• Siemens 6ES7132-6MD00-0BB1 SIMATIC ET 200SP Digital Output Module
  • Siemens 6ES7132-6MD00-0BB1 SIMATIC ET 200SP Digital Output Module
  • Siemens 6ES7132-6MD00-0BB1 SIMATIC ET 200SP Digital Output Module
  • Siemens 6ES7132-6MD00-0BB1 SIMATIC ET 200SP Digital Output Module
Product Overview The Siemens 6ES7132-6MD00-0BB1 is a relay-based digital output module for the SIMATIC ET 200SP distributed I/O system. Its official product designation is RQ 4x120VDC-230VAC/5A NO MA ST……
Siemens 6ES7132-6MD00-0BB1 SIMATIC ET 200SP Digital Output Module
  • Siemens
  • 6ES7132-6MD00-0BB1
  • Digital Output Module
  • Germany
  • 20 × 73 × 58 mm
  • 0.054 kg
  • Xiamen, China
  • New & In Stock
  • T/T, PayPal, Western Union
  • 1 Year
  • 1-3 Working Days
  • DHL, UPS, TNT, FedEx and EMS.
  • 24-Hour Service
  • COO
  • 22

Our advantage

Siemens 6ES7132-6MD00-0BB1 SIMATIC ET 200SP Digital Output Module

Global Logistics

We have a 10-year logistics and express cooperation agreement, so our products can be shipped to any place in the world.

Siemens 6ES7132-6MD00-0BB1 SIMATIC ET 200SP Digital Output Module

Brand new and original

Our products are imported in bulk from the place of origin. Because of the cooperative relationship, our products are all original and 100% new.

Siemens 6ES7132-6MD00-0BB1 SIMATIC ET 200SP Digital Output Module

24-hour service

We provide 7*24 hours service to our customers. We will be there whenever you need us.

Siemens 6ES7132-6MD00-0BB1 SIMATIC ET 200SP Digital Output Module

Price advantage

All our products are priced very favorably because we have our own warehouse and supply.


Company Information
E-mail [email protected]
Mobile +8615980777398
Whatsapp +8615980777398
WeChat 15980777398

Product Overview

The Siemens 6ES7132-6MD00-0BB1 is a relay-based digital output module for the SIMATIC ET 200SP distributed I/O system. Its official product designation is RQ 4x120VDC-230VAC/5A NO MA ST, identifying a four-channel relay output module with normally open contacts and manual operation capability.

The module converts digital control commands from a SIMATIC PLC into switching actions for external electrical circuits. Each of its four relay channels provides a normally open contact, allowing the controller to operate contactors, solenoid valves, auxiliary relays, and other compatible industrial loads.

A distinguishing feature of the 6ES7132-6MD00-0BB1 is its manual operation function. In addition to controller-based switching, the module supports manual operation of its relay outputs, which can be useful during commissioning, maintenance, and functional testing. This capability differentiates it from standard relay output variants without manual operation.

The module supports switching voltages from 24 to 120 V DC and 24 to 230 V AC. Each channel supports a maximum switching current of 5 A for resistive loads and 2 A for inductive loads, subject to the specified operating conditions.

As part of the ET 200SP platform, the module communicates through the station backplane bus and can be installed on compatible BU type B0 or B1 BaseUnits. It also supports substitute values, supply voltage monitoring, and module diagnostics.

The 6ES7132-6MD00-0BB1 is suitable for distributed automation installations where relay-based load switching and local manual operation are both required.


Technical Specifications

Parameter Specification
Manufacturer Siemens
Model 6ES7132-6MD00-0BB1
Product Series SIMATIC ET 200SP
Product Type Digital Output Module
Official Product Designation RQ 4x120VDC-230VAC/5A NO MA ST
Module Type Relay Output Module
Number of Digital Outputs 4
Output Type Relay
Contact Configuration Normally Open (NO)
Manual Operation Yes
Rated Supply Voltage 24 V DC
Permissible Supply Voltage 19.2–28.8 V DC
Rated Switching Voltage (DC) 24–120 V DC
Rated Switching Voltage (AC) 24–230 V AC
Maximum Switching Current (Resistive) 5 A per Channel
Maximum Switching Current (Inductive) 2 A per Channel
Maximum Module Output Current 20 A
Maximum Switching Frequency (Resistive Load) 2 Hz
Maximum Switching Frequency (Inductive Load) 0.5 Hz
Maximum Switching Frequency (Lamp Load) 2 Hz
Minimum Switching Current 100 mA at 5 V DC
Relay Coil Voltage 24 V DC
Maximum Relay Coil Current 40 mA for All Relays
Maximum Current Consumption 100 mA without Load
Typical Power Loss 1.5 W
Number of Switching Cycles Up to 7,000,000
External Relay Protection Maximum 6 A Fast-Acting Miniature Fuse
Compatible BaseUnit BU Type B0 / B1
Color Code CC40
Substitute Value Output Yes
Supply Voltage Monitoring Yes
Diagnostic Alarm Yes
Channel Status Display Green LED
Module Status Display Green/Red DIAG LED
Configuration Software STEP 7 V13 SP1 or Higher
PROFIBUS Configuration GSD Revision 3 and Higher
PROFINET Configuration GSDML V2.3
Short-Circuit Protection No
Safety Function Suitability No
Protection Rating IP20
Operating Temperature -30 to +60°C (Horizontal Installation)
Dimensions 20 × 73 × 58 mm
Weight 0.054 kg

