• GE 8913-PS-AC Power Supply
  • GE 8913-PS-AC Power Supply
  • GE 8913-PS-AC Power Supply
  • GE 8913-PS-AC Power Supply
Product Overview The GE 8913-PS-AC Power Supply is an industrial dual-output AC power supply module designed for process control and distributed I/O systems. It is associated with the MTL8000 and PAC800……
GE 8913-PS-AC Power Supply
  • GE
  • 8913-PS-AC
  • Power Supply
  • USA
  • 154 x 36 x 120 mm
  • 0.78 kg
  • Xiamen, China
  • New & In Stock
  • T/T, PayPal, Western Union
  • 1 Year
  • 1-3 Working Days
  • DHL, UPS, TNT, FedEx and EMS.
  • 24-Hour Service
  • COO
  • 54

Our advantage

GE 8913-PS-AC Power Supply

Global Logistics

We have a 10-year logistics and express cooperation agreement, so our products can be shipped to any place in the world.

GE 8913-PS-AC Power Supply

Brand new and original

Our products are imported in bulk from the place of origin. Because of the cooperative relationship, our products are all original and 100% new.

GE 8913-PS-AC Power Supply

24-hour service

We provide 7*24 hours service to our customers. We will be there whenever you need us.

GE 8913-PS-AC Power Supply

Price advantage

All our products are priced very favorably because we have our own warehouse and supply.


Company Information
E-mail [email protected]
Mobile +8615980777398
Whatsapp +8615980777398
WeChat 15980777398

Product Overview

The GE 8913-PS-AC Power Supply is an industrial dual-output AC power supply module designed for process control and distributed I/O systems. It is associated with the MTL8000 and PAC8000 process I/O platforms and is used to provide separate power rails for system electronics and field instrumentation.

This module converts a wide-range AC input into two regulated DC outputs. One output supplies system power, while the other provides auxiliary power for field devices. Separating these power functions helps support the electrical requirements of process automation installations.

The 8913-PS-AC accepts an AC input voltage range of 85–264 V AC and provides two nominal 5 A outputs: approximately 12 V DC for system power and 24 V DC for auxiliary field power. Its dual-output design makes it suitable for distributed control installations where controller electronics and field instrumentation require different supply voltages.

The module also supports redundancy arrangements when paired with a second compatible power supply. Its 12 V output incorporates load-sharing capability, allowing the system design to support a redundant power arrangement under the manufacturer’s specified conditions.

The 8913-PS-AC is associated with industrial applications that require reliable power distribution, including process control, remote I/O, instrumentation, and hazardous-area installations. Its electrical characteristics and mounting requirements should be checked against the specific PAC8000 or MTL8000 system before installation.

Technical Specifications

Parameter Specification
Brand / Product Identification GE / MTL / PAC8000
Model 8913-PS-AC
Product Type Dual-Output AC Power Supply
System Compatibility MTL8000 / PAC8000 Process I/O
Input Voltage (AC) 85–264 V AC
Input Frequency 47–65 Hz
DC Input Capability 90–264 V DC, according to the product datasheet
System Power Output Approximately 12 V DC
System Power Output Current 5 A nominal
Field Power Output Approximately 24 V DC
Field Power Output Current 5 A nominal
Output 1 Voltage 11.95 V DC ±5%
Output 2 Voltage 24.7 V DC ±10%
Redundancy Supports specified parallel redundancy arrangements
Load Sharing Internal load-sharing provision on the 12 V output
Input Protection Internal slow-blow fuse and voltage-dependent resistor
Thermal Protection Output power reduction under thermal overload conditions
Supply Status LED status indication
Input-to-Output Isolation 2800 V DC
Typical Hold-Up Time 15 ms at full rated load
Operating Temperature -40°C to +70°C
Maximum Operating Case Temperature +80°C
Dimensions Provided 154 × 36 × 120 mm
Weight Provided 0.78 kg
Typical Mounting DIN rail or compatible system mounting arrangement
Application Industrial process control and distributed I/O power

Note: The dimensions above are the supplied listing values. The published MTL datasheet gives different mechanical dimensions of approximately 103 × 138 × 113.6 mm and a net weight of approximately 0.75 kg. Confirm the exact mechanical version before panel design or shipment.

Function and Working Principle

The 8913-PS-AC supplies the DC power required by process I/O electronics and connected field instrumentation. Its internal conversion circuitry transforms the incoming AC supply into two regulated DC outputs.

