-Bradley 1336-SN-SP15A Inverter Snubber PCB is a power-electronics protection component used in compatible 575V Allen-Bradley 1336 adjustable frequency drives. Its function is to help suppress transient voltage disturbances associated with inverter switching and protect sensitive power circuit components. Correct installation requires confirmation of drive compatibility, careful isolation of the high-voltage DC bus, inspection of the mounting position, and verification of all electrical connections before the drive is returned to service.

This guide explains the preparation, replacement considerations, installation checks, and commissioning procedures for the 1336-SN-SP15A. Because this component is installed inside a high-energy drive assembly, replacement should only be performed by qualified personnel familiar with the specific 1336 drive model.

Contents: 1336-SN-SP15A Installation and Replacement

1. 1336-SN-SP15A Inverter Snubber PCB Function and Application

The 1336-SN-SP15A is an inverter snubber printed circuit board assembly for selected Allen-Bradley 1336 drive configurations. A snubber circuit helps control transient voltage and switching-related electrical stress in power electronic circuits. In a high-power adjustable frequency drive, these protection functions are important because the inverter operates with substantial electrical energy and rapidly switching semiconductor devices.

The component is associated with 575V 1336 drive applications in the higher-power range. The manufacturer’s product identification describes it as an inverter snubber PCB for 1336STG 575V drives rated 300–650 HP, while the product information also identifies 1336STEF as the applicable drive family. Therefore, the exact drive catalog number and hardware configuration must be checked before ordering or installing this part.

Typical Application Areas

  • High-power industrial motor drive systems.
  • Large pumps and process equipment.
  • Industrial fans and blowers.
  • Material-handling and heavy-duty machinery.
  • Production equipment using compatible 575V 1336 drives.

Why the Snubber PCB Matters

Power semiconductor switching can produce transient voltage conditions within a drive’s power circuit. The snubber network helps manage these disturbances and reduce electrical stress on associated components. A damaged or incorrectly installed snubber assembly can contribute to abnormal power circuit behavior, repeated component failures, or drive trips.

The 1336-SN-SP15A is a protection-related power assembly, not a general-purpose control board. It should not be replaced with a visually similar PCB unless the replacement is confirmed as electrically and mechanically compatible with the exact drive configuration.

2. Allen-Bradley 1336-SN-SP15A Drive Compatibility and Part Verification

Compatibility verification is the most important step before replacing the 1336-SN-SP15A. The 1336 drive family includes different voltage ratings, power ranges, frame sizes, and hardware revisions. Snubber boards that look similar may have different electrical characteristics or mounting arrangements.

Confirm the Drive Nameplate

Record the complete drive catalog number, input voltage, horsepower rating, frame designation, and relevant series information. Compare these details with the applicable spare-parts documentation for the drive. Do not identify compatibility using voltage rating alone.

Check the Required Quantity

The 1336-SN-SP15A spare-parts information identifies a requirement of three inverter snubber PCBs per applicable drive. The replacement quantity should be checked against the actual assembly and the drive-specific parts list. Do not assume that replacing one visible board is sufficient when the applicable configuration requires a matched set.

Verify the Installation Position

The exact mounting position and board designation depend on the drive power assembly. Parts information associates this model with the A21–A23 inverter snubber positions in the applicable configuration. Confirm the component locations against the correct drive drawing before removing any board.

Part Compatibility Checklist

  • Confirm the complete 1336 drive catalog number.
  • Verify the 575V voltage class.
  • Check the horsepower rating and frame designation.
  • Compare the part number with the drive-specific spare-parts list.
  • Confirm the required number of snubber PCBs.
  • Check the PCB revision and mounting arrangement.
  • Inspect the replacement kit for mounting hardware and other supplied components.

Never use the 1336-SN-SP15A as a substitute for another snubber board simply because both parts belong to the 1336 product family.

3. Safety Preparation Before 1336-SN-SP15A Installation

The 1336-SN-SP15A is installed within a high-voltage drive assembly. The DC bus capacitors can retain dangerous electrical energy after the incoming AC supply has been disconnected. Turning off the drive or opening an upstream disconnect does not prove that the internal power circuit is safe to touch.

Mandatory Electrical Isolation

  1. Stop the connected machine using the approved operating procedure.
  2. Disconnect and isolate all applicable incoming power sources.
  3. Apply the site’s lockout/tagout procedure.
  4. Wait for the discharge time specified in the exact drive manual.
  5. Use an appropriately rated meter to verify the absence of hazardous voltage at the designated DC bus test points.
  6. Verify the absence of control voltage at the specified control circuit test points.
  7. Confirm that the electrical condition remains safe before accessing the internal assembly.

Never rely solely on a discharge indicator, elapsed time, or the position of a disconnect switch. The DC bus must be measured using an approved instrument and the manufacturer’s specified procedure.

