The Allen-Bradley 20G1AJF370AN0NNNNN belongs to the PowerFlex 755 series and is designed for large industrial variable-speed motor applications.
With a 690 VAC three-phase input and 370 A current class, this drive is intended for large motors where compact low-power VFDs are not appropriate.
Its principal power ratings are approximately 400 kW Light-Duty, 355 kW Normal-Duty and 300 kW Heavy-Duty.
The drive is air cooled and uses a large Frame 8 construction.
The enclosed configuration provides an IP54 / NEMA Type 12 level of protection and uses an approximately 800 mm deep MCC-style cabinet.
The product is particularly suitable for centralized electrical rooms, motor-control centers and large industrial machinery.
Typical applications include large pumps, fans, blowers, conveyors, compressors, mixers, material-handling systems, process equipment and other high-power rotating machinery.
The AN0 configuration is particularly useful where local keypad operation is not required.
The drive can instead be integrated into a PLC-based control architecture through its embedded EtherNet/IP interface.
| Parameter | Specification |
|---|---|
| Brand | Allen-Bradley |
| Product Family | PowerFlex |
| Product Series | PowerFlex 755 |
| Product Type | High-Power Air-Cooled AC Drive |
| Catalog Number | 20G1AJF370AN0NNNNN |
| Input Voltage | 690 VAC |
| Input Phase | Three Phase |
| Rated Current | 370 A |
| Light-Duty Rating | 400 kW |
| Normal-Duty Rating | 355 kW |
| Heavy-Duty Rating | 300 kW |
| Frame Size | Frame 8 |
| Cooling Method | Forced Air |
| Input Type | AC Input with Precharge |
| DC Terminals | None |
| Communication | Embedded EtherNet/IP |
| Input Filtering | Filtered |
| Common-Mode Jumper | Removed |
| Dynamic Braking | None |
| Enclosure | IP54 / NEMA Type 12 |
| Cabinet Style | 800 mm Deep MCC Style |
| Local HIM | Blank / No HIM |
| Mounting | Floor-Mounted |
| Primary Function | Large Industrial Motor Speed Control |
The brand is Allen-Bradley.
The product belongs to the PowerFlex 755 series.
The PowerFlex 755 family is positioned for applications where large motor power, advanced motor control, industrial communications and flexible system integration are required.
Compared with compact PowerFlex models, the PowerFlex 755 platform is designed for substantially larger motors and more demanding industrial machinery.
The 20G1AJF370AN0NNNNN represents one of the higher-power configurations in the 690 VAC portion of the PowerFlex 755 family.
| Electrical Parameter | Specification |
|---|---|
| Catalog Number | 20G1AJF370AN0NNNNN |
| Input Voltage | 690 VAC |
| Input Phase | 3 Phase |
| Rated Output Current | 370 A |
| Light-Duty Continuous Current | Approximately 410 A |
| Light-Duty 1-Minute Current | Approximately 451 A |
| Light-Duty Power | 400 kW |
| Normal-Duty Continuous Current | 370 A |
| Normal-Duty 1-Minute Current | Approximately 407 A |
| Normal-Duty 3-Second Current | Approximately 555 A |
| Normal-Duty Power | 355 kW |
| Heavy-Duty Continuous Current | Approximately 308 A |
| Heavy-Duty 1-Minute Current | Approximately 339 A |
| Heavy-Duty 3-Second Current | Approximately 462 A |
| Heavy-Duty Power | 300 kW |
| Input Type | AC with Precharge |
| DC Terminals | None |
| Cooling | Forced Air |
| Frame | 8 |
| Filtering | Filtered |
| CM Jumper | Removed |
| Dynamic Braking | None |
| Communication | Embedded EtherNet/IP |
The 370 A rating makes this a substantial industrial drive.
For variable-torque applications, the Light-Duty capacity is approximately 400 kW.
For Normal-Duty applications, the rating is approximately 355 kW.
For Heavy-Duty applications, the rating is approximately 300 kW.