1. AC-to-DC Power Conversion

The module accepts a wide AC input range from 85 V to 264 V AC. This allows it to operate across different industrial supply conditions without requiring a narrow, fixed input voltage.

The internal power-conversion circuit regulates the incoming electrical energy and provides DC outputs for connected system components.

Stable DC power is important for process automation because controllers, I/O modules, and field instruments depend on consistent electrical supply conditions.

2. Dual-Voltage Output

A key characteristic of the 8913-PS-AC is its dual-output design.

The approximately 12 V DC output is intended for system power, including compatible internal electronics. The approximately 24 V DC output provides auxiliary power for field-side instrumentation and other supported devices.

Separating these power rails allows the system designer to match the supply voltage to the requirements of different equipment groups.

The two outputs must be loaded within their individual current limits. The available current can also be affected by ambient temperature and the manufacturer’s output derating requirements.

3. Redundant Power Supply Operation

Industrial process control systems may require continuous operation even if one power supply becomes unavailable.

The 8913-PS-AC supports redundancy arrangements when paired with a second compatible unit. Its 12 V output includes an internal load-sharing provision that supports the specified parallel configuration.

Redundant operation requires correct system wiring, compatible mounting hardware, suitable load distribution, and appropriate monitoring. The 24 V output should not be assumed to support identical load-sharing behavior without checking the manufacturer’s documentation.

4. Power-Failure Signalling

The module includes a power-failure signalling function associated with its system output. This allows compatible monitoring equipment to detect a supply abnormality and respond through the wider control architecture.

Power-status monitoring is useful in industrial environments because an abnormal supply condition may affect controller operation, communication, or field instrumentation.

5. Thermal and Electrical Protection

The 8913-PS-AC includes internal protection features intended to support reliable operation. These include input protection and thermal protection.

When operating conditions exceed the specified thermal limits, output power may be reduced. Proper cabinet ventilation and load management are therefore important.

The power supply’s protective functions do not replace upstream circuit protection, grounding, or the electrical safeguards required by the installation.

Role in Industrial Control Systems

The 8913-PS-AC serves as a power-distribution component within a process automation architecture. It supplies the DC power needed by compatible system electronics and field devices.

PAC8000 and MTL8000 System Power

The module is associated with PAC8000 and MTL8000 process I/O platforms. In these systems, power supplies work alongside controllers, bus interface modules, I/O modules, carriers, and field terminals.

The 12 V output supports compatible system electronics, while the 24 V output provides auxiliary field power.

Correct power allocation helps maintain stable operation across the distributed I/O installation.

Remote I/O Power Distribution

Remote I/O stations are often installed near field equipment rather than inside the main control room. These stations require suitable electrical power for their internal electronics and connected devices.

The 8913-PS-AC can provide the required DC supply rails in a compatible system arrangement. Engineers must calculate the total connected load and confirm that both output channels remain within their ratings.

Integration with DCS and PLC Architectures

A distributed control system or PLC-based architecture may include multiple power supplies serving different equipment groups.

The 8913-PS-AC does not replace the controller or perform control logic. Its function is to provide the electrical power required by compatible process I/O equipment.

Power supply status may be incorporated into the wider monitoring strategy through compatible diagnostic connections or system-level monitoring equipment.

Redundant Power Architecture

For applications where power continuity is important, compatible redundant power arrangements can help reduce the risk of system interruption caused by an individual supply failure.

The redundancy design must include appropriate wiring, load-sharing provisions, monitoring, and maintenance procedures.

Industrial Applications

The 8913-PS-AC is designed for industrial process automation environments where separate system and field power rails are required.

1. Oil and Gas Processing

Oil and gas facilities use distributed instrumentation and remote I/O to monitor process conditions across production and processing areas.

The 8913-PS-AC can provide power to compatible process I/O equipment and field instrumentation within a suitable system configuration.

Its hazardous-area approvals and installation conditions must be checked against the actual site classification before use.

2. Chemical and Petrochemical Plants

Chemical plants use sensors, transmitters, valves, and other field devices to monitor and control process operations.

A dual-output power supply can support compatible control electronics and auxiliary instrumentation circuits. Stable power distribution helps maintain the operation of connected automation equipment.

3. Water and Wastewater Treatment

Water treatment facilities use distributed control equipment to monitor pumps, valves, flow meters, pressure transmitters, and other instruments.

The 8913-PS-AC may be used in compatible remote I/O installations where separate system and field power rails are required.

4. Industrial Process Monitoring

Manufacturing and process facilities often deploy remote instrumentation across multiple equipment areas.

