• Schneider NW16N2 Circuit Breaker
  • Schneider NW16N2 Circuit Breaker
  • Schneider NW16N2 Circuit Breaker
  • Schneider NW16N2 Circuit Breaker
Product Overview The Schneider Electric NW16N2 Circuit Breaker is a low-voltage air circuit breaker (ACB) from the Masterpact NW family. Designed for industrial power distribution systems, this type of ……
Schneider NW16N2 Circuit Breaker
  • Schneider
  • NW16N2
  • Circuit Breaker
  • France
  • 352 x 537 x 297 mm
  • 65 kg
  • Xiamen, China
  • New & In Stock
  • T/T, PayPal, Western Union
  • 1 Year
  • 1-3 Working Days
  • DHL, UPS, TNT, FedEx and EMS.
  • 24-Hour Service
  • COO
  • 5

Our advantage

Schneider NW16N2 Circuit Breaker

Global Logistics

We have a 10-year logistics and express cooperation agreement, so our products can be shipped to any place in the world.

Schneider NW16N2 Circuit Breaker

Brand new and original

Our products are imported in bulk from the place of origin. Because of the cooperative relationship, our products are all original and 100% new.

Schneider NW16N2 Circuit Breaker

24-hour service

We provide 7*24 hours service to our customers. We will be there whenever you need us.

Schneider NW16N2 Circuit Breaker

Price advantage

All our products are priced very favorably because we have our own warehouse and supply.


Company Information
E-mail [email protected]
Mobile +8615980777398
Whatsapp +8615980777398
WeChat 15980777398

Product Overview

The Schneider Electric NW16N2 Circuit Breaker is a low-voltage air circuit breaker (ACB) from the Masterpact NW family. Designed for industrial power distribution systems, this type of circuit breaker provides protection against electrical faults and serves as a switching and isolation device in high-current distribution applications.

Air circuit breakers are commonly installed in main distribution boards, switchgear assemblies, power control centers, and other electrical installations where substantial current must be controlled safely. They help protect electrical circuits and connected equipment from overloads and short circuits by interrupting current when abnormal conditions are detected by the configured protection system.

The NW16N2 belongs to the NW16 frame class, associated with a 1600 A frame rating. The actual operating current and protection characteristics depend on the installed trip unit, rating plug, circuit-breaker configuration, and applicable product standard. These details should be checked against the nameplate and technical documentation of the specific unit.

The Masterpact NW platform is designed for demanding electrical distribution environments. Depending on the selected configuration, the product family supports fixed-mounted or drawout arrangements, different trip-unit options, and accessories for monitoring, control, and remote operation.

The NW16N2 is relevant to maintenance and replacement work in industrial facilities where existing Masterpact NW switchgear remains in service. Before purchasing, engineers should verify the complete model designation, rated voltage, number of poles, breaking capacity, trip-unit type, and mounting arrangement.

Technical Specifications

Parameter Specification
Brand Schneider Electric
Product Family Masterpact NW
Model NW16N2
Product Type Air Circuit Breaker (ACB)
Circuit Breaker Category Low-Voltage Power Circuit Breaker
Frame Class NW16
Frame Current Rating 1600 A
Rated Operational Voltage Verify from nameplate and exact configuration
Number of Poles Verify actual unit
Trip Unit Configuration-dependent
Protection Functions Depends on installed trip unit
Mounting Arrangement Fixed or drawout; verify actual configuration
Breaking Capacity Verify from complete model designation and nameplate
Dimensions Provided 352 × 537 × 297 mm
Weight Provided 65 kg
Typical Applications Main distribution boards, industrial switchgear, power distribution systems

Important: The table distinguishes the NW16 frame class from the actual operating and protection ratings. Do not assume that every NW16N2 unit has the same trip unit, pole configuration, voltage rating, or breaking capacity. Confirm these values using the product nameplate and applicable manufacturer documentation.