The correct rating should be selected according to the actual motor current, load profile and overload requirements.
One of the important features of the PowerFlex 755 platform is the ability to apply different duty ratings according to the characteristics of the load.
The Light-Duty rating is approximately 400 kW.
This is particularly appropriate for variable-torque loads where the motor does not continuously operate under severe overload conditions.
Typical applications include:
The Normal-Duty rating is approximately 355 kW.
This rating is appropriate for general industrial motor applications with substantial continuous loading.
Typical examples include:
The Heavy-Duty rating is approximately 300 kW.
This rating is intended for applications where greater torque demand and more demanding overload conditions are expected.
Typical applications include:
The Heavy-Duty rating should be used when the load profile actually requires the additional overload capability.
The drive’s overload capability is an important consideration when selecting it for large machinery.
| Duty | Continuous Current | 1-Minute Current | 3-Second Current | Power |
|---|---|---|---|---|
| Light Duty | Approx. 410 A | Approx. 451 A | — | 400 kW |
| Normal Duty | 370 A | Approx. 407 A | Approx. 555 A | 355 kW |
| Heavy Duty | Approx. 308 A | Approx. 339 A | Approx. 462 A | 300 kW |
Short-duration overload capability can be useful during acceleration, temporary process loading and other short-term increases in mechanical torque demand.
For large machinery, this capability should be considered together with the motor’s actual torque-speed characteristics.
| Mechanical Parameter | Specification |
|---|---|
| Catalog Number | 20G1AJF370AN0NNNNN |
| Frame Size | 8 |
| Enclosure | IP54 / NEMA Type 12 |
| Cabinet Style | MCC Style |
| Nominal Cabinet Depth | 800 mm |
| Approximate Height | 2477 mm |
| Approximate Width | 600 mm |
| Approximate Depth | 800 mm |
| Approximate Filtered Depth | Up to approximately 898 mm |
| Approximate Base Drive Weight | Approximately 644 kg |
| Cooling | Forced Air |
| Mounting | Floor-Mounted |
| Local HIM | Blank / No HIM |
| Installation Type | Industrial Electrical Room / MCC Area |
| Service Access | Front Access |
The Frame 8 enclosure is physically large.
A practical reference envelope for this class of PowerFlex 755 cabinet is approximately:
2477 mm × 600 mm × 800 mm (H × W × D).
The approximate base-drive weight is 644 kg.
If additional cabinets or option bays are included, the overall footprint and installed weight can increase.
The filtered arrangement may increase the effective depth to approximately 898 mm.
The exact mechanical drawing should be used for final installation, lifting, shipping and foundation calculations.
The 20G1AJF370AN0NNNNN is not a compact machine-mounted VFD.
It is a large floor-mounted industrial drive.
The Frame 8 construction provides sufficient space for:
This construction is appropriate for centralized electrical installations where large motor drives are grouped together.
The 690 VAC rating is one of the defining characteristics of this model.
Large industrial motors often use higher voltage levels as motor power increases.
At a given mechanical power level, higher voltage allows the operating current to remain lower than would be required at a much lower motor voltage.
This can be useful for:
The 690 VAC system should be designed as a complete electrical system, including transformer, protection, motor, cabling, grounding and drive.
The drive includes embedded EtherNet/IP.
This allows the VFD to be integrated into a networked industrial automation system.
Typical drive information can include:
This is particularly valuable in large plants where multiple drives must be monitored and controlled from a central PLC or HMI.
The drive can therefore function as a networked component rather than as an isolated motor controller.
The AN0 configuration is supplied with a blank / no HIM arrangement.
This means there is no local full-numeric operator interface included as part of this configuration.
This is often appropriate for a large automated installation where the primary control interface is provided by:
The no-HIM arrangement can also reduce unnecessary local operator hardware when the drive is installed in a controlled electrical room.