Required Tools and Preparation

  • Suitable insulated electrical tools.
  • Voltage measurement equipment rated for the circuit.
  • Approved personal protective equipment.
  • ESD protection equipment for handling circuit boards.
  • Drive-specific wiring diagrams and spare-parts documentation.
  • Replacement mounting hardware specified for the assembly.

ESD and Component Handling

Handle the snubber PCB by its edges and avoid touching exposed electronic components or conductive contact areas. Keep the replacement board in its protective packaging until installation. Do not place the PCB on metal surfaces or in locations where conductive debris can contact the circuitry.

4. Inspection of the Allen-Bradley 1336 Inverter Power Assembly

Before removing the existing snubber board, inspect the surrounding power assembly. The condition of nearby components may help identify why the original board failed.

Check for Visible PCB Damage

  • Cracked or discolored circuit board areas.
  • Burn marks around resistive or semiconductor components.
  • Damaged solder joints or lifted conductive tracks.
  • Signs of overheating near connectors.
  • Corrosion, dust accumulation, or conductive contamination.
  • Damaged mounting holes or insulating supports.

Inspect the Surrounding Power Components

Check the relevant inverter assembly, heatsink area, bus connections, and associated wiring for visible damage. A failed snubber PCB may be a symptom of a wider power circuit problem. Replacing the board without investigating the original failure can result in repeated damage.

Document the Original Wiring and Position

Before disconnecting any jumper or connector, record its original position using the drive wiring diagram and maintenance documentation. In particular, verify the specified jumper positions and connector orientation. Do not rely on memory or assume that every 1336 drive revision uses an identical arrangement.

5. Allen-Bradley 1336-SN-SP15A Inverter Snubber PCB Replacement Procedure

The replacement sequence must follow the service instructions for the exact 1336 drive model. The following workflow provides a general maintenance framework, not a substitute for the drive-specific electrical and mechanical procedure.

Step 1: Confirm the Power Circuit Is Safe

Complete the isolation and voltage verification procedure described above. Confirm the DC bus and control voltage test points meet the manufacturer’s safe-work requirements before touching the assembly.

Step 2: Identify the Correct Snubber Assembly

Locate the inverter snubber PCB position using the drive-specific parts drawing. Confirm the correct A21–A23 position where applicable and compare the installed component with the replacement part.

Step 3: Record and Disconnect the Relevant Connections

Identify the jumper connectors and other electrical connections associated with the snubber PCB. Record their locations and orientation. Disconnect only the connectors identified in the applicable service procedure. Avoid pulling on wires or applying force to fragile connector housings.

Step 4: Remove the Existing Board

Remove the specified fastening screws and mounting hardware. Support the PCB during removal to avoid bending it or damaging adjacent components. Inspect the mounting plate and bracket after the board has been removed.

Step 5: Install the Replacement 1336-SN-SP15A

Position the replacement PCB in the designated mounting location. Confirm the alignment of the mounting holes and insulating supports. Install the specified fasteners and tighten them according to the drive service documentation. Do not substitute unrelated screws or mounting hardware.

Step 6: Reconnect the Jumpers and Wiring

Reconnect the identified jumper connectors in their documented positions. Check that each connection is fully seated and correctly oriented. Inspect the wiring for pinching, abrasion, or contact with sharp edges and hot components.

Step 7: Complete the Assembly Inspection

Verify that the replacement PCB is secure and that all relevant connectors, fasteners, and protective covers are correctly installed. Confirm that no tools, loose hardware, or foreign materials remain inside the drive.

6. 1336-SN-SP15A Electrical and Mechanical Verification

Before restoring power, carry out a systematic inspection of the replaced snubber assembly and surrounding drive components. This is particularly important in high-power applications where a loose connection or incorrect component can lead to further damage.

Mechanical Inspection

  • Confirm the correct PCB catalog number.
  • Check that the board is installed in the specified position.
  • Verify that the mounting plate and fasteners are secure.
  • Confirm that the board does not contact adjacent conductive parts.
  • Check that all covers and barriers are correctly reinstalled.

Electrical Connection Inspection

  • Verify all specified jumper connections.
  • Inspect connector housings for damage.
  • Check that no wires have been trapped or pinched.
  • Confirm that the surrounding power circuit has no visible damage.
  • Review the work against the drive-specific schematic.

Why a Complete Inspection Matters

A snubber PCB is part of a coordinated power circuit. Incorrect jumper placement, loose connections, or a mismatched replacement board can affect circuit behavior. The replacement should therefore be treated as a power electronics maintenance task rather than a simple plug-in control board exchange.

7. Allen-Bradley 1336-SN-SP15A Drive Startup and Commissioning

After the installation inspection is complete, the drive can be prepared for controlled startup. Power restoration and operational testing must follow the manufacturer’s procedure and the site’s machine safety requirements.