Function and Working Principle

The NW16N2 is designed to protect and control electrical distribution circuits. Its operation involves current sensing, fault detection, and mechanical interruption of the electrical circuit.

1. Overload Protection

An overload occurs when a circuit carries more current than its permitted operating level for an extended period. This may result from excessive equipment demand, motor overload, or an incorrectly sized electrical system.

When the installed protection unit detects an overload condition that exceeds its configured threshold and time delay, it initiates a trip command. The circuit breaker’s contacts then separate to interrupt the current.

The exact overload protection settings depend on the installed trip unit and rating configuration.

2. Short-Circuit Protection

A short circuit can cause a rapid and substantial increase in current. If not interrupted promptly, the resulting electrical and thermal energy can damage cables, busbars, switchgear, and connected equipment.

The circuit breaker uses its configured protection system to detect a short-circuit condition and initiate interruption. Its ability to safely interrupt fault current depends on the rated breaking capacity at the applicable system voltage.

For this reason, the breaking-capacity rating must be checked against the prospective short-circuit current at the installation point.

3. Arc Interruption

When the main contacts separate under load or during a fault, an electrical arc may form between them. An air circuit breaker uses an arc-control and arc-extinguishing arrangement to interrupt the current safely.

The interruption process is a critical part of circuit-breaker operation. Correct maintenance of the contacts and internal operating mechanism helps preserve reliable performance.

4. Switching and Isolation

In addition to protection, an ACB can be used to switch a power-distribution circuit between connected and disconnected states.

Depending on the installed arrangement, the circuit breaker may support manual operation, electrical closing and opening, and remote control through suitable accessories.

Isolation procedures must follow the equipment manufacturer’s instructions and the site’s electrical safety requirements. A circuit breaker should not be treated as the only means of ensuring a safe work condition without verifying the required isolation and lockout procedures.

5. Protection Coordination

In a multi-level electrical distribution system, circuit breakers must be coordinated so that the protective device closest to a fault can operate appropriately while minimizing unnecessary interruption to other circuits.

The NW16N2’s protection settings should therefore be considered as part of the complete distribution-system design. Engineers should review upstream and downstream protection devices, fault-current levels, and selectivity requirements.

Role in Industrial Power Distribution Systems

The NW16N2 can serve as a main or feeder circuit breaker in an industrial low-voltage distribution system. Its role depends on the electrical architecture and the installed switchgear configuration.

Main Incoming Circuit Protection

In a main distribution board, a large-frame air circuit breaker may be used to control and protect the incoming power supply. It provides a switching point between the incoming source and the downstream distribution network.

The required current rating and fault-interruption capability must be established through electrical-system calculations and equipment specifications.

Feeder Circuit Protection

Industrial facilities often distribute electrical power to multiple production areas, motor-control centers, and auxiliary systems. An ACB can protect a major feeder supplying one of these distribution sections.

The trip-unit settings should be coordinated with downstream protective devices to limit the impact of faults.

Integration with Power Monitoring Systems

Modern industrial distribution systems may use metering and monitoring equipment to collect information about current, voltage, power, and energy consumption.

Depending on the installed accessories and trip-unit configuration, Masterpact NW systems may support additional monitoring and communication functions. These capabilities should not be assumed for every NW16N2 unit; verify the actual accessories and interfaces before planning integration.

Industrial Switchgear Assemblies

The circuit breaker can form part of a larger switchgear assembly containing busbars, protective devices, metering equipment, control circuits, and auxiliary components.

Its physical arrangement, terminal connections, and accessory configuration must match the switchgear design.

Industrial Applications

The Schneider Electric NW16N2 is intended for use in electrical distribution applications where a large-frame circuit breaker is required.

1. Industrial Manufacturing Plants

Manufacturing facilities often have large electrical distribution networks supplying production lines, machine tools, motors, and auxiliary equipment.