The 20G1AJF370AN0NNNNN belongs to a group of closely related 370 A configurations.
| Configuration | Catalog Number | Local HIM | Typical Control Approach |
|---|---|---|---|
| AN0 | 20G1AJF370AN0NNNNN | Blank / No HIM | Network-centric |
| JN0 | 20G1AJF370JN0NNNNN | Blank / No HIM | Network-centric |
| JN4 | 20G1AJF370JN4NNNNN | Enhanced LCD / Full Numeric | Local + Network |
The AN0 and JN0 versions are particularly similar from the standpoint of no-HIM operation.
The JN4 version is more suitable when local operator and maintenance access is important.
The drive uses AC input with precharge.
The internal precharge system controls the initial charging of the DC-link capacitors when the drive is energized.
This is especially important for a high-power drive because the DC-link capacitance is substantial.
The catalog configuration also specifies no DC terminals.
Therefore, the drive is designed around conventional AC input rather than a common DC-bus configuration.
The 20G1AJF370AN0NNNNN is supplied in a filtered configuration.
Input filtering is useful for managing electrical noise and improving compatibility with the surrounding industrial electrical system.
This can be important in plants containing:
Filtering should still be considered together with proper grounding, cable shielding and installation practices.
One of the configuration details that distinguishes this model is the CM jumper removed configuration.
This affects the drive’s common-mode electrical relationship with ground.
It should be considered together with:
The CM jumper configuration should not be changed casually after installation.
It should be selected according to the electrical system and the manufacturer’s installation requirements.
The 20G1AJF370AN0NNNNN is configured with no dynamic-braking transistor.
This is important for applications with significant regenerative energy.
Potentially demanding applications include:
If the process requires fast deceleration or significant regenerative energy absorption, the complete braking system should be evaluated before selecting the final drive configuration.
The drive uses IP54 / NEMA Type 12 enclosure protection.
This is suitable for many industrial electrical rooms and enclosed MCC environments.
The enclosure can help protect the internal drive components from:
Typical installation locations include:
Severe corrosive or conductive environments require additional engineering evaluation.
The 370 A power level results in substantial heat generation.
The drive therefore uses forced-air cooling.
Cooling performance depends on:
Large rooms containing several PowerFlex 755 drives may require substantial HVAC capacity.
Cooling-fan inspection should be included in preventive maintenance.
Large pumps are among the most suitable applications for this drive.
Variable-speed operation can allow pump speed to be adjusted according to process demand.
Potential applications include:
The 400 kW Light-Duty rating is particularly relevant to suitable variable-torque pump applications.
Large fans can benefit from variable-speed control.
Potential applications include:
For these applications, the Light-Duty rating can provide substantial available motor power.
Industrial blowers can require high motor power while operating over a variable airflow range.
The drive can regulate motor speed according to process demand.
Potential applications include:
The actual duty rating should be selected according to the blower’s torque-speed characteristics.
The drive is also suitable for large conveyor systems.
Conveyor motors can require considerable torque during startup.
Controlled acceleration can help reduce mechanical shock.
Potential benefits include reduced stress on:
Applications include mining, aggregate, cement, bulk-material handling and industrial production.
The 690 VAC high-power platform makes this drive appropriate for many large mining applications.
Potential equipment includes:
Mining environments require particular attention to dust, vibration, temperature and maintenance access.
The IP54 / NEMA Type 12 enclosure is useful for an appropriately designed electrical-room installation.
Large material-handling equipment often requires high-power motors.
Potential applications include:
The variable-speed capability can provide controlled acceleration and process-speed regulation.
Large industrial compressors can use motors in the hundreds-of-kilowatts range.
The 20G1AJF370AN0NNNNN provides a high-power platform for compressor systems where variable-speed control is appropriate.
Potential applications include:
The compressor manufacturer’s speed and torque requirements should always be considered.
Large mixers can require significant torque.
The PowerFlex 755 can provide controlled acceleration and variable-speed operation.
Potential applications include:
For demanding constant-torque applications, the Heavy-Duty rating should be used when selecting the drive.
The drive can be used for large process machines requiring variable-speed control.