A suitable dual-output power supply can provide the DC power required by process I/O hardware and connected field devices.

5. Hazardous-Area Automation

Certain versions and approved installation arrangements are designed for use in specified hazardous locations, including applicable Zone 2 or Class I, Division 2 environments.

The actual site classification, temperature code, enclosure requirements, and certification conditions must be checked before installation. Product approval does not mean the module can be installed in every hazardous location.

Installation and System Integration

Correct installation is essential for electrical safety, stable output voltage, and reliable operation.

1. Verify the Input Supply

Before installation, confirm that the incoming supply falls within the specified 85–264 V AC range.

Check the supply frequency, input protection, wiring, and grounding requirements. Although the datasheet also identifies a DC input capability, the actual installation must follow the approved connection arrangement for the unit.

2. Confirm the Mounting Arrangement

The supplied listing dimensions are 154 × 36 × 120 mm. However, the published MTL datasheet lists a different mechanical size.

Before preparing the mounting panel, verify the exact unit, connector arrangement, and mechanical drawing. Allow sufficient space for wiring access, ventilation, and maintenance.

The module should be mounted using the compatible DIN rail or system mounting arrangement specified for the installation.

3. Connect the DC Outputs Correctly

Identify the system-power and field-power terminals before connecting equipment.

The nominal output rails are:

  • Approximately 12 V DC at 5 A for system power.
  • Approximately 24 V DC at 5 A for auxiliary field power.

Check polarity, terminal assignments, cable sizing, and total connected current. Do not exceed the permitted output ratings.

4. Design Redundancy Carefully

When two power supplies are used for redundancy, follow the manufacturer’s specified wiring and load-sharing arrangement.

The 12 V output supports the documented load-sharing function. Do not assume that both outputs can be connected in parallel using the same method.

Confirm the system carrier, wiring accessories, and monitoring arrangements before commissioning.

5. Provide Adequate Cooling

The module is designed for an industrial operating temperature range, but its actual performance depends on ambient temperature, output loading, and ventilation.

Avoid obstructing airflow around the power supply. Excessive temperature may cause output power reduction and affect system reliability.

6. Test Before Operation

After installation, verify input voltage, DC output voltage, polarity, grounding, and connected load.

Check the status indicator and power-failure signalling function where applicable. If the module is part of a redundant arrangement, test the system response to an individual power supply failure according to the approved maintenance procedure.

Compatible System Components

The 8913-PS-AC is intended for use with compatible process I/O hardware and field instrumentation.

Component Function Integration Considerations
PAC8000 Process I/O system Distributed process control and I/O platform Verify system hardware and power compatibility
MTL8000 Process I/O Process I/O platform associated with the power supply Confirm the correct carrier and system configuration
Controller or Bus Interface Module Manages communication and process data exchange Check the required system power and carrier arrangement
I/O Modules Connect field signals to the control system Verify voltage and current requirements
Field Transmitters Measure process variables Confirm compatibility with the 24 V DC auxiliary supply
DIN Rail or Mounting Carrier Provides mechanical support Match the exact module mounting arrangement
Redundant Power Supply Provides an alternative supply path Follow the approved load-sharing and wiring design
Field Terminals Connect external instrumentation wiring Check terminal assignments and current capacity
Circuit Protection Protects the power supply and connected circuits Select according to electrical design requirements

The components listed above are examples of equipment that may be used in a compatible installation. They are not necessarily included with the power supply.

Alternative Models and Replacement Considerations

When replacing an 8913-PS-AC, the most important requirement is matching the electrical outputs and system compatibility.

Alternative or Related Product Consideration
MTL 8913-PS-AC Exact model replacement; verify hardware revision and condition
MTL 8914-PS-AC Related field power supply model; output configuration differs and must be checked
Compatible PAC8000 power supply May be considered where the system architecture and electrical requirements match
Compatible MTL8000 power supply Verify output voltage, current, mounting, and redundancy functions
Industrial dual-output DC power supply Requires a detailed engineering review before substitution

Before selecting a replacement, compare:

  • Input voltage and frequency range.
  • System output voltage and current.
  • Field output voltage and current.
  • Redundancy and load-sharing requirements.
  • Input-to-output isolation.
  • Power-failure signalling.
  • Thermal operating range.
  • Hazardous-area approvals.
  • Mechanical dimensions and mounting arrangement.
  • Connector and terminal assignments.

A power supply with the same nominal output voltage may not be a suitable replacement if its output current, isolation, monitoring, or system compatibility differs.