Product Features

  • Four Relay Output Channels: Provides four independent relay switching channels for controlling external electrical equipment.
  • Manual Operation Capability: Supports manual operation of relay outputs for commissioning and maintenance activities.
  • Normally Open Contacts: Each channel uses a normally open relay contact that closes when activated.
  • Electrical Isolation: Provides isolation between individual output channels and between the output circuits and the backplane bus.
  • Wide Switching Voltage Range: Supports 24–120 V DC and 24–230 V AC external switching circuits.
  • 5 A Resistive Load Capacity: Supports up to 5 A per channel for specified resistive loads.
  • Inductive Load Switching: Supports inductive loads up to 2 A per channel under specified operating conditions.
  • Substitute Value Function: Allows configured substitute output values under supported operating conditions.
  • Integrated Diagnostics: Provides supply voltage monitoring, diagnostic alarms, and module status indication.
  • Flexible BaseUnit Compatibility: Supports BU type B0 and B1 BaseUnits for different ET 200SP connection arrangements.

Product Working Principle

The Siemens 6ES7132-6MD00-0BB1 converts digital output commands into relay switching operations through four mechanical relay channels.

During normal automatic operation, the SIMATIC controller sends output commands through the ET 200SP interface module. These commands travel across the station backplane bus to the relay output module.

When an output is activated, the corresponding relay coil is energized using the 24 V DC supply. The electromagnetic action closes the normally open contact, completing the external electrical circuit. When the output is deactivated, the relay releases and the contact returns to its normally open state.

A simplified control arrangement is:

SIMATIC PLC → ET 200SP Interface Module → Backplane Bus → 6ES7132-6MD00-0BB1 → Relay Contacts → External Loads

The module also supports manual operation. This provides an additional operating method for relay switching during service and commissioning procedures, reducing dependence on controller commands for supported manual operations.

Each output channel is electrically isolated from the other channels. This arrangement allows separate external circuits to be switched while maintaining the specified electrical separation.

The module supports resistive switching currents up to 5 A and inductive switching currents up to 2 A per channel. Inductive loads require particular attention because the interruption of current can generate voltage transients. Suitable external suppression and protection should be applied according to the connected equipment.

The module continuously monitors its supply voltage and provides diagnostic information through its PWR and DIAG indicators. These functions help maintenance personnel identify supply-related problems and module operating conditions.


Role in Siemens SIMATIC ET 200SP Control Architecture

Within the SIMATIC ET 200SP architecture, the 6ES7132-6MD00-0BB1 serves as a relay output interface between the PLC control program and external field circuits.

The controller executes the automation logic and transfers output commands to the distributed I/O station through the communication interface. The backplane bus distributes these commands to the relay module, which operates the corresponding output contacts.

The manual operation capability adds another operating method for maintenance and commissioning activities.

A typical control arrangement is:

SIMATIC PLC → ET 200SP Interface Module → Backplane Bus → 6ES7132-6MD00-0BB1 → External Electrical Equipment

System Component Function
SIMATIC S7-1200 / S7-1500 PLC Executes automation logic
ET 200SP Interface Module Connects the distributed I/O station to the controller network
6ES7132-6MD00-0BB1 Provides four relay outputs with manual operation
ET 200SP BU Type B0 Provides the three-wire connection arrangement
ET 200SP BU Type B1 Provides the two-wire connection arrangement
24 V DC Power Supply Supplies the module and relay coils
Contactors Switch external power circuits
Solenoid Valves Receive relay-based switching commands
Auxiliary Relays Interface with external control circuits
Field Wiring Connects the relay contacts to external loads

This arrangement is useful in control cabinets where manual switching capability is required alongside PLC-based operation.


Industrial Applications

The 6ES7132-6MD00-0BB1 is suitable for industrial installations requiring relay-based switching, isolated output channels, and manual operation capability.