Potential applications include:
EtherNet/IP allows the drive to exchange control and status information with the rest of the automation system.
The drive is also suitable for large utility systems.
Examples include:
The enclosed cabinet is particularly appropriate when the drive is installed inside a dedicated electrical room.
The 690 VAC platform allows the drive to serve large motor systems while maintaining a practical current level for the power rating.
The 370 A output rating provides substantial capacity for large industrial motors.
This provides significant capacity for variable-torque applications.
The Normal-Duty rating provides a strong fit for general large industrial machinery.
This provides substantial capacity for more demanding constant-torque applications.
Integrated communication simplifies integration into PLC-based industrial automation.
The enclosed design provides useful industrial environmental protection.
The Frame 8 architecture is designed for large industrial power levels.
The AN0 configuration is well suited to centralized network-controlled installations.
The filtered configuration helps address electrical-noise requirements within the complete installation.
The AN0 configuration is particularly attractive when the drive is installed in a centralized electrical room.
A typical system can use:
PLC → EtherNet/IP → PowerFlex 755 → 690 VAC Motor
The operator may interact with the motor through a central HMI rather than through a local drive keypad.
This architecture is especially useful when a facility contains many large motors.
The central control system can provide:
The networked architecture provides useful remote information.
Maintenance personnel can monitor:
This can reduce the need for technicians to physically access the drive for every routine status check.
For local maintenance access, a related JN4 configuration can be considered.
The following models are closely related PowerFlex 755 configurations within the 690 VAC high-power family.
| Model | Voltage | Current | Light Duty | Normal Duty | Heavy Duty | Frame | Enclosure |
|---|---|---|---|---|---|---|---|
| 20G1AJF265AN0NNNNN | 690 VAC | 265 A | 315 kW | 250 kW | 200 kW | 8 | IP54 / Type 12 |
| 20G1AJF330AN0NNNNN | 690 VAC | 330 A | 355 kW | 315 kW | 250 kW | 8 | IP54 / Type 12 |
| 20G1AJF370AN0NNNNN | 690 VAC | 370 A | 400 kW | 355 kW | 300 kW | 8 | IP54 / Type 12 |
| 20G1AJF415AN0NNNNN | 690 VAC | 415 A | 450 kW | 400 kW | 355 kW | 8 | IP54 / Type 12 |
| 20G1AJF460AN0NNNNN | 690 VAC | 460 A | 500 kW | 450 kW | 375 kW | 8 | IP54 / Type 12 |
These models form a useful capacity progression.
The 265 A version is the lower-capacity alternative.
The 330 A version is one step below the target model.
The 415 A and 460 A versions provide progressively more current and power capacity.
| Model | Continuous Current | Light Duty | Normal Duty | Heavy Duty |
|---|---|---|---|---|
| 20G1AJF265AN0NNNNN | 265 A | 315 kW | 250 kW | 200 kW |
| 20G1AJF330AN0NNNNN | 330 A | 355 kW | 315 kW | 250 kW |
| 20G1AJF370AN0NNNNN | 370 A | 400 kW | 355 kW | 300 kW |
| 20G1AJF415AN0NNNNN | 415 A | 450 kW | 400 kW | 355 kW |
| 20G1AJF460AN0NNNNN | 460 A | 500 kW | 450 kW | 375 kW |
The 370 A model is positioned between the 330 A and 415 A versions.
This makes it a useful selection when a 330 A drive does not provide enough current but a 415 A drive would be unnecessarily large.