An appropriately configured ACB can protect a main incoming supply or a major feeder within the plant’s low-voltage distribution system.

2. Power Distribution Rooms

Electrical distribution rooms contain switchgear and protective devices that distribute power throughout a building or industrial site.

The NW16 frame class may be used in installations where the system design requires a circuit breaker with a frame rating of up to 1600 A. The actual trip rating must be selected according to the circuit requirements.

3. Data Centers

Data centers require reliable electrical distribution for servers, cooling equipment, UPS systems, and supporting infrastructure.

Air circuit breakers may be used in main switchboards and major distribution feeders. Protection coordination and continuity-of-service requirements are especially important in these applications.

4. Water and Wastewater Treatment Facilities

Water treatment plants use pumps, blowers, filtration systems, and other electrically powered equipment.

An ACB installed in the main distribution system can provide protection and switching for major electrical feeders. The protection settings must account for the facility’s electrical load and fault-current conditions.

5. Commercial and Infrastructure Facilities

Large commercial buildings, transportation facilities, and infrastructure installations may require high-current circuit breakers in their main electrical distribution systems.

The Masterpact NW family is designed for this type of power-distribution environment, subject to the exact ratings and configuration of the selected unit.

6. Industrial Power Control Centers

Power control centers distribute electricity to multiple sections of a facility. A circuit breaker such as the NW16N2 may be used as part of a coordinated protection arrangement to help isolate faults and protect downstream equipment.

Installation and System Integration

Correct installation is essential for electrical safety and reliable circuit-breaker operation. The NW16N2 should be installed and commissioned by qualified electrical personnel.

1. Verify Electrical Ratings

Before installation, confirm the system voltage, frequency, rated current, and prospective short-circuit current.

The NW16 frame designation indicates a 1600 A frame class, but the actual trip rating is determined by the installed protection configuration. The circuit breaker’s breaking capacity must be sufficient for the fault level at the installation point.

Do not select or replace a circuit breaker based only on frame size.

2. Confirm Fixed or Drawout Construction

Masterpact NW circuit breakers may be supplied in different mounting arrangements. Fixed-mounted and drawout versions have different installation and connection requirements.

For a drawout installation, confirm the compatibility of the circuit breaker with its cradle, guide rails, position indicators, and secondary connections.

For a fixed installation, verify the mounting arrangement, terminal connections, busbar dimensions, and required mechanical clearances.

3. Check Dimensions and Cabinet Space

The supplied dimensions are:

  • Length: 352 mm
  • Width: 537 mm
  • Height: 297 mm

The listed weight is 65 kg.

These values should be checked against the actual unit and its mounting arrangement before designing or modifying a switchgear cabinet. Additional space may be needed for terminals, busbar connections, operating mechanisms, control wiring, and maintenance access.

The installation should also account for ventilation and the thermal conditions inside the switchgear enclosure.

4. Inspect Busbar and Electrical Connections

Busbar connections must be correctly aligned and installed according to the manufacturer’s specifications. Incorrect contact pressure, poor alignment, or unsuitable connection hardware can lead to overheating and equipment damage.

Inspect connection surfaces and verify the required tightening procedures. Do not apply arbitrary torque values; use the specifications for the exact circuit-breaker and connection arrangement.

5. Configure the Trip Unit

The installed trip unit determines the available protection functions and settings. Before energizing the system, confirm the trip-unit type, rating plug, current settings, time delays, and protection coordination requirements.

The protection configuration should be reviewed against the facility’s electrical protection study.

6. Connect Auxiliary and Control Accessories

Depending on the unit, accessories may include auxiliary contacts, shunt trips, undervoltage releases, motor operators, and communication or monitoring components.

Verify the accessory part numbers, rated control voltages, wiring diagrams, and compatibility with the specific circuit-breaker version.

7. Perform Commissioning Tests

Before returning the equipment to service, qualified personnel should perform the applicable mechanical and electrical inspections.