Key Advantages

Dual DC Output

The module provides separate system and field power outputs, supporting compatible process I/O and instrumentation requirements.

Wide AC Input Range

The 85–264 V AC input range allows the module to operate across a broad range of industrial supply conditions.

Redundancy Support

The documented load-sharing provision on the 12 V output supports suitable redundant power supply arrangements.

Industrial Environmental Capability

The specified operating temperature range supports use in demanding industrial environments when installation conditions remain within the product limits.

Electrical Isolation

The module provides specified input-to-output isolation, helping separate the incoming supply from its DC output circuits.

Power Status Monitoring

The supply health indicator and power-failure signalling function help maintenance personnel identify abnormal supply conditions.

PAC8000 and MTL8000 Integration

Its association with these process I/O platforms makes it relevant to maintenance and replacement projects involving compatible distributed automation systems.

Technical FAQs

1. What is the GE 8913-PS-AC?

The 8913-PS-AC is a dual-output industrial AC power supply associated with the MTL8000 and PAC8000 process I/O platforms. It converts a wide-range input into separate DC outputs for system electronics and field instrumentation.

2. What is the input voltage range?

The documented AC input range is 85–264 V AC, with an input frequency range of 47–65 Hz.

3. What are the output voltages?

The module provides approximately 12 V DC and 24 V DC outputs. The datasheet specifies approximately 11.95 V DC ±5% and 24.7 V DC ±10%.

4. What is the output current rating?

Each output is rated at a nominal 5 A, subject to the manufacturer’s operating conditions and derating requirements.

5. Can the 8913-PS-AC support redundant operation?

Yes. The module supports specified redundancy arrangements when paired with a compatible second power supply. The internal load-sharing provision is associated with the 12 V output. Follow the manufacturer’s wiring instructions.

6. Is this module compatible with PAC8000 systems?

It is associated with PAC8000 process I/O systems. Confirm the exact carrier, system configuration, and electrical requirements before installation.

7. Can it be used in hazardous areas?

The product documentation identifies approvals or installation provisions for specified hazardous locations, including applicable Zone 2 and Class I, Division 2 conditions. Always verify the exact certification and site requirements before installation.

8. What is the operating temperature range?

The documented operating ambient temperature range is -40°C to +70°C. The maximum operating case temperature is +80°C.

9. Does the module provide power-failure monitoring?

Yes. It includes a power-failure signalling function associated with the system output, allowing compatible monitoring equipment to detect supply abnormalities.

10. What should be checked before purchasing?

Verify the complete model number, physical condition, output ratings, connector condition, mounting arrangement, and availability of test information. For replacement applications, compare the unit against the existing system’s electrical and mechanical requirements.

Procurement and Maintenance Recommendations

When purchasing the 8913-PS-AC, confirm that the model number matches the existing installation. The product is associated with MTL8000 and PAC8000 process I/O equipment, so compatibility should be checked against the actual system architecture rather than relying on a generic description of an AC power supply.

For new-old-stock, used, or refurbished units, request clear photographs of the nameplate, connectors, and housing. Confirm whether the module has been functionally tested and whether its output voltages and power-failure signalling have been checked.

During routine maintenance, inspect the power supply for abnormal temperature, damaged connectors, loose wiring, and signs of contamination. Maintain adequate ventilation and monitor the DC output voltages under normal operating load.

For redundant systems, verify that both power supplies are operating correctly and that the load-sharing arrangement follows the manufacturer’s instructions. Record the wiring and output measurements so that future replacement work can be completed accurately.

Before replacing the unit with another power supply, compare the input range, both output ratings, isolation, monitoring functions, mounting arrangement, and hazardous-area requirements. A general-purpose 24 V power supply is not necessarily a suitable substitute for this dual-output module.

Conclusion

The GE 8913-PS-AC is an industrial dual-output power supply associated with MTL8000 and PAC8000 process I/O systems. It accepts an 85–264 V AC input and provides approximately 12 V DC and 24 V DC outputs, each rated at 5 A nominal.

Its dual-voltage architecture, redundancy support, power-failure signalling, and industrial operating range make it relevant to process automation and distributed I/O applications.

For maintenance and replacement projects, verifying the exact model, output configuration, mounting dimensions, and system compatibility is essential. Proper installation and regular inspection help maintain stable power distribution for connected control equipment and field instrumentation.



Related Products

Get the latest price? We will reply as soon as possible (within 12 hours)

No:77501