If local operator access is required, JN4 versions provide a useful alternative.
| Model | Voltage | Current | Light Duty | Normal Duty | Heavy Duty | Local HIM |
|---|---|---|---|---|---|---|
| 20G1AJF265JN4NNNNN | 690 VAC | 265 A | 315 kW | 250 kW | 200 kW | Enhanced LCD / Full Numeric |
| 20G1AJF330JN4NNNNN | 690 VAC | 330 A | 355 kW | 315 kW | 250 kW | Enhanced LCD / Full Numeric |
| 20G1AJF370JN4NNNNN | 690 VAC | 370 A | 400 kW | 355 kW | 300 kW | Enhanced LCD / Full Numeric |
| 20G1AJF415JN4NNNNN | 690 VAC | 415 A | 450 kW | 400 kW | 355 kW | Enhanced LCD / Full Numeric |
| 20G1AJF460JN4NNNNN | 690 VAC | 460 A | 500 kW | 450 kW | 375 kW | Enhanced LCD / Full Numeric |
The JN4 configuration is useful when local commissioning and maintenance are important.
The AN0 configuration is more appropriate when the installation is designed around centralized control and does not require a local HIM.
| Model | Approx. Height | Approx. Width | Approx. Depth | Approx. Weight | Frame |
|---|---|---|---|---|---|
| 20G1AJF265AN0NNNNN | 2477 mm class | 600 mm class | 800 mm class | 644 kg class | 8 |
| 20G1AJF330AN0NNNNN | 2477 mm class | 600 mm class | 800 mm class | 644 kg class | 8 |
| 20G1AJF370AN0NNNNN | 2477 mm class | 600 mm class | 800 mm class | 644 kg class | 8 |
| 20G1AJF415AN0NNNNN | 2477 mm class | 600 mm class | 800 mm class | 644 kg class | 8 |
| 20G1AJF460AN0NNNNN | 2477 mm class | 600 mm class | 800 mm class | 644 kg class | 8 |
These figures represent the common Frame 8 cabinet class.
The actual final equipment dimensions and weight can change with options and cabinet arrangements.
| Model | Series | Voltage | Current | Power Rating | Frame | Enclosure / Construction | Typical Application |
|---|---|---|---|---|---|---|---|
| 25B-D030N114 | PowerFlex 525 | 380–480 VAC | 30 A | 20 HP ND / 15 HP HD | D | IP20 | Compact machine control |
| 25C-D030N114 | PowerFlex 527 | 380–480 VAC | 30 A | 20 HP ND / 15 HP HD | D | IP20 | Networked machine control |
| 20F1AND302JA0NNNNN | PowerFlex 753 | 480 VAC | 302 A | 250 HP ND / 200 HP HD | 7 | Industrial drive | Large industrial motors |
| 20G1AJE460JN4NNNNN | PowerFlex 755 | 600 VAC | 460 A | 500 HP class | 8 | IP54 / Type 12 | Large 600 VAC motors |
| 20G1AJF415JN4NNNNN | PowerFlex 755 | 690 VAC | 415 A | 450 kW LD / 400 kW ND / 355 kW HD | 8 | IP54 / Type 12 | High-power 690 VAC motors |
These five models cover different sections of the Allen-Bradley drive portfolio.
The 25B-D030N114 is aimed at compact machine applications.
The 25C-D030N114 is another compact solution with strong network-oriented machine-control capabilities.
The 20F1AND302JA0NNNNN provides a comparison with the PowerFlex 753 platform at 480 VAC.
The 20G1AJE460JN4NNNNN is useful for large 600 VAC motor systems.
The 20G1AJF415JN4NNNNN is one of the closest alternatives when the motor is in the 690 VAC high-power range but requires more than approximately 370 A.
| Model | Primary Application | Main Advantage | Relative Size |
|---|---|---|---|
| 25B-D030N114 | Compact machinery | Compact drive and integrated communications | Small |
| 25C-D030N114 | Automated machinery | Network-centric machine control | Small |
| 20F1AND302JA0NNNNN | Large industrial equipment | High-power 480 VAC operation | Large |
| 20G1AJE460JN4NNNNN | Large 600 VAC motors | High-current PowerFlex 755 | Very Large |
| 20G1AJF415JN4NNNNN | Large 690 VAC motors | Higher current than 370 A class | Very Large |
| Parameter | 20G1AJF370AN0NNNNN | 20G1AJF330AN0NNNNN |
|---|---|---|
| Voltage | 690 VAC | 690 VAC |
| Current | 370 A | 330 A |
| Light Duty | 400 kW | 355 kW |
| Normal Duty | 355 kW | 315 kW |
| Heavy Duty | 300 kW | 250 kW |
| Frame | 8 | 8 |
| Enclosure | IP54 / Type 12 | IP54 / Type 12 |
| Cooling | Forced Air | Forced Air |
| EtherNet/IP | Yes | Yes |
| Local HIM | No | No |
| Main Difference | Higher capacity | Lower capacity |
The 370 A version provides a useful additional operating margin compared with the 330 A model.