Typical checks include:

  • Visual inspection of the circuit breaker and terminals.
  • Verification of mounting and connection arrangements.
  • Inspection of the operating mechanism.
  • Verification of trip-unit settings.
  • Testing of auxiliary contacts and control circuits.
  • Functional checks of opening and closing operations.
  • Verification of protective-device coordination.
  • Documentation of commissioning results.

Testing must follow the manufacturer’s instructions and applicable electrical safety standards.

Compatible System Components

The NW16N2 is generally installed as part of a complete switchgear and electrical distribution assembly.

Component Function Integration Considerations
Masterpact NW cradle Supports a compatible drawout circuit breaker Verify frame size, model, and mechanical compatibility
Electronic trip unit Detects abnormal current conditions and initiates tripping Confirm exact trip-unit model and protection functions
Rating plug Defines the applicable current rating for supported configurations Must match the trip unit and circuit-breaker requirements
Auxiliary contacts Provide breaker status signals Check contact arrangement and control-circuit ratings
Shunt trip release Enables remote electrical tripping Confirm coil voltage and accessory compatibility
Undervoltage release Trips or prevents closing under specified undervoltage conditions Verify control voltage and operating requirements
Motor operator Supports electrical charging or operation where applicable Confirm compatibility with the breaker version
Busbar system Distributes power through the switchgear assembly Verify current rating, connection dimensions, and thermal design
Power monitoring equipment Measures electrical operating conditions Check available interfaces and required accessories
Switchgear cabinet Houses the breaker and related electrical equipment Confirm mounting, ventilation, and maintenance clearances

The listed components are examples of equipment that may be used in a complete installation. They are not necessarily included with the NW16N2.

Alternative Models and Replacement Considerations

When replacing an NW16N2, selecting another circuit breaker from the Masterpact family requires more than matching the frame rating.

Alternative or Related Product Replacement Considerations
Another Masterpact NW16 configuration Check voltage, breaking capacity, poles, trip unit, mounting type, and accessories
Masterpact NW08 or NW12 Smaller frame classes; not direct replacements without confirming system current requirements
Masterpact NW20 Larger frame class; may require different switchgear and connection arrangements
Masterpact NT series Different product frame and mechanical arrangement; detailed engineering review required
Current-generation Masterpact circuit breaker May be considered for an upgrade, subject to switchgear compatibility and protection-system review

Before selecting a replacement, compare:

  • Rated operational voltage.
  • Frame current and actual trip rating.
  • Number of poles.
  • Ultimate and service breaking capacities.
  • Short-time withstand current.
  • Trip-unit model and protection functions.
  • Fixed or drawout construction.
  • Cradle and busbar compatibility.
  • Auxiliary and control accessories.
  • Communication and monitoring requirements.
  • Physical dimensions and switchgear clearances.

A replacement circuit breaker must be suitable for the electrical system and the specific switchgear assembly. A similar frame rating does not guarantee mechanical or electrical interchangeability.

Key Advantages

High-Current Distribution Capability

The NW16 frame class is associated with a 1600 A frame rating, making it relevant to large industrial distribution circuits.

Comprehensive Circuit Protection Options

The Masterpact NW family supports different protection configurations. The actual functions depend on the installed trip unit and accessories.

Industrial Switchgear Integration

The product family is designed for installation in low-voltage switchgear and power distribution assemblies.

Configurable Installation Arrangements

Depending on the selected version, Masterpact NW circuit breakers are available in fixed-mounted and drawout arrangements.

Accessory and Monitoring Options

The wider Masterpact NW platform supports auxiliary devices and monitoring options. Availability must be verified for the specific breaker configuration.

Maintenance and Replacement Use

The NW16N2 model designation can help maintenance teams identify existing equipment and source a matching unit for legacy switchgear installations.