Pre-Energization Checklist

  1. Confirm that the work area is clear.
  2. Check that all tools and temporary test leads have been removed.
  3. Verify the snubber PCB installation and connector positions.
  4. Confirm that the drive enclosure and protective covers are secured.
  5. Ensure that personnel are clear of hazardous moving equipment.
  6. Complete the required authorization before restoring power.

Initial Power-Up

Restore power according to the drive’s startup procedure. Observe the drive’s display and diagnostic indications. If an abnormal condition appears, stop the commissioning process and investigate the reported fault rather than repeatedly resetting the drive.

Controlled Operational Test

Where the machine design permits, perform an approved low-risk operational test before returning the equipment to its normal production duty. Monitor drive status, motor behavior, current, and relevant fault indications. Compare operating values with the established baseline for the application.

Maintenance Record

Record the replacement part number, drive catalog number, board revision where available, work date, test results, and any related components inspected or replaced. Retain this information with the drive maintenance history to support future troubleshooting.

8. Allen-Bradley 1336-SN-SP15A Technical Specifications

Parameter Specification
Manufacturer Allen-Bradley / Rockwell Automation
Catalog Number 1336-SN-SP15A
Product Type Inverter Snubber PCB
Product Family 1336 Adjustable Frequency Drives
Drive Voltage Class 575 V
Published Drive Rating 300–650 HP in the manufacturer’s product identification
Related Drive Information 1336STG / 1336STEF; confirm exact catalog compatibility
Applicable Power Assembly Positions A21–A23 in the referenced spare-parts configuration
Quantity per Applicable Drive 3 inverter snubber PCBs
Accessory Category Snubber PCBs
Electrical Function Transient suppression in the inverter power circuit
Lifecycle Status Discontinued
Manufacturer Discontinuation Date January 31, 2022
Dimensions Not confirmed in the available manufacturer product data
Weight Not confirmed in the available manufacturer product data

Compatibility note: The manufacturer’s product identification and spare-parts references should be checked against the exact drive nameplate and hardware revision. The 300–650 HP description and the broader 300–800 HP range appearing in some parts listings should not be treated as interchangeable without confirmation from the applicable drive documentation.

9. Technical FAQs About the Allen-Bradley 1336-SN-SP15A

What is the 1336-SN-SP15A?

It is an Allen-Bradley inverter snubber printed circuit board assembly used in compatible 575V 1336 drive configurations.

What does an inverter snubber PCB do?

A snubber circuit helps suppress transient voltage disturbances associated with switching in power electronic circuits. It helps reduce electrical stress on relevant inverter components.

Which drives use the 1336-SN-SP15A?

The manufacturer’s product information identifies it with 575V 1336STG applications and also lists 1336STEF in the use-with information. Confirm the exact drive catalog number, frame, and power rating before ordering.

How many 1336-SN-SP15A boards are required per drive?

The applicable spare-parts information specifies three inverter snubber PCBs per drive. Confirm the actual requirement using the drive-specific parts list.

Can the 1336-SN-SP15A be used on a 460V drive?

It is identified as a 575V snubber PCB. Do not install it in a 460V drive unless the manufacturer documentation explicitly confirms compatibility for the exact drive configuration.

What should be checked before replacing the snubber PCB?

Verify the drive catalog number, voltage rating, horsepower, frame, board position, revision, and required quantity. Also inspect the surrounding power assembly for damage.

Is it safe to replace the PCB immediately after disconnecting the drive?

No. The DC bus capacitors may retain dangerous voltage after power is removed. Follow the specified discharge time and verify the absence of hazardous voltage at the designated test points with an appropriately rated meter.

Why should the original jumper positions be recorded?

Jumper locations and connections are part of the power circuit configuration. Incorrect placement can cause abnormal operation or damage. Always follow the correct drive schematic and service procedure.

Is the 1336-SN-SP15A still available as a current manufacturer product?

Rockwell Automation lists the 1336-SN-SP15A as discontinued effective January 31, 2022. Availability of unused or refurbished stock depends on independent suppliers.

Should a damaged snubber PCB be repaired at component level?

Internal repair should not be attempted without an approved repair process and the necessary power electronics expertise. A damaged assembly should be evaluated by a qualified service provider or replaced with a confirmed compatible part.

10. Installation Conclusion: Allen-Bradley 1336-SN-SP15A Inverter Snubber PCB

The Allen-Bradley 1336-SN-SP15A is a specialized inverter snubber PCB for compatible 575V 1336 drive power assemblies. Its correct installation depends on accurate drive identification, verification of the required board quantity, safe DC bus isolation, correct jumper connections, and careful mechanical inspection.

Because the component is part of a high-energy power circuit and the catalog number is discontinued, replacement work should be based on the exact drive documentation rather than assumptions from similar 1336 models. A controlled startup and documented operational test help confirm that the repaired drive is ready for service.

Get the latest price? We will reply as soon as possible (within 12 hours)

No:77501