It is particularly useful when the motor current is approaching the upper range of the 330 A configuration.
| Parameter | 20G1AJF370AN0NNNNN | 20G1AJF415AN0NNNNN |
|---|---|---|
| Voltage | 690 VAC | 690 VAC |
| Current | 370 A | 415 A |
| Light Duty | 400 kW | 450 kW |
| Normal Duty | 355 kW | 400 kW |
| Heavy Duty | 300 kW | 355 kW |
| Frame | 8 | 8 |
| Enclosure | IP54 / Type 12 | IP54 / Type 12 |
| Cooling | Forced Air | Forced Air |
| EtherNet/IP | Yes | Yes |
| Local HIM | No | No |
| Main Difference | Lower capacity | Higher capacity |
The 415 A version is a logical alternative when the motor requires more than the 370 A class can comfortably provide.
| Feature | 20G1AJF370AN0NNNNN | 20G1AJF370JN4NNNNN |
|---|---|---|
| Voltage | 690 VAC | 690 VAC |
| Current | 370 A | 370 A |
| Light Duty | 400 kW | 400 kW |
| Normal Duty | 355 kW | 355 kW |
| Heavy Duty | 300 kW | 300 kW |
| Frame | 8 | 8 |
| Enclosure | IP54 / Type 12 | IP54 / Type 12 |
| Cooling | Forced Air | Forced Air |
| EtherNet/IP | Yes | Yes |
| Input | AC with Precharge | AC with Precharge |
| DC Terminals | None | None |
| Dynamic Braking | None | None |
| Local HIM | Blank / No HIM | Enhanced LCD / Full Numeric |
| Primary Advantage | Centralized/network control | Local + network control |
If the installation is controlled entirely through a PLC and HMI, the AN0 version can be a practical configuration.
If local operator access is important, the JN4 version is generally the more convenient choice.
The motor should be selected based on its actual nameplate data.
Important values include:
The motor current is especially important.
A motor’s kW rating alone does not always provide enough information to select a large industrial VFD.
A 690 VAC, 370 A drive requires a properly engineered electrical distribution system.
The installation should consider:
The drive should therefore be selected as part of the complete motor-control system.
Thermal management is particularly important at this power level.
The drive can generate considerable heat during operation.
The electrical room should have enough capacity to remove the heat produced by the drive.
Important factors include:
If several large drives are installed in the same room, the combined thermal load can be substantial.
A suitable preventive-maintenance program should include regular checks of:
| Maintenance Item | Main Inspection |
|---|---|
| Cooling Fans | Operation, noise and airflow |
| Air Passages | Dust and obstruction |
| Cabinet | Cleanliness |
| Power Terminals | Connection condition |
| Grounding | Ground integrity |
| Motor Cables | Insulation and termination |
| Network | EtherNet/IP communication |
| Fault History | Repeated faults |
| Motor Current | Abnormal changes |
| Cabinet Temperature | Overheating |
| Enclosure | Physical condition and seals |
| Internal Components | Thermal or mechanical damage |
The maintenance interval should be adapted to the actual application.
Mining, cement, aggregate and dusty industrial facilities generally require more frequent inspection than clean electrical rooms.
The large Frame 8 cabinet requires careful planning.
A preliminary installation envelope of approximately:
2477 mm H × 600 mm W × 800 mm D
should be considered.
