This module pairs the core signal-conditioning unit (163179‑01) with the non‑isolated input/output board (133819‑01), producing a six‑channel temperature monitoring module. It supports both RTDs and thermocouples and integrates seamlessly into the 3500 Rack System. Configurable alarm thresholds provide early detection of thermal anomalies for rotating equipment, electrical apparatus, and process components.
| Parameter | Details |
|---|---|
| Model | 3500/60 (163179‑01 + 133819‑01) |
| Number of Channels | 6 (RTD or Thermocouple, per channel) |
| Input Types | RTD (2‑ or 3‑wire), Thermocouple (Types J, K, T, E, R, S, B, etc.) |
| Input Impedance | Greater than 10 GΩ |
| Accuracy | Typically ±1 °C (sensor dependent) |
| Resolution | Approximately 0.1 °C |
| Alarm Functionality | Two levels per channel: Alert and Danger |
| Power Supply | Via 3500 Series Rack Backplane |
| Operating Temp | –30 °C to +65 °C |
| Storage Temp | –40 °C to +85 °C |
| Maximum Humidity | 0–95% RH, non‑condensing |
| Dimensions (mm) | 241.3 (H) × 24.4 (W) × 163.1 (D) |
| Weight | ≈0.9 kg (module with I/O board) |
| Isolation | Channel-to-channel: None (non‑isolated I/O) |
| Certifications | Industrial CE, CSA, ATEX/IECEx Zone 2 capable |
Rotating Equipment: Monitor bearing, gearbox, and motor winding temperatures in turbines, compressors, generators.
Process Equipment: Protect pressure vessels, heat exchangers, and reactors from thermal excursions.
Pumps and Gearboxes: Detect early temperature rises indicating lubrication issues or wear.
Electrical Components: Track enclosure and control panel temperatures to prevent thermal stress.
Manufacturing Lines: Integrate into centralized condition monitoring for thermal trend analysis.
Multi‑Sensor Compatibility: Supports both RTD and thermocouple sensors on all channels.
Compact Design: Six temperature channels in a single rack slot—maximizing efficiency.
Custom Alarm Levels: Dual setpoints per channel allow graded response before failure.
Industrial‑Grade Construction: Built to survive vibration, electrical interference, and extreme conditions.
Rack‑System Integration: Fully compatible with 3500 System architecture for easy expansion.
| Model | Description |
|---|---|
| 3500/61 | Temperature module with recorder (4‑20 mA) output |
| 3500/65 | Dual Keyphasor/tachometer input module |
| 3500/50M | Dual tachometer input module |
| 3500/42M | Proximity displacement monitoring module |
| 3500/53M | Dual overspeed detection module |
3500-TIV-CPU — Rack CPU providing trending, alarms, and communication.
3500/22M — Dual‑channel shaft displacement monitor.
3500/44M — Compact vibration monitoring.
3500/33 — High-density relay output module.
3500/15 — Rack power supply unit.
Q1: Can the module support mixed sensor types?
A1: Yes—each of the six channels may be individually programmed for either RTD or thermocouple inputs.
Q2: Is there channel-to-channel isolation?
A2: No—the 133819‑01 I/O board is non‑isolated. If needed, an isolated version must be selected.
Q3: What is the module’s weight and dimension?
A3: It weighs approximately 0.9 kg and measures 241.3 × 24.4 × 163.1 mm (H×W×D).
Q4: What alarm features are included?
A4: Each channel can be set with two thresholds: “Alert” (warning) and “Danger” (critical).
Q5: What condition environments can it withstand?
A5: Rated for –30 °C to +65 °C and up to 95% non‑condensing humidity.
Q6: Is it hot-swappable?
A6: No—standard safety practice requires powering down the rack before installation or removal.
Q7: How precise is the temperature reading?
A7: Usually accurate within ±1 °C, with fine resolution around 0.1 °C.
Q8: Can this join redundant setups?
A8: Yes—multiple modules can be deployed to form redundant temperature protection schemes.
Q9: Which industries commonly use this module?
A9: Turbine generators, petrochemicals, oil & gas, marine, and manufacturing process control.
Q10: Is the design safety-compliant?
A10: Yes—it conforms to industrial CE standards and is suitable for use in hazardous zones (e.g., ATEX/IECEx Zone 2).
Authenticity guarantee
All product specifications are original and authentic imported products. We have an annual sales volume of 300 million yuan, and we only produce original and authentic products. All customers who cooperate with us directly online can enjoy low discounts.
Free warehouse
We have a complete range of product models, 80% of conventional models are in stock, and we have established channels in Asia, Africa, North America, South America, and Europe, effectively shortening the order processing time and satisfying customers in a timely manner.
Technical Team
Fast delivery. Spot goods can be shipped on the same day, and the delivery time transaction is 20% faster than that of peers on average, with a delivery time accuracy rate of 99%.
Thoughtful after-sales service
24-hour after-sales service guarantee team, professional and standardized management service system.