Industrial Application Typical Use
Manufacturing Automation Switching contactors and auxiliary electrical equipment
Packaging Machinery Operating machine actuators and control circuits
Conveyor Systems Switching motor contactor circuits
Material Handling Controlling external switching devices
Water Treatment Operating pumps and auxiliary electrical equipment
HVAC Automation Switching fans, dampers, and control relays
Chemical Processing Controlling external electrical circuits
Power Distribution Switching auxiliary control equipment
Industrial Assembly Lines Operating machine interlocks and signaling devices
Building Automation Switching compatible electrical loads

Installation and Maintenance

  1. Verify the Module Number: Confirm that 6ES7132-6MD00-0BB1 matches the project hardware configuration and required relay output functions.
  2. Check BaseUnit Compatibility: Select a compatible BU type B0 or B1 BaseUnit according to the required wiring arrangement.
  3. Inspect the Module: Check the housing, connection interfaces, and mechanical coding elements for visible damage.
  4. Isolate the Power Supply: Disconnect the relevant power supplies before installing or removing the module.
  5. Mount the Module: Install the module on the designated ET 200SP BaseUnit and ensure that it is securely seated.
  6. Verify Supply Voltage: Confirm that the 24 V DC supply is within the specified 19.2–28.8 V DC operating range.
  7. Check Relay Output Wiring: Connect each normally open relay contact according to the Siemens wiring diagram and external circuit requirements.
  8. Verify Electrical Isolation: Maintain the specified separation between output circuits and avoid unintended connections between independent field circuits.
  9. Check Load Ratings: Ensure that resistive loads do not exceed 5 A and inductive loads do not exceed 2 A per channel.
  10. Install External Protection: Provide the specified fast-acting miniature fuse protection, with a maximum tripping current of 6 A, for the relay output circuits.
  11. Configure Manual Operation: Check the module’s manual operation arrangements and follow the Siemens operating instructions before using manual switching during commissioning or maintenance.
  12. Perform Functional Testing: Test all four relay outputs, verify automatic and supported manual operation, inspect PWR and DIAG indicators, and record the commissioning results.

During routine maintenance, inspect the terminal connections, relay contact performance, external fuse protection, and diagnostic indications. When controlling inductive loads, verify that suitable suppression measures are installed to reduce switching transients.


Compatible System Components

Component Function
Siemens 6ES7132-6MD00-0BB1 Four-Channel Relay Output Module with Manual Operation
Siemens ET 200SP BU Type B0 Compatible Three-Wire BaseUnit
Siemens ET 200SP BU Type B1 Compatible Two-Wire BaseUnit
Siemens ET 200SP Interface Module Distributed I/O Communication
Siemens 6ES7131 Series ET 200SP Digital Input Modules
Siemens 6ES7132 Series ET 200SP Digital Output Modules
Siemens 6ES7134 Series ET 200SP Analog Input Modules
Siemens 6ES7135 Series ET 200SP Analog Output Modules
Siemens SITOP Power Supply 24 V DC Power Supply

Recommended Related Models

Model / Product Product Type Typical Application
Siemens 6ES7132-6HD01-0BB1 Digital Output Module Four-channel ET 200SP relay outputs
Siemens 6ES7132-6HD00-0BB1 Digital Output Module ET 200SP normally open relay outputs
Siemens 6ES7132-6HC50-0BU0 Digital Output Module Three-channel isolated relay outputs
Siemens 6ES7132-6HC70-0BU0 Digital Output Module Three-channel non-isolated relay outputs
Siemens 6ES7132-6BH00-0AA0 Digital Output Module ET 200SP transistor outputs
Siemens 6ES7132-6GD51-0BA0 Signal Relay Module ET 200SP relay switching

Key Advantages

  • Four independent relay output channels.
  • Integrated manual operation capability.
  • Normally open relay contacts.
  • Electrical isolation between output channels.
  • Supports AC and DC switching applications.
  • Maximum 5 A resistive switching current per channel.
  • Compatible with BU type B0 and B1 BaseUnits.
  • Substitute value output and supply voltage diagnostics.
  • Suitable for commissioning and industrial maintenance applications.

Technical FAQs

1. What does MA mean in the product designation RQ 4x120VDC-230VAC/5A NO MA ST?

MA identifies the manual operation version of the relay output module. Unlike standard variants without this designation, the 6ES7132-6MD00-0BB1 supports manual operation in addition to PLC-controlled switching.

2. How many relay outputs does the 6ES7132-6MD00-0BB1 provide?

The module provides four relay output channels. Each channel uses a normally open contact and supports switching external AC or DC circuits within the specified voltage and current limits.

3. What is the difference between the 6ES7132-6MD00-0BB1 and 6ES7132-6HD01-0BB1?

Both are four-channel ET 200SP relay output modules with normally open contacts. The 6ES7132-6MD00-0BB1 includes manual operation capability, while the 6ES7132-6HD01-0BB1 is a standard relay output version without the MA designation.

4. Which BaseUnit should be used with the 6ES7132-6MD00-0BB1?

Siemens specifies BU type B0 and B1 BaseUnits. B0 supports the three-wire connection arrangement, while B1 supports the two-wire arrangement. The selection should match the wiring design of the ET 200SP station.



Related Products

Get the latest price? We will reply as soon as possible (within 12 hours)

No:77501