The approximate base-drive weight is:
644 kg
The installation area should provide enough space for:
The floor must be capable of supporting the equipment.
The drive can be considered for:
Large conveyors, pumps, fans and material-handling systems.
Fans, conveyors, mixers and process equipment.
Large pumps, blowers and circulation systems.
Pumps, mixers, compressors and process equipment.
Large fans, pumps, rollers and production machinery.
Large production lines and rotating machinery.
Large pumps, fans and auxiliary equipment.
Conveyors, feeders and transfer systems.
The 20G1AJF370AN0NNNNN combines a high-voltage motor-control architecture with substantial output capacity.
Its major advantages include:
This makes it especially attractive for large networked motor-control systems.
| Parameter | Specification |
|---|---|
| Brand | Allen-Bradley |
| Series | PowerFlex 755 |
| Model | 20G1AJF370AN0NNNNN |
| Product Type | High-Power Air-Cooled AC Drive |
| Input Voltage | 690 VAC |
| Input Phase | Three Phase |
| Rated Current | 370 A |
| Light-Duty Rating | 400 kW |
| Normal-Duty Rating | 355 kW |
| Heavy-Duty Rating | 300 kW |
| Light-Duty Current | Approx. 410 A continuous |
| Light-Duty 1-Minute Current | Approx. 451 A |
| Normal-Duty Current | 370 A continuous |
| Normal-Duty 1-Minute Current | Approx. 407 A |
| Normal-Duty 3-Second Current | Approx. 555 A |
| Heavy-Duty Current | Approx. 308 A continuous |
| Heavy-Duty 1-Minute Current | Approx. 339 A |
| Heavy-Duty 3-Second Current | Approx. 462 A |
| Frame | 8 |
| Cooling | Forced Air |
| Enclosure | IP54 / NEMA Type 12 |
| Cabinet Depth | 800 mm |
| Approx. Height | 2477 mm |
| Approx. Width | 600 mm |
| Approx. Depth | 800 mm |
| Approx. Filtered Depth | 898 mm |
| Approx. Base Weight | 644 kg |
| Input Configuration | AC Input with Precharge |
| DC Terminals | None |
| Communication | Embedded EtherNet/IP |
| Filtering | Filtered |
| CM Jumper | Removed |
| Dynamic Braking | None |
| Local HIM | Blank / No HIM |
| Mounting | Floor-Mounted |
| Primary Applications | Pumps, fans, blowers, conveyors, compressors, mixers, process machinery |
| Typical Installation | Industrial Electrical Room / MCC |
The Allen-Bradley 20G1AJF370AN0NNNNN is a strong choice for large industrial motor applications where the system requires a 690 VAC, 370 A PowerFlex 755 platform.
Its 400 kW Light-Duty rating makes it especially suitable for large variable-torque applications such as centrifugal pumps and fans.
The 355 kW Normal-Duty rating provides a strong capacity level for general industrial motor systems.
The 300 kW Heavy-Duty rating makes it suitable for demanding constant-torque applications when the motor and load fall within the applicable rating.
The IP54 / NEMA Type 12 Frame 8 enclosure is appropriate for many industrial electrical-room installations.
The embedded EtherNet/IP interface makes the drive particularly suitable for centralized PLC-based automation.
The AN0 no-HIM configuration is a practical choice when operators and maintenance personnel primarily work through a centralized HMI, PLC or industrial network.
If local operator access is required, the related 20G1AJF370JN4NNNNN configuration is a logical alternative.
If the motor requires less capacity, the 20G1AJF330AN0NNNNN can be considered.
If the motor requires more current, the 20G1AJF415AN0NNNNN or 20G1AJF460AN0NNNNN can provide additional capacity.
One lifecycle point is important for procurement: the exact 20G1AJF370AN0NNNNN catalog number is a discontinued configuration, with the 20G1AJF370JN0NNNNN identified as its direct replacement. Therefore, for a new project, the replacement catalog number should be evaluated rather than treating the AN0 version as a current new-product selection.