Technical FAQs

1. What is the Schneider Electric NW16N2?

The NW16N2 is a Masterpact NW low-voltage air circuit breaker used for switching and protecting electrical distribution circuits.

2. What does NW16 mean?

NW16 identifies the 1600 A frame class in the Masterpact NW family. The actual operating current and trip settings depend on the installed trip unit and rating configuration.

3. What is the rated current of the NW16N2?

The NW16 frame class is associated with a 1600 A frame rating. The actual trip rating should be confirmed from the rating plug, trip unit, and product nameplate.

4. What is the breaking capacity of this circuit breaker?

Breaking capacity depends on the exact breaker version, rated voltage, and applicable product standard. Check the nameplate and manufacturer documentation rather than assuming a value from the NW16 frame designation alone.

5. Is the NW16N2 a fixed or drawout circuit breaker?

The exact mounting arrangement must be confirmed from the installed unit. Masterpact NW products are available in different mounting configurations, and their cradles and connections are not automatically interchangeable.

6. What protection functions does it provide?

The available protection functions depend on the installed trip unit. Typical electronic trip-unit functions may include long-time, short-time, instantaneous, and ground-fault protection where supported by the selected configuration.

7. Can the NW16N2 be used in a main distribution board?

It may be used in a main distribution application when its electrical ratings, protection configuration, and installation arrangement meet the system requirements.

8. What should be checked before purchasing a replacement?

Confirm the complete model designation, nameplate ratings, pole count, trip-unit type, mounting arrangement, breaking capacity, cradle compatibility, and installed accessories.

9. What are the dimensions and weight of the NW16N2?

The supplied listing dimensions are 352 × 537 × 297 mm, and the supplied weight is 65 kg. Verify the actual unit and mounting configuration before planning transportation or installation.

10. Can a different Masterpact NW model replace the NW16N2?

Not automatically. Replacement requires checking electrical ratings, mechanical dimensions, trip-unit compatibility, accessories, and switchgear connections. A qualified engineer should approve the replacement before installation.

Procurement and Maintenance Recommendations

When sourcing the Schneider Electric NW16N2, begin by identifying the complete model designation and checking the product nameplate. The NW16 frame class alone is not sufficient to establish the exact electrical and mechanical configuration.

For replacement projects, request photographs of the front label, trip unit, terminals, operating mechanism, and any accessory identification labels. Confirm whether the circuit breaker is supplied as a fixed unit or with a drawout cradle, and establish which accessories are included.

For used or refurbished units, ask for condition details and available inspection or functional-test records. Verify the contact condition, mechanical operation, trip-unit configuration, and accessory functionality. For critical power systems, use qualified personnel to perform the necessary inspection and commissioning tests.

During routine maintenance, follow the manufacturer’s maintenance schedule and applicable electrical safety procedures. Inspect connections, contacts, operating mechanisms, auxiliary wiring, and protection settings. Keep maintenance records and document any changes to trip-unit settings.

For long-term equipment planning, review the availability of replacement parts and consider the compatibility of current-generation circuit breakers with the existing switchgear assembly. Any modernization project should include an engineering review of fault levels, protection coordination, mechanical installation, and system downtime.

Conclusion

The Schneider Electric NW16N2 Masterpact NW Circuit Breaker is a low-voltage air circuit breaker intended for high-current industrial power distribution applications. Its NW16 frame class is associated with a 1600 A frame rating, while its actual trip rating, breaking capacity, pole configuration, and protection functions depend on the installed configuration.

With supplied dimensions of 352 × 537 × 297 mm and a listed weight of 65 kg, the NW16N2 is a substantial switchgear component that requires appropriate mounting, electrical connections, and maintenance access.

For industrial procurement and replacement projects, verifying the complete model designation, nameplate ratings, trip unit, mounting arrangement, and accessory configuration is essential to ensure safe and reliable integration into the existing power distribution system.



Related Products

Get the latest price? We will reply as soon as possible (within 12 hours)

No:77501